LUTRON URMJS-8T-DV-B Dimming Module Installation Guide
- June 8, 2024
- Lutron
Table of Contents
LUTRON URMJS-8T-DV-B Dimming Module
Installation
-
RMJS-8T-DV-B 120 / 277 V~ 50 / 60 Hz 8 A
URMJS-8T-DV-B
RMJS-8TN-DV-B -
RMJS-8T-DV-B-EM 120 / 277 V~ 50 / 60 Hz 8 A
-
0 –10 V- Control: 10 V- 60 mA
UL 2043 Plenum Rated
Compatible with ANSI E1.3 2001 (R2006), IEC 60929 Annex E
Note for Replacement:
RMxS and URMxS – the “S” model can replace the non-“S” model
Important Notes: Please read before installing.
For installation by a qualified electrician in accordance with all local and
national electrical codes (including periodic testing and maintenance of
emergency systems).
- Note: Use copper conductors only.
- Check to see that the device type and rating is suitable for the application.
- DO NOT install if product has any visible damage.
- If moisture or condensation is evident, allow the product to dry completely before installation.
- Operate between 32 °F and 104 °F (0 °C and 40 °C) ambient.
- 0% to 90% humidity, non-condensing.
- For indoor use only.
All Wireless Transmitters must be installed within 30 ft (9 m) of the PowPak Dimming Module with 0 –10 V-.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
- Do not use outdoors.
- Do not mount near gas or electric heaters.
- Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS
Required Components
For each system, ensure that you have:
-
One PowPak Dimming Module
PowPak Dimming Module with 0 –10 V- (1 maximum) -
At least one Wireless Transmitter
Radio Powr Savr Occupancy / Vacancy Sensor (10 maximum) -
Pico Remote Control (10 maximum)
-
Radio Powr Savr Daylight Sensor (1 maximum)
Start Here
Mount, Wire, and Install 0 –10 V- Devices and Lighting Fixtures
Consult third-party device installation guide
WARNING! Shock Hazard. May result in serious injury or death. Turn off
power at circuit breaker before installing the unit.
- Connect mains wiring (switched hot, neutral) to each fixture.
- Connect 0 –10 V- control (+ and – ) to each fixture.
Install PowPak Dimming Module with 0 –10 V-
Suggested Installation Location: Center of room to ensure proper RF coverage
of area.
- PowPak Dimming Module with 0 –10 V- can be installed on a junction box or marshalling box using the conduit nut (provided) or with mounting screws (not provided). The device must NOT be mounted inside a fixture or other metallic enclosure – only on the exterior of a fixture. Please consult local and national electric codes for proper installation. If installing unit inside a junction box, please see Application Note #423 (P/N 048423 at www.lutron.com).
- Once installed, energize the PowPak Dimming Module with 0 –10 V-.
- Use the Toggle button “ u” to toggle between high-end and OFF to verify ballast wiring.
- Use the Raise “▲” and Lower “Δ” buttons to verify control wiring.
Programming with a Vive Hub
-
Use an iOS® or Android® compatible device.
-
Download the Lutron Vive app.
-
Open the app and follow the instructions.
Note: For further information on set up, programming, and troubleshooting
with a Vive system, please refer to the installation instructions included
with the Vive hub or visit www.lutron.com/vive
Note: For programming the PowPak Dimming Module without a Vive hub see
reverse side.
At least one 0 –10 V- Fluorescent Ballast or LED Driver
Consult third-party 0 –10 V- fixtures installation guide for fixture-specific
wiring.
For mounting and wiring best practices see Lutron Application Note #620 (P/N
048620).
60 mA maximum for the control lines. Switches up to 8 A total.
May be pre-installed in light fixture.
Note: All drivers and ballasts used with Vive wireless controls must
comply with the limits for a Class A device, pursuant to Part 15 of the FCC
rules.
RMJS-8T-DV-B-EM
-
- Use 18 AWG to 16 AWG (0.75 mm2 to 1.5 mm2) solid wire only
- Note: For periodic testing and maintanance of emergency systems, use the toggle button of the RMJS-8T-DV-B-EM to ensure proper operation. Make sure PowPak buttons remain accessible.
