SJE RHOMBUS 123 Single Phase Duplex Capacitor Control Panel Instruction Manual
- June 1, 2024
- SJE RHOMBUS
Table of Contents
SJE RHOMBUS 123 Single Phase Duplex Capacitor Control Panel
Specifications:
- Model: 123 Single Phase Duplex Capacitor Start/Run
- Enclosures: UL Type 4X for indoor or outdoor use
- Warranty: Five-year limited warranty by SJE Rhombus
- Technical Support: 1-800-Rhombus (1-800-746-6287), Mon-Fri 7:00 AM – 6:00 PM CST
Product Usage Instructions
Installing the Float Switches:
- Ensure all power is turned OFF before installing floats in the tank to prevent shock hazards.
- Label each float and cord end with the provided STOP, LEAD, LAG, and ALARM stickers.
- Mount the control panel ensuring proper distance and connections for correct pump function
- Ensure floats have free range of motion and are not obstructed.
- Securely tighten the pipe clamp, ensuring it does not interfere with float operation.
Wiring the Control Panel :
- Determine conduit entrance locations on the control panel as per the provided schematic.
- Check local codes and panel schematic for required power circuits.
- Ensure pump power voltage and phase match the pump motor specifications.
Frequently Asked Questions (FAQ):
-
Can I install the control panel myself?
The control panel must be installed and serviced by a licensed electrician in compliance with relevant electrical codes to ensure safety and proper operation. -
What should I do if my pumps are not functioning correctly?
Check the float switches for proper installation and connections. Ensure they have free range of motion and are labeled correctly. If issues persist, contact technical support at SJE Rhombus for assistance. -
How do I clean and sanitize the returned product?
Prior to returning the product, ensure it is cleaned, sanitized, or decontaminated as necessary to prevent health hazards for handling personnel. Adhere to all applicable laws and regulations during the process.
Model 123
Single Phase Duplex Capacitor Start/Run
Installation and Operation Manual
Parts Included
WARNING! ELECTRICAL SHOCK HAZARD Disconnect all power sources before
servicing. Failure to do so could result in serious injury or death.
This control panel must be installed and serviced by a licensed electrician in
accordance with the National Electric Code NFPA-70, state and local electrical
codes. UL Type 4X enclosures are for indoor or outdoor use.
Warranty void if panel is modified.
- For information regarding operation, available options, or servicing questions, please call SJE Rhombus Technical Support.
- SJE Rhombus offers a five-year limited warranty. For complete terms and conditions, please visit www.sjerhombus.com.
- Products returned must be cleaned, sanitized, or decontaminated as necessary prior to shipment to ensure that employees will not be exposed to health hazards in handling said material. All applicable laws and regulations shall apply.
Manufactured by : SJE Rhombus
- Technical support : +1 800-746-6287
- techsupport@sjerhombus.com
- www.sjerhombus.com
- Technical Support Hours : Monday-Friday, 7 A.M. to 6 P.M. Central Time
- PN 1009560F 06/20
- ©2019 SJE, Inc. All Rights Reserved. SJE RHOMBUS is a trademark of SJE, Inc
Installing the Float Switches
The Model 123 Single Phase Duplex control panel operates with fl oat switches. They activate pump STOP, LEAD pump START, LAG pump START and high-level ALARM functions.
- Ensure all power is turned OFF before installing fl oats in tank. Failure to do so could result in serious or fatal shock.
- Label each float and cord end with the provided pairs of STOP, LEAD, LAG, and ALARM stickers.
- CAUTION!
If the floats are not properly mounted and connected in the correct order, the pumps will not function properly.
Mounting the Control Panel
NOTE
If the distance to the control panel exceeds the length of the fl oat
switch cords or the pump power cord, splicing in a liquid-tight junction box
will be required. For outdoor or wet installation, we recommend an SJE Rhombus
UL Type 4X junction box.
Floats require free range of motion. They must not touch each other or any equipment in the pump chamber.
Wiring the Control Panel
-
Determine conduit entrance locations on control panel as shown. Check local codes and schematic on the inside cover of the panel for the number of power circuits required.
CAUTION!
Be sure the pump power voltage and phase are the same as the pump motor being installed. -
Connect the following wires to the proper terminal positions:
- incoming power
- pump 1
- pump 2
- float switches
See schematic on inside cover of the control panel for details.
Operation
SJE Rhombus Model 123 Single Phase Duplex control panel operates with float switches. When all floats are in the open or OFF position, the panel is inactive. As the liquid level rises and closes the STOP float, the panel remains inactive until the LEAD float closes. At this point the LEAD pump will turn ON (if the Hand-Off-Auto switch is in the AUTO mode and the power is ON). The pump will remain ON until both the STOP and LEAD floats return to their OFF positions. If the liquid level rises beyond both the STOP and LEAD floats to reach the LAG float, the lag pump will turn ON (if the Hand-Off-Auto switch is in the AUTO mode and the power is ON). Both pumps will remain ON until the STOP, LEAD, and LAG floats return to their OFF positions. If the liquid level rises to reach the ALARM float, the alarm will be activated.
Typical Layout (May vary with options ordered).
CAUTION!
You must use conduit sealant to prevent moisture or gases from entering the
panel.
Type 4X conduit must be used to maintain a Type 4X rating of the control
panel.
Verify correct operation of control panel after installation is complete.
Model shown contains optional Seal Fail circuitry.
COMPONENTS
- ON/OFF Switch – Control/Alarm Power
- 120V Incoming Power Terminals
- Power LED – (Green)
- Pump HOA Switches
- Float LEDs – (Red) x4
- Pump LEDs x2
- Pump Run – (Green)
- Pump Fail – (Red)
- Simulate Float Buttons x4
- Float Terminals x8
- Lead/Lag Selector Switch
- Dual Seal Fail Pot – (Optional)
- Dual Seal Fail LEDs – (Red) – (Optional)
- Auxiliary Alarm Terminals
PROGRAMMING INSTRUCTIONS
WITH POWER ON, HOAs OFF, FLOATS OFF OR DISCONNECTED, PRESS DESIRED FLOAT
BUTTON RAPIDLY 4 TIMES AND HOLD
PUMP LEDs WILL FLASH UPON SUCCESSFUL PROGRAMMING
OPTIONS| FLOAT BUTTON| DEFAULT| OPERATION
PUMP FAIL ALARM| STOP| ON| ACTIVATES IF A PUMP CAUSES “LAG” 3 CYCLES IN A ROW
MANUAL ALARM RESET| LEAD| OFF| LATCHES HIGH ALARM: CLEAR WITH EXTERNAL TEST
SWITCH
SEAL FAIL HORN| LAG| OFF| ACTIVATES HORN UPON SEAL FAIL
ALARM FLASHER| ALARM| OFF| FLASHES BEACON UPON HIGH ALARM
ALARM CONDITIONS
ALARM| BEACON| CONTROLLER LED| HORN
PUMP FAIL| FLASHING| RED PUMP LIGHT| NO
SEAL FAIL| FLASHING| SF1, SF2| PROG
FLOAT FAIL| FLASHING| BAD FLOAT NOT LIT| NO
HIGH ALARM| SOLID| ALARM FLOAT| YES
- Technical Support: +1 800-746-6287
- techsupport@sjerhombus.com
- www.sjerhombus.com
- Technical Support Hour s: Monday – Friday, 7 A.M. to 6 P.M. Central Time