SOLAX POWER X3 3 Phase Inverter Installation Guide
- June 9, 2024
- SOLAX POWER
Table of Contents
- SOLAX POWER X3 3 Phase Inverter
- Packing List
- Tool Preparation
- Mounting Steps
- PV Connection
- Grid and EPS(Off-grid) Connection
- Battery Connection
- Communication Connection (BMS/Meter/CT/COM/DRM)
- Monitoring Operation
- Start Guide
- Start Inverter
- Firmware Upgrading
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SOLAX POWER X3 3 Phase Inverter
Packing List
Note: “ ☆ ”attachments are not included in the M series inverter attachment package and will be included in the X3-Matebox. The inverter in Australia needs to be connected to DRM, which is 1 more communication line adapter than that in other countries. The number of “D” and “E” are different for different power sections. For 5-6kW inverters, the number of positive and negative PV terminals and PV pin angle is 2, 2, 2, and 2 respectively. For 8- 15kW inverters, the number of positive and negative PV terminal and PV pin angles is 3, 3, 3, and 3 respectively.
Tool Preparation
Mounting Steps
- a) Use a marker to mark the drilling holes of the bracket on the wall.
- b) Drill holes at marked spots with a depth of 65 mm.
- c) Insert the expansion bolt into the hole, use a rubber hammer to knock the expansion screw bolt into the wall.
- d) The bracket is aligned with the screw uses the inner hexagonal wrench to screw the tapping screw until the expansion bolt “bang” is heard.
- e) Hang the buckle on the inverter to the corresponding position of the backplane.
- f) Use the inner hexagonal wrench to tighten the inner hexagonal screw on the right side of the inverter.
PV Connection
The PV port wiring of the M series inverter has been completed. For specific installation details, please refer to the X3-Matebox Quick Installation Guide, the D series needs to be wired according to the following steps.
- Step 1. Turn off the DC switch, connect the PV module, prepare a 4 mm² PV cable, and find the PV (+) terminal and PV (-) terminal in the package.
- Step 2. Use a wire stripper to strip the 7mm insulation layer of the wire end.
- Step 3. The PV connector is divided into 2 parts, to the plug and the fastening head. Pass the cable through the fastening head and the alignment plug. Note that the red and black lines correspond to different pairs of plugs. Finally, force the cable into the plug and hear a “click” to indicate that the connection is complete.
- Step 4. Tighten the fastening head and into insert the corresponding positive and negative (PV-/PV+) ports of the inverter.
Note:
Before inserting the PV terminal, please turn on the switch of the PV module,
and use a multimeter to measure the positive and negative poles of the PV
terminal port to prevent reverse connection.
Grid and EPS(Off-grid) Connection
- Diagram A: N line and PE line separate wiring, D series inverter; (For most countries)
- Diagram B: N line and PE line separate wiring, M series inverter; (For most countries)
- Diagram C: N line and PE line together, D series inverter; ( Applicable to Australia)
- Diagram D: N line and PE line together, M series inverter; ( Applicable to Australia).
Note: The RCD on the gure represents a leakage protection device with a
circuit breaker function.
The Grid and the EPS (Off-grid) ports of the M series inverter have been
connected, for specific installation details, please refer to the X3-Matebox
Quick Installation Guide. and the D series needs to be wired according to the
following steps.
Step 1.
Prepare a Grid cable (five-core wire) and an EPS(Off-grid) cable (four-core
wire), and then find the European terminal and waterproof cover in the
accessory bag.
Grid Cable and Micro-breaker recommended
EPS(Off-grid) Cable and Micro-breaker recommended
Step 2:
First remove the waterproof housing plug, The GRID and EPS(Off-grid) cables go
through the corresponding GRID and EPS(Off-grid) ports of the waterproof
cover. Remove the 12mm insulation layer at the end of the wire. Insert the
European-style terminals respectively, and make sure that the stripped ends
are inserted into the European-style terminal, and use crimping pliers to
press tightly. And locked in the Grid and EPS(Of-grid) ports respectively.
Finally, lock the waterproof cover screw.
Battery Connection
Battery connection diagram:
Note:
When using the battery, it is recommended to use the number of battery control
(T-BAT-5.8) is 1, the number of battery modules (HV11550) is 1-3; the number
of battery control (MC0600) is 1, the number of battery modules (HV10230) is
2-4.
Battery port connection line of the M series inverter is on the X3-Matebox, for specific installation details, please refer to the X3-Matebox Quick Installation Guide It is necessary to wire the D series according to the following steps.
Step 1.
Turn off the DC switch, connect the BAT module, prepare a 6 mm cable, and find
the BAT (+) terminal and BAT (-) terminal in the package.
Step 2.
Use a wire stripper to strip the 7 mm insulation layer of the wire end
.
Step 3.
The BAT joint is divided into 2 parts, to the plug and the fastening head.
Pass the cable through the fastening head and the alignment plug. Note that
the red and black lines correspond to different pairs of plugs. Finally, force
the cable into the plug and hear a “click” to indicate that the connection is
completed.
Step 4.
Tighten the fastening head and insert it into the corresponding positive and
negative (BAT-/BAT+) parts of the inverter.
- Note: BAT port (Blue one) not PV port(Black one)
- Note: The positive and negative wires of the battery are not allowed to be reversed!
Notice!
After the BMS communication between the battery and the inverter is finished,
the battery will work normally.
Communication Connection (BMS/Meter/CT/COM/DRM)
-
Electric meter connection diagram
Note: To connect the meter, please connect the GND terminal of Meter1 to the ground. -
CT connection diagram
-
LCD settings
To select CT, you need to enter Use setting, then enter CT/Meter Setting.
