LUMASCAPE dBEM dBeam-6 Directional Ceiling Light Instruction Manual

June 3, 2024
LUMASCAPE

LUMASCAPE dBEM dBeam-6 Directional Ceiling Light Instruction

LUMASCAPE-dBEM-dBeam-6-Directional-Ceiling-Light-Instruction-PRODACT-
IMG

INSTALLATION

LUMASCAPE-dBEM-dBeam-6-Directional-Ceiling-Light-Instruction-
FIG-1

  1. Change the beam angle lens and color filter by rotating, removing, and replacing existing components (optional).
  2. Attach a luminaire to structure using selected mount.
  3. Use a voltmeter to ensure 11 to 15 V at the luminaire.
  4. Connect wiring with a waterproof connector.
  5. Orient the setscrew in the downward direction. Aim luminaire.

CIRCUITING GUIDELINES

LUMASCAPE-dBEM-dBeam-6-Directional-Ceiling-Light-Instruction-
FIG-2

TRANSFORMERS

Single transformer: When using one transformer, center the transformer on the wattage load. Minimize all cable runs to reduce voltage drop.
Multiple transformers: When using multiple transformers, spread
the load evenly across all transformers. Avoid voltage drop by installing the transformers as close to the luminaires as possible.

DIRECTIONAL LUMINAIRES

Please read and keep all safety and use instructions. If you have questions, contact your local agent or visit https://www.lumascape.com

WARNING – To reduce the risk of FIRE OR INJURY TO PERSON

  • Turn off/unplug and allow to cool before replacing lamp.
  • Lamp gets HOT quickly. Contact only switch/plug when turning on.
  • Do not touch hot lens, guard, or enclosure.
  • Keep lamp away from materials that may burn.
  • Do not touch the lamp at any time. Use a soft cloth. Oil from skin may damage lamp.
  • Do not operate the luminaire fitting with a missing or damaged shield.

WARNING – Risk of Electric Shock

  • Install all luminaires 5′ (1.5 m) or more from a pool, spa, or fountain.
  • A luminaire shall not use tungsten halogen lamps unless the luminaire is marked for such lamps.
  • Supply connection and electrical components are located above ground level, except for secondary cord that is suitable for wet locations.

LOW-VOLTAGE CABLE SHALL

  • Be protected by routing in close proximity to the luminaire or fitting, or next to a building structure such as a house or deck.
  • Not be buried except for a maximum 6″ (152 mm) in order to connect to the main low- voltage cable.
  • Have the length cut off so that it is connected to a connector within 6″ (152 mm) from a building structure, a luminaire, or fitting.