- Note: Momentary power outages can envoke emergency mode on the dimming module. See Troubleshooting section for details.
Default Functionality
- Wireless Controls: All lights
- On: 100% ; Favorite: 50%; Off: 0%
Occupancy Sensors
- Occupied: All lights100% ; Unoccupied: All lights off
Daylight Sensor
- All lights dim in response to daylight.
Part of the Vive Family Start Here
Associate Wireless Transmitters to PowPak Dimming Module with 0 –10 V-
Before beginning this step, make sure that there are no other PowPak modules
being set up within the same building. It is possible that wireless
transmitters from other systems can be incorrectly associated to this module.
-
On PowPak Dimming Module with 0 –10 V-, hold Toggle button “ u” for 6 seconds until lights flash.
The Load Status LED will begin flashing twice per second. -
Hold the indicated button on each transmitter for 6 seconds. Lights will flash to show that wireless transmitters have been associated.
-
On PowPak Dimming Module with 0 –10 V-, hold Toggle button “ u” for 6 seconds to save association. Lights will flash and LED will quickly blink for 2 seconds.
-
Permanently install wireless transmitters (consult individual component installation guides for information).
Reset Factory Defaults
Note: In some instances, it may be necessary to reset the PowPak Dimming Module with 0 –10 V- and connected devices back to factory default settings. Before beginning, make sure that all devices are connected and powered.
- Rapidly tap the Toggle button “ u” on the PowPak Dimming Module 3 times and hold on the fourth time until the LED begins to flash at a rate of approximately 2 blinks every 1 second; then release the Toggle button “ u” .
- Within 3 seconds of the start of flashing of the LED on the PowPak, rapidly tap the Toggle button “ u” on the PowPak Dimming Module 3 times again. Make sure to release the Toggle button “ u” after the third press.
- The LED will flash at a rate of 2 blink every 3 seconds and the connected load will cycle 3 times to indicate the unit has been reset to factory defaults.
Note: Any associations or programming previously set up with the PowPak will be erased and will need to be re-programmed.
Calibrate the Radio Powr Savr Daylight Sensor
Daylight Sensor will control all wired fixtures equally.
-
Press and release the “Cal.” button on the Daylight Sensor.
-
Test B Set lights in room to desired light level.
-
Press and hold the “Cal.” button for 6 seconds.
-
Exit room for 5 minutes to complete calibration.
Note: When calibration has completed, all lights will flash and begin to respond to daylight.
Multiple Daylight Rows (Optional)
For every row of daylighting a separate PowPak Dimming Module with 0 –10 V- must be used. For detailed setup refer to the tuning section of the Radio Powr Savr Daylight Sensor installation guide. -
Select the PowPak Dimming Module with 0 –10 V- that you want to adjust by pressing the toggle button.
Set a Favorite Light Level (Optional)
For Pico remote controls with a Favorite button.
-
Adjust lights to desired level:
Use the Raise button “ ” or Lower button “ ” on the Pico remote control. -
Save favorite level:
Press and hold the Favorite button for 6 seconds. The load will flash 3 times to confirm that the Favorite level is saved.
Set Low-End Trim and High-End Trim (Optional)
For best results, minimize the amount of sunlight entering the room before
performing the following procedures.
Notes Depending on the fixture manufacturer or load, low-end trim and high-end trim may need to be adjusted.
- Trim low-end to ensure a stable light level because some loads will flicker or drop out if trimmed too low.
- Be sure that you can turn on the lights to the low-end trim level without any abnormal operation.
- The factory default high-end trim is suitable for most applications but can be adjusted as desired.
Low-End Trim
-
Enter low-end trim adjustment mode:
Press and hold the Lower button “ Δ” on the fixture control for 12 seconds.
The lights will flash and the load status LED will begin flashing. -
Adjust the low-end trim:
Use the Raise button “▲” and Lower button “ Δ” on the fixture control to adjust and set the
lights to the desired low-end (1 to 45%). -
Save the low-end trim:
Press and hold the Toggle button “ u” for 6 seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
High-End Trim
-
Enter high-end trim adjustment mode:
Press and hold the Raise button “▲” on the fixture control for 12 seconds.
