LUMASCAPE sDLT Surface Luminaires
INSTALLATION
- Change the beam angle lens and color filter by removing and replacing existing components (optional).
- Mount bracket to installed junction box or mounting surface. Run luminaire wiring through mounting bracket.
- Use a voltmeter to ensure 11 to 15 V at the luminaire.
- Connect wiring with a waterproof connector.
- Attach luminaire to mounting bracket.
CIRCUITING GUIDELINES
TRANSFORMERS
Single transformer: When using one transformer, center the transformer on
the wattage load. Minimize all cable runs to reduce voltage drop.
Multiple transformers: When using multiple transformers, spread the load
evenly across all transformers. Avoid voltage drop by installing the
transformers as close to the luminaires as possible.
- Please read and keep all safety and use instructions. If you have questions, contact your local agent or visit https://www.lumascape.com.
WARNING – To reduce the risk of FIRE OR INJURY TO PERSON:
- Turn off/unplug and allow to cool before replacing lamp.
- Lamp gets HOT quickly. Contact only switch/plug when turning on.
- Do not touch hot lens, guard, or enclosure.
- Keep lamp away from materials that may burn.
- Do not touch the lamp at any time. Use a soft cloth. Oil from skin may damage lamp.
- Do not operate the luminaire fitting with a missing or damaged shield.
WARNING – Risk of Electric Shock
- May be installed less than 5′ (1.5 m) from a pool, spa, or fountain when used with a UL 379 listed transformer.
- A luminaire shall not use tungsten halogen lamps unless the luminaire is marked for such lamps.
- Supply connection and electrical components are located above ground level, except for the secondary cord that is suitable for wet locations.
LOW-VOLTAGE CABLE SHALL:
- Be protected by routing in close proximity to the luminaire or fitting, or next to a building structure such as a house or deck.
- Not be buried except for a maximum 6″ (152 mm) in order to connect to the main low-voltage cable.
- Have the length cut off so that it is connected to a connector within 6″ (152 mm) from a building structure, a luminaire, or a fitting.