SAFETY INSTRUCTIONS
- Read instructions carefully before attempting to install fixture.
- All wiring should be performed by a qualified electrician.
- Disconnect power before installing or servicing.
- This fixture must be wired in accordance with the National Electrical
- Code and applicable local codes and ordinances.
- Proper grounding is required to ensure personal safety.
- This fixture is for outdoor use and should not be used in areas with limited ventilation or high ambient temperatures.
- CAUTION : Risk of fire
- WARNING : Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside.
CLEANING & MAINTENANCE
CAUTION : Be sure the fixture temperature is cool enough to touch. Do NOT clean or maintain while the fixture is energized.
- Clean glass lens with non-abrasive cleaning solution.
- Do NOT open fixture to clean the LED. Do NOT touch the LED.
Note : These instructions do not cover all details or variation in equipment, nor do they provide for every possible situation during installation, operation or maintenance.
TROUBLESHOOTING
- Check that the line voltage at fixture is correct. Refer to wiring directions.
- Check that the fixture is grounded properly.
MOUNTING:
- Install the mounting plate to a sturdy mounting surface.
- Tighten the 4 screws (Fig. 1A).
- Hang the fixture on the square mounting bracket.
- Connect the wires correctly.
- Slide the fixture horizontally into the 4 slots of the mounting plate (Fig. 1B).
- Screw the safety clamp of the mounting plate on the fixture side (Fig. 2).
PENDANT MOUNTING
- Feed fixture wires through the pendant pipe.
- Mount the pendant pipe into the top of the fixture.
WIRING:
Universal voltage driver permits operation at 120V through 277V, 50/60Hz.
-
Connect the BLACK fixture lead to the (+) LIVE line supply lead.
-
Connect the WHITE fixture lead to the (-) COMMON supply wire.
-
Connect the GROUND wire from fixture to the supply ground.
Universal voltage driver permits operation at 120V through 277V, 50/60Hz. For 0-10V dimming, follow the wiring instructions in Fig 3. -
Connect the BLACK fixture lead to the (+) LINE supply lead.
-
Connect the WHITE fixture lead to the (-) COMMON supply lead.
-
Connect the GROUND wire from fixture to supply ground. DO NOT connect the GROUND of the dimming fixture to the
output. -
Connect the PURPLE fixture lead to the (V+) DIM lead.
-
Connect the PINK (GRAY) fixture lead to the (V-) DIM lead.
-
Cap the Vaux 12V fixture lead if present, Do NOT connect.
-
The driver comes with dimmable leads. If it is unused, make sure the leads are properly capped (if applicable).
WATTAGE AND CCT ADJUSTABLE TABLE SWITCH SETTING:
(Only for models with wattage and CCT adjustable functions.)
- Unscrew the G1/2 cover on the fixture side
- Select the Wattage and CCT desired.
- Screw the G1/2 cover back on the fixture side.