The lights will flash and the load status LED will flash. -
Adjust the high-end trim:
Use the Raise button “▲” and Lower button “ Δ” on the fixture control to adjust and set the
lights to the desired high-end (55 to 100%). -
Save the high-end trim:
Press and hold the Toggle button “ u” for 6 seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
Set Minimum Light Level (Optional)
Certain applications (e.g., hallways), may require that the lights never turn
off. For these areas, activate Minimum Light Level
mode.
-
A Enter minimum light level adjustment mode:
Press and hold Toggle button “ u” and Lower button “ Δ” for 12 seconds. Lights will flash high-low-high and LED will begin flashing.
If lights stop flashing and go to high-end, the minimum light level is set to OFF (default).
If lights stop flashing and go to low-end, the minimum light level is ON and set to low-end. -
Change the minimum light level:
Press Raise button “▲” to set minimum light level to low-end.
Press Lower button “ Δ” to set minimum light level to OFF. -
Save the minimum light level:
Press and hold Toggle button “ u” for 6 seconds. LED will quickly flash to indicate that new level has been saved.
Set Occupancy Light Levels (Optional)
Note: Unoccupied light level is always the minimum light level and cannot
be adjusted.
-
A Set desired occupancy light levels:
Use the Raise/Lower buttons “▲ / Δ” on the PowPak Dimming Module with 0 –10 V- or the Raise/Lower buttons “ / ” on all associated Pico Remote Controls to dim the lights to the desired level. Note: Setting lights to OFF during this step will make that control module unaffected by occupancy (will function as vacancy only). -
B Save occupancy light levels:
Press and hold Test button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor without a Lights On
button. Release when the sensor lens starts to flash. Or, press and hold Lights On button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor. Release when the sensor lens starts to flash.
Troubleshooting
Ballasts cannot be controlled locally from PowPak Dimming Module with 0 –10 V-.
| • Ensure that the breaker(s) to the PowPak Dimming Module with 0 –10 V- are energized.
• Ensure that the PowPak Dimming Module with 0 –10 V- switched hot lead is wired to the lighting fixture(s).
• Ensure that the PowPak Dimming Module with 0 –10 V- control lines are wired to the lighting fixture(s).
---|---
Reset to factory defaults.
Lights do not dim as expected.| • Ensure that 0 –10 V- control lines are
wired properly.
• Ensure that fixture does not require an inverted signal (10 – 0 V- control).
Lights do not respond to Wireless Transmitter(s).
| • Ensure that the breaker(s) to the PowPak Dimming Module with 0 –10 V- and ballasts are energized.
• Ensure that Wireless Transmitters are associated to the PowPak Dimming Module with 0 –10 V-.
Reset to factory defaults.
Lights are unstable at low-end or flash/flicker at turn-on or turn-off.| •
Adjust low-end trim.
Wireless Transmitter(s) cannot be associated to PowPak Dimming Module with 0
–10 V-.| • The maximum number of Wireless Transmitters have been associated
to the PowPak Dimming Module with
0 –10 V-. To remove a previously set up Wireless Transmitter, tap a Wireless Transmitter button three times; on the third tap hold for three seconds and then tap three more times.
PowPak is in emergency mode (RMJS-8T-DV-B-EM only).| • In systems with a Vive hub: Contact Lutron Customer Assistance for further details.
• In systems without a Vive hub: Wait 90 minutes for the PowPak to return to normal operation.
PowPak will not go into emergency mode(RMJS-8T-DV-B-EM only).| • Contact Lutron Customer Assistance for further details.
Customer Assistance:
U.S.A., Canada, and the Caribbean: 1.844.LUTRON1
Mexico: +1.888.235.2910
Brazil: +55.1.3257.6745
Central / S. America: +1.610.282.6701
Other Countries: +1.610.282.3800
www.lutron.com/support
Limited Warranty:
www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
For FCC/IC information: Please visit: www.lutron.com/fcc-
ic
Lutron, Pico, PowPak, Radio Powr Savr, and Vive are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. All other product names, logos, and brands are property of their respective owners. ©2013-2022 Lutron Electronics Co., Inc.
References
- Vive Reconnect | Lutron
- lutron.com/fcc-ic
- Lutron Support Center | Lutron
- Vive - Commercial Wireless Lighting Control System | Lutron