Fixing Instructions for
XX9328 Motorised Touchbar surface-mounted latch device
XX9329 Motorised Touchbar surface-mounted vertical rod panic bolt
FIXX9328
Issue 03 – 09/2020

9328 Motorised Touchbar Surface-Mounted Latch Device

Please ensure the formula for reduction of aluminium profiles is followed accurately.

allgood 9328 Motorised Touchbar Surface Mounted Latch Device - Fig
2

IMPORTANT:

Before the fitting of Outside Access Device (OAD) or Outside Access Key Switch (KS) onto a door it is important to establish the correct position of the centre mechanism and appropriate striker.
For OAD or KS see seperate fitting instructions

allgood 9328 Motorised Touchbar Surface Mounted Latch Device - Fig
4

Measurement Z varies depending on recessed, flush or stepped applications. This measurement should be established before holes are drilled into door section
For reductions of less than 160mm cut touch bar L1 and housing L3 down to size using formula (A) For reductions over 160mm it will be necessary to reduce internal connecting bar L2 using formula (B) This formula is only for the 1170/1300mm sizes

Cut aluminium profiles using a circular saw.

After completing the cutting of components, re-assembly centre mechanism to the housing, internal connecting bar and touch bar.

allgood 9328 Motorised Touchbar Surface Mounted Latch Device - Fig
4

Ensure fixing screws are securely fixed to the door material. For all glazed aluminium doors, housing bracket HB should extend across to the vertical section of door. Alternatively housing bracket HB can be fixed to midrail. Insert the wiring through hole in centre into door section.

End cap components I & II can now be secured using screws provided

Component Qty
2

| 6

Fix centre mechanism onto door at appropriate height.
The touch bar should be positioned between 900 – 1100mm from FFL ensuring good contact with centre striker.
For flush applications the strike should be mounted on frame as shown. 1mm packers are provided with each striker
For stepped applications 4 – 8mm the strike can be rotated 180° as shown here.
For recessed situations the PH4303 should be turned 90 degrees to door face as shown – see page 4 (strike applications)

****0425 – 1520 – 11 Allgood plc 68-83 Brearly Street Birmingham B19 3NT
EN1125: 2008 3-7-7-B-1-4-2-2-B-A

The safety features of this exit device are of fundamental importance to ensure its compliance with standard EN1125:2008
No modifications of any kind to the device other than those described in the fitting instructions are permitted.
This panic device may be fitted to fire or smoke door assemblies.

Fix the centre mechanism of touchbar onto door section at appropriate height (touch bar should be positioned between 900 – 1100mm from FFL) ensuring good contact with centre striker if required.
Fix top and bottom pullmans ensuring good contact with top and bottom strikers.
Cut threaded rods to size (X + 25mm & Y + 25mm) Insert threaded rod B into connector A with lock-nuts C as shown. Push RG rubber grommets over thread (2 per rod) Insert threaded rod into riv-nut D of pullman latch and rotate. Push connector A over bush of centre mechanism as shown. Insert M4 screws E to secure connector in place After final adjustments of rods are made, secure all lock-nuts making sure that all of the connections are tight. Care should be taken to ensure any lost motion is prevented by adjustment of threaded rods and lock-nuts.
Length of threaded rods:
X + 25mm
Y + 25mm
Length of rod covers:
X – 1.5mm
Y – 1.5mm

allgood 9328 Motorised Touchbar Surface Mounted Latch Device -Icon
10

Floor strikers should be mounted on floor as shown. If aluminium low threshold strips are used the striker should be notched into aluminium section to comply with current legislation.

allgood 9328 Motorised Touchbar Surface Mounted Latch Device - Fig
9

IMPORTANT: Before the fitting of an Outside Access Device onto a door it is important to establish the correct position of the centre mechanism and appropriate strikers.

Ensure rubber washers RG are pushed over threaded rods to prevent any vibration or rattle.

Component Qty

| 14
| 6
A| 2
C| 2
E| 2
BP| 1
RG| 4
****0425 – 1520 – 11| Allgood plc 68-83 Brearly Street Birmingham B19 3NT
---|---
EN1125: 2008| 3-7-7-B-1-4-2-2-B-A

The safety features of this exit device are of fundamental importance to ensure its compliance with standard EN1125:2008
No modifications of any kind to the device other than those described in the fitting instructions are permitted.
This panic device may be fitted to fire or smoke door assemblies.

Fix the centre mechanism of touch bar onto door section at appropriate height (touch bar should be positioned between 900 – 1100mm from FFL) ensuring good contact with centre strike. Fix top and bottom pullmans ensuring good contact with top and bottom strikers.
Cut threaded rods to size (X + 15mm & Y + 15mm) Insert threaded rod B into connector A with lock-nuts C as shown. Push RG rubber grommets over thread (2 per rod) Insert threaded rod into riv-nut D of pullman latch and rotate. Push connector A over bush of centre mechanism as shown. Insert M4 screws E to secure connector in place After final adjustments of rods are made, secure all lock-nuts making sure that all of the connections are tight. Care should be taken to ensure any lost motion is prevented by adjustment of threaded rods and lock-nuts.
Length of threaded rods:
X + 15mm
Y + 15mm
Length of rod covers:
X – 1.5mm
Y – 1.5mm
For flush situations strikes should be mounted on frame as shown above. 1mm packers are provided with each striker.
For stepped applications 4 – 8mm the strike can be rotated 180° as shown here. Also see strike applications on page 4 for typical applications.

allgood 9328 Motorised Touchbar Surface Mounted Latch Device - Fig
8

Cut rod covers to size (X – 1.5mm & Y – 1.5mm) Push pullman covers into groove as shown.Position on door and push mechanism over to hold in place
IMPORTANT: Before the fitting of an Outside Access Device  onto a door it is important to establish the correct position of the centre mechanism and appropriate strikers.

allgood 9328 Motorised Touchbar Surface Mounted Latch Device - Fig
12

Drawings are for guidance only

allgood 9328 Motorised Touchbar Surface Mounted Latch
Device

STRIKE APPLICATIONS

Typical door/frame sections showing correct use of strikers on recessed or flush applications.
Please note that position of the strike and latch will determine the centre line of holes for Outside Access Device. Strikes to suit other sections are also available.![allgood 9328 Motorised Touchbar Surface Mounted Latch Device

Floor strikes should be mounted on floor as shown. If aluminium low threshold strips are used the strike should be recessed into aluminium section to comply with current legislation.

allgood 9328 Motorised Touchbar Surface Mounted Latch Device - Fig
1

XX9320 Striker Applications
FIXX9328
Issue 03 – 09/2020
Recycle responsibly
T: 0121 359 4415
www.allgood.co.uk

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals