SJE RHOMBUS CP-SJEIFSD31W100H8AC17J FRIENDLY SERIES IFS In-Site Single Phase Simplex Instruction Manual
- June 4, 2024
- SJE RHOMBUS
Table of Contents
SJE RHOMBUS CP-SJEIFSD31W100H8AC17J FRIENDLY SERIES IFS In-Site Single
Phase Simplex
Get In-Site® to your On-Site™ Systems!
The IFS In-Site® simplex control panel utilizes an innovative circuit board
design to control one 120/208/240V single phase pump in water and sewage
applications. IFS panels feature an easy-to-use touch pad on inner door for
programming and system monitoring. Quick retrieval of all system events can be
done by downloading panel information onto a USB flash drive. The panel
configuration can be easily converted in the field to either a timed dose or
demand dose. Available with the EZconnex® float system.
Monitor system events including pump run times, pump cycles, alarm conditions,
power outages, service calls and more! Quick, convenient reports make
diagnosing system conditions easy! Plug the flash drive into the USB port
located on the inner door of the IFS In-Site® panel to download system events
which occurred. No computer is needed at the site! Use the flash drive
(included with panel) with any computer to download system information and
reports. The pre-loaded software on the flash drive formulates system data for
you, creating reports quickly in an easy-to-read format so system conditions
can be easily identified and corrected. In addition to monitoring system
events, the IFS In-Site® panel logs any service calls and changes made to
system settings, which helps protect service providers. The panel can utilize
the C-Level™ sensor for continuous level monitoring. It senses the level in
the tank and sends a signal to the panel. Pump activation levels can be
adjusted by using the panel touch pad. C-Level™ CL40 sensor operating range is
3-39.9 inches (7.6-101.3 cm). C-Level™ CL100 operating range is 3-99.5 inches
(7.6-252.7 cm).
TOUCH PAD FEATURES
- A. Level Status indicators illuminate when floats or set points are activated; alarm will activate if a float operates out of sequence
- B. HOA (Hand-Off-Automatic) buttons with indication control pump mode; Hand mode defaults to Automatic when stop level or redundant off level is reached
- C. Pump Run indicator illuminates when pump is called to run
- D. LED display for system information including: level in inches or centimeters (C-Level™ sensor only), mode, pump elapsed time (hh:mm), events (cycles), alarm counter, float error count, timed dose override counter (timed dose only), pump ON/OFF times (timed dose only), and sequence ON/OFF times (timed dose only)
- E. NEXT push button toggles display
- F. UP and SET push buttons used to set pump ON/OFF times (timed dose only), date and hour, activation levels (C-Level™ only)
COMPONENTS
- Enclosure base measures 14 x 12 x 6 inches (35.56 x 30.48 x 15.24 cm); NEMA 4X (ultraviolet stabilized thermoplastic with removable mounting feet for outdoor or indoor use)
- Red LED beacon provides 360° visual check of alarm condition
- Exterior Alarm Test/Normal/Silence switch allows horn and light to be tested and horn to be silenced in an alarm condition; alarm automatically resets once alarm condition is cleared
- Alarm horn provides audio warning of alarm condition (83 to 85 decibel rating) (Not shown)
- Circuit breaker (optional) provides pump disconnect and branch circuit protection
- Power relay controls pump by switching electrical lines; definite purpose contactor used when pump full load amps are above 15
- Float connection terminal block
- Incoming control/alarm terminal block
- Control Power indicator/fuse indicator light illuminates if control power is present in panel; alarm will activate if control fuse is blown
- Alarm Power indicator/fuse indicator light illuminates if alarm power is present in panel
- Ground lug
- Incoming pump power connections
- RF filter
- Power supply
- Control fuse
- Alarm fuse
- USB port for flash drive to download time-stamped system events
- Manual report switch date and time stamps service calls
Note: Options, voltage, and amp range selected may change enclosure size
and component layout.
Note: Schematic/Wiring Diagram and Pump Specification Label are located
inside the panel.
INSTALLER FRIENDLY SERIES® IN-SITE® SINGLE PHASE SIMPLEX
IFI | 1 | W | 8AC | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
CONTROL | MODEL | ALARM | ENCLOSURE | STARTING | PUMP | ||||||||||
FULL | PUMP | FLOAT SWITCH | OPTIONS (LISTED |
BELOW)
PANEL| TYPE| PACKAGE| RATING| DEVICE| LOAD
AMPS| DISCONNECTS| APPLICATION
CONTROL PANEL| ✓| IFI|
---|---|---|---
MODEL TYPE| | 1| Simplex Timed Dose (includes Option 8AC as
standard)
| 2| Simplex Demand Dose (includes Option 8AC as standard)
__**ALARM PACKAGE __| ✓| 1| Alarm Package (includes
test/normal/silence switch, fuse, red light, & horn)
ENCLOSURE RATING| ✓| W| Weatherproof, NEMA 4X (engineered
thermoplastic)
STARTING DEVICE| | 1| 120/208/240V
| 9| 120V only
PUMP FULL LOAD AMPS**| | 0| 0 – 7 FLA
| 1| 7 – 15 FLA
| 2| 15 – 20 FLA
PUMP DISCONNECTS
| | 0| No Pump Disconnect
| 4| Circuit Breaker 120V (select STARTING DEVICE Option 9 above)
Circuit Breaker 120/208/240V (select STARTING DEVICE Option 1 above)
FLOAT SWITCH APPLICATION
| | H| Floats – Pump Down (select Option 17 below)
Timed dose = timer enable and alarm / Demand dose = stop, start, and alarm
| E| EZconnex® Float Switch System
(select Option 33, 35 or 36 below)
| Timed Dose
Demand Dose
| X| No Floats| Timed Dose
Demand Dose
| C| C-Level™ Sensor (select Option 24 or 29) Select Option 3E and/ or 4A &
4D for high water alarm and/or redundant off floats| Timed Dose
Demand Dose
NOTE: Pump down applications only. Industry practices suggest that a secondary device, such as a float switch, be used for redundant activation of the high level alarm and pump shut off when using the C-Level™ sensor.
