SOLAX POWER DataHub1000 Commercial and Rooftop String Inverter Instruction Manual

June 5, 2024
SOLAX POWER

SOLAX POWER DataHub1000 Commercial and Rooftop String Inverter Instruction Manual

Preparation

Packing List

  • Power adapter

  • Installation instruction

  • WiFi antenna

  • 630 Nylon type2

  • ST4.8L302

  • M3L64

  • Plug-in terminal*5

  • Plug-in terminal*1

  • Plug-in terminal*1

  • Rail buckle*2

Line Type Specification
RS485 Cross-sectional area 0.2mm²~2.5mm² (24AWG ~ 14AWG) dual-core or multi-

core cables
DO/DI/AI| Cross-sectional area 0.2mm²~1.5mm² or (24AWG ~ 16AWG) dual-core or multi-core cables
NET Cable| Cat 5e or higher standard network cable

Product Introduction

  1. Antenna jack
  2. RST button (RST)
  3. USB socket (USB)
  4. LED indicator (RUN,SERVER,ALARM)
  5. NET socket (NET)
  6. CAN socket (CAN)
  7. DO socket (DO)
  8. DI socket (DI)
  9. TF card socket (TF)
  10. SIM card socket (SIM)
  11. TYPE-C socket
  12. Rail clip
  13. RS485 socket (RS485)
  14. 12V power output (12V/GND)
  15. AI socket (AI)
  16.  12V power input (DC12V)

Installation Requirements

Size

Space

Device parameters

Power Adapter| 100-240V 50/60HZ 1.5A AC input

12V 2A DC output

Ethernet| 10/100M
Wi-Fi Frequency Range| 2.4~2.5GHz
Wi-Fi EIRP Power| 17.5dBm
Dimensions| 20512433 mm
Weight| 440g
Degree of Protection| IP21
Operating Temperature Range| -20℃~+60℃

Indoor Wall Mounting

  1. Choose a flat and solid indoor wall to drill for installation.
  2. Hang the DataHub on the wall with the cable connection area facing down.

Note: The aperture is 6.0mm.

Guide Rail Mounting

  1. Use the four M3*L6 screws in the accessory bag to fix the buckle on the DataHub.
  2. Please prepare 35mm standard rail (effective length ≥230mm) and install it firmly.

Note: The outdoor installation must be in a waterproof housing.

Cascade Connection

  1. It is recommended that the number of devices connected to each channel of RS485 is less than 20.
  2. The baud rate, communication protocol and verification method of all devices on each RS485 cascade link must be consistent with the RS485 communication parameters of the corresponding COM port of DataHub.

Installation of the RS485

Ensure that RS485+ is connected to DataHub’s RS485+ ,RS485- is connected to DataHub’s RS485-, RS485 GND is connected to the GND of DataHub.

Pocket Sign Illustrate

RS485-1 RS485-2 RS485-3

RS485-4

| +| RS485A,RS485Differential signal+
–| RS485B,RS485Differential signal-
GND| Ground wire

Installation of the DI Signal Cable

  1. DataHub can access DI signals such as remote control and alarms through the DI port.
  2. It is recommended that the signal transmission distance does not exceed 10m.
  3. If the selected wire is flexible, press the white terminal adjacent to the wiring port to access.
Socket Illustrate
Dl1 Support passive dry contact signal access

Dl2
Dl3
Dl4

Installation of the AI Signal Cable

  1. It is recommended that the transmission distance does not exceed 10m.
  2. AI port0 , 1 are connected to AI signal +, and GND is connected to AI signal –.
Socket Illustrate
Al0 Supports 0-12V voltage input
Al1 Supports 0-12V voltage input

Installation of the DO Signal Cable

It is recommended that the transmission distance not exceed 10m.

Installation of the Network Cable

  1. DataHub can connect Ethernet switches, routers, and computers through NET ports.
  2. Use Cat 5e or higher specifications and Shielded crystal head connectors to prepare the network cable.
  3. The communication distance does not exceed 100m. When crimping the network cable, ensure that the shielding layer of the network cable is properly connected to the metal shell of the RJ45 connector

Checking of the Pre-power

Num Inspection standards
1 Check whether DataHub has been installed firmly.
2 Check whether the cable is reliably connected.
3 Check whether the cables meet the requirements of strong and weak current

cabling plan.
4| Check whether the cables are bundled neatly, and the orientation are the same.
5| Check whether there are excess copper wires and cable ties left on the cables.

System Power-up

  1. Use a power adapter to connect DataHub to a 100~220V power outlet.
  2. Observe the LED indicator to see if DataHub is operating normally.
Sign Status Illustrate
Run (Green) Slow flashing Normal
Always on or off Abnormal
Serve (Green) On Normal
Off Abnormal
Alarm (Red) Off Normal
On Abnormal

Login

  1. Configure the IP address of your computer and DataHub in the same network segment.
  2. Enter http://datahub.local/ in the computer browser to log in.
  3. Choose the language according to your needs.
  4. Enter:Account: admin, initial password: (initially same as the Registration No.).
  5. After logging in, it is recommended to change the initial password and log in again.

Note: Need router to support mDNS and DHCP protocols.

Safety Instructions

Indicates that the product must not be processed with household waste. It must be brought to an electric and electronic waste collection point for recycling and disposal.By ensuring the appropriate disposal of this product you also help in preventing potentially negative consequences for the environment and human health. The recycling of materials helps preserve our natural resources. For further information regarding the recycling of this product, please contact your municipality, local waste disposal centre or the store where the products was purchased.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

FCC warning:
Any Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.

FAQ

DataHub cannot be powered on

  1. Check whether the DC output of the power adapter cable is plugged into the 12V power input port of DataHub.
  2. Check whether the power adapter cable is plugged into an AC outlet.
  3. Check whether the power adapter is damaged.

Unable to communicate

  1. Check whether the NET socket of DataHub is properly connected.
  2. Check whether network parameters are set correctly.

DataHub cannot find the device

  1. Check the connection of the RS485 communication line or AC power line. If there is any looseness, fall off, or reverse connection, reconnect and tighten it.
  2. Check the RS485 communication parameters and ensure that the baud rate and communication address are set correctly. The device address is within the search address range set for the DataHub.
  3. Check whether the device that does not support automatic recognition, such as electric meters, has been manually added.
  4. Check whether the connected device is powered on.

Contact us

Please contact us if you have any further confusions

SolaX Power Network Technology (Zhejiang) Co., Ltd.

ADD No.288 shizhu Road, Tonglu Economic Zone, Tonglu City, Zhejiang Province, China.
Tel +86 571 56260011 FAX +86 571 56075753
EMAIL [email protected]
WEB www.solaxpower.com