allgood 9456 Electromagnetic Overhead Door Instructions

June 9, 2024
allgood

allgood 9456 Electromagnetic Overhead Door

Installation Instructions

Installation Instructions

Fixing Instruction

Fit to template FT9456

Once the door closer has been installed and adjusted no further maintenance should be necessary. However, an annual check should ensure that:

  • The door leaf closes freely and positively into its frame from any angle without slamming.
  • Excessive force is not required by the user to open the door.
  • All fixings are tight.
  • The hexagon bolt is tight.
Testing (before power is supplied)
  • Open the door leaf to its maximum opening angle and release. The door leaf should close fully into the door fame and overcome the latch.
  • Open the door leaf and rest the latch bolt on the striker plate. Release the door leaf. The door closer should have sufficient power to latch the door leaf closed.

Any failure to close the door into the frame should be investigated. It may indicate that the door closer is undersized or that excessive force is required to close the door due to distortion or misalignment.

Warning

This door closer contains a powerful spring which Is inserted into the body under pressure. Under no circumstances should attempts be made to dismantle a door closer!

Testing (when power is supplied)
  • Open the door leaf to at least 80° and ensure that the door hold open.
  • Gently pull the door to check that the door can be manually pulled off hold.
  • Open the door leaf to the hold position i.e. greater than 80° and test the release by pressing the black button which is located between the LEDs or by other emergency power shut down mechanism.

Certifire Conditions of use Reference CF104

This approval relates to the use of the door closer model with the following door assemblies:

a. Latched and unlatched, intumescent sealed door assemblies consisting of timber faced and edged leaves with timber, cellulosic or mineral cores in timber frames and having fire resistances of between 20 minutes and 120 minutes (Code ITT)
b. Latched and unlatched, intumescent sealed door assemblies consisting of timber faces and edges leaves with timber, cellulosic or mineral cores in metal frames and having fire resistances of up to 30 minutes (Code ITM30)

Closer adjustment

Latch Speed – outer control

“Off” as drawn. Rotate ½ a turn towards ‘latch’ to turn “on”.

Latch Speed – inner control

Rotate clockwise to reduce closing speed (Do not open valve past leading edge of outer ring).

Latch Mix

Power Supply

Electro-magnetic door closers can have power supplied by the: 9471 armoured lip or 8066T2/8066T8 power transfer hinge.

  • The loop slots into the power conditioning module.
  • The block should be fixed to the door frame and then connect to an appropriate 24V DC power supply.

Size 3, suitable for doors up to 950mm wide and 60kg.

Ce Symbol

**Recycle  Responsibly

**

Customer Support

www.allgood.co.uk

allgood  Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals