SOLAX POWER Inverter 60KW X3-Mega Three Phase Grid-Tie User Guide

June 5, 2024
SOLAX POWER

Quick Installation Guide
X3-Mega G2 20kW-60kW

Packing List

*Note: The double offset ring wrench in the accessory box is used to remove the screws on the front cover of the inverter. Keep it in a safe place

Mounting the inverter on the wall

  • Use the bracket as a template for marking the position of holes with a level and marker.

  • Drill the four holes with a Φ12 drill.

  • Depth: at least 65mm.

  • Hammer the M8x80 expansion screw into four holes.

  • Screw in the nut firmly with a socket wrench.

  • Lift up the inverter.

  • Two methods are available two installers or a lifting ring

  • Hang it onto the bracket

  • Fix it on the wall bracket with M8 bolts

Mounting the inverter on the stand

  • Use a bracket as a template for marking the position of the holes with a level and marker.

  • Drill the four holes with a Φ10 drill.

  • Screw in the corresponding screw into holes.

  • Tighten the nut firmly with a corresponding socket wrench.

*Note: Screws used for stand installation are not in the accessory box. Please prepare them in advance.

Grounding connection

  • Strip the grounding cable insulation

  • Select OT copper terminal

  • Pull the heat-shrink tubing over the grounding cable

  • The tubing must be below stripped cable section

  • Insert the stripped section into the OT terminal.

  • And crimp with a crimping tool

  • Pull the heat-shrink tubing onto a crimped section of the OT terminal

  • Use a hot-air blower to shrink it so that they are in firm contact with the OT terminal

  • Connect the grounding cable to the grounding point on the inverter

  • Tighten it with torque 10-12 N·m.

Grid connection

  • Disassemble the AC protective shield

Fastening head, Blue rubber seal ring, Orange ring Red ring Black part Protective shield
*Note: Select the corresponding rubber seal ring in accordance with cable size used. The black part no longer used.

  • Strip the 35 50 AC cable insulation

  • mm² L1/L2/L3: 70±5, N/PE: 100±5

  • Select OT copper terminal

  • Install the fastening head and AC protective shield

  • And pre-tighten the fastening head

  • Pull the heat-shrink tubing over the AC cable

  • Insert the stripped section into the OT terminal and crimp with a crimping tool

  • Pull the heat-shrink tubing onto a crimped section of the OT terminal

  • Use a hot-air blower to shrink it so that they are in firm contact with the OT terminal

  • Disassemble the five screws and connect the AC cable to the corresponding AC terminal with cross screwdriver

  • Tighten the screw with torque 6 N·m.

  • Loosen the fastening head and fix the AC protective shield with a cross screwdriver

  • Clockwise screw in the screws to fix it with 1 N·m.

  • Tighten the fastening head again

PV connection

  • Disassemble the DC contactor

  • Strip the PV cable insulation

  • Connect the PV cable to the corresponding PV port

Communication connection

  • Select 0.5~0.75 mm² twisted pair and strip the 20-pin communication insulation

  • Insert the insulated cord end terminal into the cable end
    (ENY0512 nylon terminal for 0.5mm²/22 AWG conductor;
    ENY7512 nylon terminal for 0.75 mm²/20 AWG conductor)

  • Clamp with terminals press clamp

  • Disassemble the communication terminal

  • Set the nut, claw, seal body, seal ring and body on the cable

  • Insert the tube-type terminal into the housing according to the label

  • Push the terminal-inserted housing into the body; you will hear “Click” if it is correctly inserted

  • Please check the following table for more details about the corresponding Pin definition

Port Pin Definition Remark
RS-485-1 1 RS485A IN+ Imerter RS485 networking or connect

the data collector
2| RS4858 IN-
3| GND
4| RS485A OUT+
5| RS485B our-
6| GND
RS-485-2| 7| RS485A METER| Connect the RS485 meter or other devices
8| RS485B METER
9| +5V
10| GND
DRNI| 11| DRMI /5| Reserved for DPM
12| DRM2/6
13| DRM3I7
14| DRM4/8
15| RG/O
16| CVO
DI| 21| Digital IN+| Input digital signal
22| Digital IN-
DO| 29| Digital our+| Output digital signal
30| Digital OUT-

  • Push the seal body into the seal ring, then push the claw Clockwise tighten the nut with torque 8+/-2 N·m
  • Keep the buttons on both sides pressed and then connect them to the communication port on the inverter. You will hear “Click” if it is correctly connected

Monitoring connection

SolaXcloud is a mobile phone application that can communicate with the inverter via WiFi/LAN/4G. It can realize alarm queries, parameter configuration, daily maintenance, and other functions. This is a convenient maintenance platform.
Plug Dongle into the “USB” port at the bottom of the inverter. After the DC side or AC side is powered on, the APP and inverter can be connected. Please refer to the corresponding manual for details.

  • WiFi connection
    SolaX Pocket WiFi Dongle connects to a local network within 50 m of the installation to enable access to the SolaX Cloud monitoring platform.

  • LAN connection
    If WiFi isn’t suitable, the Pocket LAN enables users to connect to the network via an ethernet cable. Ethernet allows for a much more stable connection with less interference.

  • 4G connection
    SolaX Pocket 4G dongle allows you to use a 4G connection to monitor your system without the option of connecting to a local network. (This product is not available in the UK)

  • Basic setting and advanced setting
    Basic settings include the time, date, and language.
    Advanced settings can set Safety, System Switch, PVConnection, Active Power Control, Export Control, Reactive Power Control, Grid Voltage Parameters, Grid Frequency Parameters, Grid Through Parameters, Check Parameters, Reset, Communication Parameters, and New Password.