OPTIONS | DESCRIPTION | OPTIONS | DESCRIPTION | |||
---|---|---|---|---|---|---|
1J | Duo Alarm Inputs | 17C | Sensor Float® / Internally Weighted (per |
Float) – Mercury
| 3A| Alarm Flasher| | | 17D| Sensor Float® / Externally Weighted (per
Float) – Mercury
| 3B| Manual Alarm Reset| | | 17G| SJE MilliAmpMaster™ / Pipe Clamp (per
Float) – Mechanical
| 3E| High Water Alarm Float (must also select Option 17)
Only Available with Float Switch Application = C
| | | 17H| SJE MilliAmpMaster™ / Externally Weighted (per Float) –
Mechanical
| 17J| Sensor Float® / Pipe Clamp (per Float) – Mercury
| 4A| Redundant Off
(must also select Option 4D if floats are required)
| Timed Dose| | | 18A| Timer Override Float (Timed Dose Float Panel Only)
Demand Dose| | | 24E| C-Level™ CL40 Sensor with 4’ Vent Tube and 20’ Cord
| 4D| Redundant Off Float (must also select Option 4A and Option 17)| | |
24F| C-Level™ CL40 Sensor with 4’ Vent Tube and 40’ Cord
| 6A| Auxiliary Alarm Contact, Form C| | | 24G| C-Level™ CL40 Sensor with
8’ Vent Tube and 20’ Cord
✓
|
8AC
|
Display Board – Includes: ETM Counter, Events (Cycles) Counter, Alarm Counter, and Override Counter (Timed Dose Only) (in- cluded as standard)
| | | 24H| C-Level™ CL40 Sensor with 8’ Vent Tube and 40’ Cord
| 24X| No C-Level™ CL40 Sensor
| 29A| C-Level™ CL100 Sensor with 10’ Vent Tube and 20’ Cord
| 10E| Lockable Latch – NEMA 4X| | | 29B| C-Level™ CL100 Sensor with 10’
Vent Tube and 40’ Cord
| 10F| Lightning Arrestor (select pump circuit breaker, control and alarm
power combined)| | | 29X| No C-Level™ CL100 Sensor
| 33D ■| EZconnex® 3-Port, 25’, with 10’ Floats (3) / Pipe Clamp
| 10K| Anti-condensation Heater (must select if operating temperature
is colder than 0 degrees F or -18 degrees C)| | | 33E ■| EZconnex®
3-Port, 50’, with 10’ Floats (3) / Pipe Clamp
| 33G ■| EZconnex® 3-Port, 25’, with 20’ Floats (3) / Pipe Clamp
| 11C| Additional NEMA 1 Remote Alarm Panel (must also select Option 6A)| |
| 33H ■| EZconnex® 3-Port, 50’, with 20’ Floats (3) / Pipe Clamp
| 11D| Additional NEMA 4X Remote Alarm Panel (must also select Option 6A)| |
| 35D ■| EZconnex® 4-Port, 25’, with 10’ Floats (4) / Pipe Clamp
| 15A| Control/Alarm Circuit Breaker| | | 35E ■| EZconnex® 4-Port, 50’,
with 10’ Floats (4) / Pipe Clamp
| 16A| 10’ Cord in Lieu of 20’ Cord (per Float)| | | 35G ■| EZconnex®
4-Port, 25’, with 20’ Floats (4) / Pipe Clamp
| 16B| 15’ Cord in Lieu of 20’ Cord (per Float)| | | 35H ■| EZconnex®
4-Port, 50’, with 20’ Floats (4) / Pipe Clamp
| 16C| 30’ Cord in Lieu of 20’ Cord (per Float)| | | 36D ■| EZconnex®
3-Port, 25’, with 10’ Floats (2) / Pipe Clamp, Sealing Plug
| 16D| 40’ Cord in Lieu of 20’ Cord (per Float)| | | 36E ■| EZconnex®
3-Port, 50’, with 10’ Floats (2) / Pipe Clamp, Sealing Plug
| | 36G ■| EZconnex® 3-Port, 25’, with 20’ Floats (2) / Pipe Clamp, Sealing
Plug
| 36H ■| EZconnex® 3-Port, 50’, with 20’ Floats (2) / Pipe Clamp, Sealing
Plug
EZconnex® mechanically-activated, narrow angle float switches with quick release connections
www.sjerhombus.com
email: customer.service@sjeinc.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>