LEDone LOC-EMDR HV Series 25 Watt Emergency Battery Backup Instruction Manual

June 3, 2024
LEDone

**LEDone LOC-EMDR HV Series 25 Watt Emergency Battery Backup Instruction Manual

**

SAVE THESE INSTRUCTIONS!

SAFETY INSTRUCTIONS

Read instructions carefully before attempting to install fixture.

  • All wiring should be performed by a qualified electrician.
  • Disconnect power before installing or servicing. This fixture must be wired nin accordance with the National Electrical Code and applicable local codes and ordinances.
  • Proper grounding is required to ensure personal safety

CAUTION

  • WARNING: This emergency battery provides more than one power supply output source. To reduce the risk of electrical shock, disconnect both normal and emergency source by turning off the A.C. branch circuit and by disconnecting the unit connector.
  • WARNING: Do NOT attempt to service the battery. A sealed, no  maintenance battery is used that is not field replaceable. Replace the entire unit when necessary.
  • WARNING: The use of accessory equipment is NOT recommended bythe manufacturer. It may cause an unsafencondition, void warranty and result in non-compliance with ULb specifications.
  • WARNING: The emergency battery requires an un-switched AC power source of 100-277VAC, 50/60Hz or 100- 347VAC, 50/60Hz. Verify the correspondent electrical rating at the LED fixture before servicing. Both electrical rating will supply power under an output voltage of 25-230VDC in emergency mode for at least 90 minutes. (See individual units for output specifications).
  • WARNING: This emergency battery provides more than one power supply output source. To reduce the risk of electrical shock, disconnect both normal and emergency source by turning off the A.C. branch circuit and by disconnecting the unit connector.
  • WARNING: Do NOT attempt to service the battery. A sealed, no maintenance battery is used that is not field replaceable. Replace the entire unit when necessary.
  • WARNING: The use of accessory equipment is NOT recommended by the manufacturer. It may cause an unsaf  condition, void warranty and result in non-compliance with UL specifications
  • WARNING: The emergency battery requires an un-switched AC power source of 100-277VAC, 50/60Hz or 100- 347VAC, 50/60Hz. Verify the correspondent electrical rating at the LED fixture before servicing. Both electrical rating will supply power under an output voltage of 25-230VDC in emergency mode for at least 90 minutes. (See individual units for output specifications).

LUMEN OUTPUT DURING EMERGENCY OPERATION

The luminaire rated data and maximum mounting height can be found as follows

  1. Determine the fixture efficacy under normal AC operation based on fixture manufacturer published data in lumens per watt (LM/W).
  2. Reference DLC QPL (www.designlights.org) and Energy Star (www.energystar.gov for rated data on fixture efficacy. If fixture is NOT found on DLC or Energy Star Qualified Product Lists, contact the fixture manufacturer.
  3. Multiply fixture LM/W by rated output power of emergency pack. (example: model LOC-EMDR-25W is 25W x 100LM/W = 2,500LM)

SELF-DIAGNOSTIC (MAINTENANCE):

  • The integrated self-diagnostic circuity will automatically conduct 1 monthly 30 seconds and annual 90-minute tests to verify proper emergency capability per Life Safety Code requirements. NFPA101, Life Safety Code Outlines the following schedule:
  • a. Monthly: Ensure that the test button is illuminated. Conduct a 30 second discharge test by depressing the test button. The LED load should operate at reduced output.
  • b. Annually: Ensure that the test button is illuminated. Conduct a full 90-minute discharge test. The unit should operate as intended for the duration of the test. “Written records of the testing should be kept by the owner for inspection by the authority having jurisdiction.” If the charging indicator is  flashing rapidly or off, contact manufacturer.

INSTALLATION: MAKE SURE THE POWER IS OFF BEOFRE INSTALLING!

  1. INSTALLING THE EMERGENCY BATTERY:
    • a. Indicator light and test switch should be mounted where can be seen by the maintenance personnel.
    • b. Determine appropriate location for emergency battery in the fixture. Install the emergency battery to the fixture using existing mounting holes in the fixture. The installationb binstruction of LED luminaire may provide guidance on mounting location.
  2. WIRING:
    • a. Make certain the A.C. power is OFF. The E emergency battery and A.C. driver must be on the same branch circuit.
    • b. Select the appropriate wiring diagram found as reference. For other diagrams, consult the manufacturer.
    • c. Connect the emergency LED driver to the A.C. driver and LED load in accordance with manufacturers installation instructions. d. Make sure all connections are accordance with National Electrical Code or any other local regulations.
  3. MOUNTING THE INDICATOR COMBO TEST SWITCH (ICTS) :
    • a. The emergency battery requires an unswitched A.C. power source of 100 347VAC, 50/60Hz. Therefore, when used with switched fixtures, the emergency battery input must be wired ahead of the test switch.

INSTALLATION

  1. LABEL:
    • a. Attach the appropriate labels adjacent to the ICTS. Annotate Replacement Label with identical manufacturer part number(s). The caution and replacement label must be on the fixture in a readily visible location to anyone attempting to service the fixture.
  2. TESTING:
    • a. After installation is complete, supply A.C. power to the emergency driver and join the unit connector.
    • b. The battery in this unit may not be fully charged. A short-term discharge test may be conducted after the emergency battery has been charging for 1 hour. Charge for 24 hoursn nbeforen conducting a long-term discharge test.

OPERATION

OPERATION INDICATOR  STATUS

Model| Test Switch Operation| Indicator Status| Comments & Solutions
AC MODE (1)| NO Pressed| ON(no flashing)| Battery is charging
AC MODE (2)| Pressed once| 2s ON and 2s OFF (slow flashing)| Battery is conducting a 305 short-term emergency test
AC MODE (3)| Pressed twice| (2s) in sequence 2s ON and 2s OFF (slow flashing)| Battery is conducting a lon  term emergency test unti battery is fully discharged
EMERGENCY MODE (1)| NO Pressed| 2s ON and 2s OFF (slow nesting)| Battery is automaticaly conducting a emergency until battery is fully discharged)
EMERGENCY MODE (2| Pressed once| OFF| Battery is turned off
PROBLEM| When indicator flashes (0.2s) ON and (0.2s) OFF fast or goes off, the emergency backup pack is abnormal. Contact the manufacturer.
WARNING| Note: Please pressed test switch of the LOC-EMDR 25WHV(in once) and make certain the battery is turned off before installation, maintenance, storage or shipping.

WIRING INSTRUCTIONS

Caution: Risk of electric shock! The LED fixture must have 0-10V driver when
wattage is greater than the emergency battery.

Standard Installation

NOTE: FOR LED FIXTURE POWER 5. EMERGENCY LED DRIVER
Standard Installation

USE WIRE NUTS TO COVER UNUSED WIRES

With Dimmer

With Dimmer

Without Dimmer

Without Dimmer

Without Dimmer or Switch

Without Dimmer or Switch