SJE RHOMBUS Select Start LT Starter Boxes Installation Guide

September 23, 2024
SJE RHOMBUS

SJE RHOMBUS Select Start LT Starter Boxes

SJE-RHOMBUS-Select-Start-LT-Starter-Boxes-product

Product Information

Product Specifications

  • Model: Control Panel X123
  • Power Supply: 120V-240V AC
  • Max Current: 20A
  • Operating Temperature: 0°C to 40°C
  • IP Rating: IP65

Product Usage Instructions

Mounting and Wiring the Control Panel

  1. Determine the mounting location for the control panel. Ensure proper distance for cables.
  2. Mount the control panel using provided mounting devices.
  3. Determine conduit entrance locations and drill proper size holes for connections.
  4. Attach cable connectors and/or conduit connectors to the control panel.
  5. Turn off all power sources before proceeding.

Setting up the Control Panel

  1. Follow the schematic and connect power conductors to proper terminals.
  2. Verify correct operation of the control panel after installation.

Adjusting the Overload Relay (Telemecanique Brand)

  1. Flip open the protective cover of the relay.
  2. Adjust the relay by rotating the dial to match the motor nameplate full load amps.

Testing Trip Mechanism

  1. Slide the test mechanism to the left. The relay should trip.
  2. Press the reset button to set the overload relay in operation status.
  3. In case of a trip during normal operation, press the reset button.

FAQ

  • Q: What should I do if the control panel does not power on after installation?
    • A: Check the power source and connections, ensuring they are secure and meet specifications. If issues persist, contact technical support.
  • Q: Can I install the control panel outdoors without additional precautions?
    • A: For outdoor installations, use a junction box with liquid-tight connectors and conduit sealant to prevent moisture or gas ingress. Always follow local codes.

Safety Information

WARNING: ELECTRICAL SHOCK HAZARD

  • Disconnect all power sources before servicing. Failure to do so could result in serious injury or death.

This control panel must be installed by a LICENSED ELECTRICIAN and in accordance with the National Electric Code NFPA-70, and state and local codes.

All conduit running from the sump or tank to the control panel must be sealed with conduit sealant to prevent moisture or gases from entering the control panel. NEMA 1 enclosures are for indoor use primarily to provide a degree of protection against contact with enclosed equipment.

Cable connectors are not required to be liquid tight on NEMA 1 enclosures. Do not use NEMA 1 enclosures if subjected to rain, splashing water, or hose- directed water. NEMA 4X enclosures are for indoor or outdoor use primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose-directed water. Cable and conduit connectors must be liquid tight on NEMA 4X enclosures.

Mounting and Wiring the Control Panel

  1. Determine the mounting location for the control panel. If distance exceeds the length of either the control switch cables or the pump power cables, splicing will be required. For an outdoor or a wet installation we recommend the use of a junction box with liquid tight connectors to make required connections. You must use conduit sealant to prevent moisture or gases from entering the panel.
  2. Mount the control panel (mounting devices are furnished with control panel).
  3. Determine the conduit entrance locations on the control panel. Check local codes and schematic for power circuit requirements.
    • CAUTION: BE SURE THE POWER SUPPLY VOLTAGE AND PHASE ARE THE SAME AS THE PUMP MOTORS BEING INSTALLED. IF IN DOUBT, SEE THE PUMP IDENTIFICATION PLATE FOR VOLTAGE/PHASE REQUIREMENTS.
  4. Drill proper size holes for connection to the panel.
    • CAUTION: IF USING CONDUIT, BE SURE THAT THE CONDUIT BEING USED IS OF ADEQUATE SIZE TO PULL THE PUMP AND SWITCH CABLES THROUGH. RECOMMENDED MINIMUM 1 1/2’’ FOR DUPLEX APPLICATIONS.
  5. Attach cable connectors and/or conduit connectors to the control panel.
    • CAUTION: AT THIS POINT, TURN OFF ALL POWER SOURCES.
    • FOR INSTALLATIONS WITHOUT A SPLICE, GO TO STEP 11.
    • FOR INSTALLATIONS REQUIRING A SPLICE, FOLLOW STEPS 6-10.
  6. Determine the location for mounting the junction box according to local code requirements. Do not mount the junction box inside the sump or basin.
  7. Run the conduit or connectors to junction box and drill the junction box as required to make the proper connections. Attach the conduit or connectors to the junction box.
  8. Mount junction box to proper support.
  9. Identify and label each wire before pulling through conduit into junction box. Make necessary wire splice connections at the junction box.
  10. Firmly tighten all fittings on the junction box.
  11. Pull pump cables and control switch cables through connectors/conduit into the control panel.
  12. Connect pump cables and control switch cables to the appropriate terminals. SEE SCHEMATIC INSIDE CONTROL PANEL.
    • CAUTION: IF CONTROL SWITCH CABLES ARE NOT WIRED IN THE CORRECT ORDER, THE PUMP SYSTEM WILL NOT FUNCTION PROPERLY.
  13. Connect “power in’’ conductors to proper terminals. SEE SCHEMATIC.
  14. Verify the correct operation of the control panel after installation is complete.

SETTING/TESTING THE OVERLOAD RELAY

WARNING: ELECTRICAL SHOCK HAZARD

Disconnect power before installing or servicing this product. A qualified service person must install and service this product according to national and local electrical codes. Do not install in hazardous locations as defined by the National Electrical Code, ANSI/NFPA 70.

ADJUSTING THE RELAY – TELEMECANIQUE BRAND

SJE-RHOMBUS-Select-Start-LT-Starter-Boxes-fig-2

TESTING TRIP MECHANISM

  1. Slide test mechanism to the left. Relay should trip.

SJE-RHOMBUS-Select-Start-LT-Starter-Boxes-fig-4

Note: In normal operation, if relay trips, press reset button.

Limited Warranty

SJE Rhombus® Five-Year Limited Warranty

  • Five-Year Limited Warranty.
  • For complete terms and conditions, please visit www.sjerhombus.com.

NOTICE: Products returned must be cleaned, sanitized, or decontaminated as necessary prior to shipment to ensure that employees will not be exposed to health hazards in handling said material. All applicable laws and regulations shall apply.