Meter/ CT PIN is defined as follows:
Note:
Only one of the Meter and CT connections can be selected. Meter cable goes to
pin terminal 4 and 5; the CT-R cable to PIN Terminals 1 and 8; the CT-S cable
to PIN Terminals 2 and 7; CT-T cable is connected to terminals 3 and 6.
- To connect the Communication line of the CT line, the lines need to be made on both sides, connecting the RJ45 terminal on one side and the Communication line Adapter on the other.
- One side of the finished cable, the Communication line adapter is inserted into the inverter, and one side of the RJ45 terminal is inserted into the CT connection.
Note:
When installing, pay attention to water resistance. All the connected parts of
CT must be put into the distribution cabinet.
COM Communication
Inverter communication control external equipment:
COM PIN Definition
Note:
Customers can communicate or control the inverter and external devices through
the COM interface. Professional users can use pins 4 and 5 to realize data
acquisition and external control functions. The communication protocol is
Modbus RTU. For details, please contact us. If the user wants to use the
inverter dry contact to control external equipment (such as a heat pump), it
can be used with our Adapter Box. For details, please refer to the Quick
Installation Manual of the Adapter Box.
The BMS pin is defined as follows:
Note: The communication port on the lithium battery must be consistent with the definition of pins 4, 5, 7, and 8 above;
The DRM pin is defined as follows:
Note:
Currently only PIN6 (DRM0) and PIN1 (DRM1/5) are functional, other PIN
functions are under development.
Communication Connection Steps
- Step 1. Prepare a communication cable, and then find the communication adapter in the accessory bag.
- Step 2. Remove the cover plate on the inverter and make the communication line.
- Step 3. Insert the communication cable through the communication adapter, and peel off the outer insulation layer of 15 mm.
- Step 4. Insert the prepared communication cables into the RJ45 terminals in sequence, and then use network cable crimping pliers to press them tightly.
- Step 5: Insert the communication line (CAN/DRM/OFF) into the corresponding port, lock the cover plate, and tighten the fastening head. Finally, the corresponding COM, METER, CT, and BMS can be found to insert the corresponding ports of the inverter communication cable.
And screw the communication adapter tightly.
Monitoring Operation
DONGLE connection diagram
Wireless monitoring accessories connection steps:The
DONGLE port connection line of the M series inverter is on the
X3-Matebox,for specific installation details, please refer to the X3-Matebox
Quick Installation Guide It is necessary to wire the D series according to the
following steps.
- Step 1. First find the DONGLE port of the inverter.
- Step 2. Plug Pocket WiFi into the DONGLE port.
Please check the Pocket WiFi user manual/Pocket LAN user manual /4G user manual for more details.
Start Guide
- Set date time
- Set language
- Set the safety standard
- CT/Meter Setting
- Set export control
- Set work mode
- External ATS
Export Control
This function allows the inverter able to control energy exported to the
grid. There are user value and factory value. The factory value is the default
which can not be charged by user. The user value set by the installer must be
less than the factory value.
Start Inverter
Start inverter
After the inverter is checked, the inverter will take the following steps :
- Make sure that the inverter is fixed on the wall.
- Ensure that all ground wires are grounded.
- Confirm that all DC lines and AC lines are connected.
- Make sure the CT are connected.
- Make sure the battery is well connected.
- Turn on the Load switch and EPS(Off-grid) switch Turn on the battery switch.
- Long press Enter for 5 seconds to exit the shutdown mode. Mode is the mode when it is turned off for the first time; factory default: off mode)
Firmware Upgrading
- In order to upgrade the firmware smoothly, if the DSP and ARM firmware needs to be upgraded, please note that ARM firmware must be upgraded first, then DSP firmware!
- Make sure that this directory is completely consistent with the above table, and do not modify the firmware file name, Otherwise, the inverter may not work!
- For the inverter, ensure that the PV input voltage is greater than 180V (upgrade on sunny days). please ensure that the battery SOC is greater than 20% or the battery input voltage is greater than 180V. Otherwise, it may cause serious failure during the upgrade process!
- If the ARM firmware upgrade fails or stops, please do not unplug the U disk power off the inverter, and restart it. Then repeat the upgrade steps.
Upgrade Preparation
- Please check the inverter version and prepare a U disk (USB 2.0/USB3.0) and personal computer before upgrading.
- Please contact our service support through service to obtain the firmware, and store the firmware in the U disk according to the following path.
Update:
- For ARM file: “update \ARM\618.00406.00_HYB_3P_ARM_V1.13_1220.usb”;
- For DSP file: “update\DSP\618.00405.00_HYB_3P_DSP_V1.14_1215.usb”;
Upgrade steps
- Step 1. Please save the “Update” firmware in your U disk first, and press the “Enter” button on the machine screen for 5 seconds to enter the shutdown mode. Then unscrew the waterproof cover, and insert the U disk into the “upgrade” port at the bottom of the inverter.
- Step 2. Find the “Upgrade” port of the inverter, unplug the monitoring module (Pocket WiFi/ Pocket 4G/Pocket LAN) by hand, and insert the USB flash drive.
- Step 3. LCD operation, enter the upgrade interface “update”, as shown below(a): Please press the up and down keys to select ARM, then press the bottom of the page to select “OK”, press the enter key to enter the software version interface;
- Step 4. Please confirm the new firmware version again and select the firmware to upgrade. The upgrade takes about 20 seconds. (d) When it is completed, the LCD screen returns to the “Update” page.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>