allgood 9151ADC Delayed Action Overhead Door Closer Instructions

June 9, 2024
allgood

lgood 9151ADC Delayed Action Overhead Door Closer Instructions

Instruction

  • Delayed action allows the door to remain open for an adjustable period of time, before closing.

  • The delayed function operates from fully open down to 75° in figure 1.

  • The delay speed can be adjusted – for example: the closer is adjusted to give 20 seconds of delay between 90 and 75°, however, if the door is opened to 100° the delay would be in the region of 30 seconds and if the door were only opened to 80°, the delay would be in the region of 10 seconds.

  • Longer or shorter delay times can be achieved by adjustment shown below

  • In figure 6 delay operates from fully open down to 85°.

  • If the angle of opening is restricted to 90° or less, no delay may be evident.

  • To overcome this, move the closer and the bracket 100mm further from the hinge side. This will also restrict the angle of opening.
    Overview

  • Set grey outer control with the mark towards the green zone (as shown)

  • Open door to 45 degrees to set closing speed with brass inner control

  • Open door to 90 degrees plus to set delay time, for longer delay turn brass inner control one full turn at a time clockwise, for shorter delay turn one full turn at a time anti-clockwise

  • If latch action is required, move the red outer control into the black zone

  • If delay is not required, move the red outer control into the red zone

Allgood Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

allgood User Manuals

Related Manuals