SJE RHOMBUS WellZone Pressure Controller Single Phase 3 Wire Well Pump Control Panel Instruction Manual

June 1, 2024
SJE RHOMBUS

SJE RHOMBUS WellZone Pressure Controller Single Phase 3 Wire Well Pump

Control Panel

Product Information

  • Specifications:
    • Input Voltage: 230 VAC, 60Hz
    • Pump Ratings:
    • Single phase, 3-wire (4~17FLA)
    • Pressure Transducer: 0-150 PSI (included) 1/4 NPT Male, NSF 61 rated, 4-20mA, with 16.4 ft (5m) cable
    • Auxiliary Alarm Contacts: N.O. 1 amp, 120 VAC Max

Product Usage Instructions

  • Features:
    • Start Relay: Circuit breaker for pump disconnect and branch circuit protection.
    • LCD Display: Shows pressure reading, pump amp reading, and pump-on indicator.
    • Pump Test Switch: Allows manual running of the pump.
    • Rotary Encoder Push Button: Rotate to scroll menu settings, press to select.
    • ESC Button: Exit without saving or jumping to the previous display.
  • Mounting the Control Panel:
    • Drill and fasten the top of the enclosure using appropriate anchors.
    • Drill and fasten the bottom of the enclosure using appropriate anchors.
  • Wiring the Control Panel:
    • CAUTION! Disconnect all power to the control panel before wiring. Ensure that the incoming supply power voltage matches the pump motor rating. The motor’s rated Amps should not exceed the control panel’s rating. Ensure correct HP rating and Capacitor values.

FAQs

  • Q: Can this controller provide variable speed pump control?
    • A: No, this digital controller does not provide Variable Speed Pump Control.

Parts Included

SJE-RHOMBUS-WellZone-Pressure-Controller-Single-Phase-3-Wire-Well-Pump-
Control-Panel-FIG-1 \(1\)

Specifications

  • Input Voltage: 230 VAC, 60Hz
  • Operating Temperature: 14°to 122° (-10° to 50°)
  • Pump Ratings: Single phase, 3-wire (4~17FLA)
  • Enclosure: 10 x 8 x 4 inch (25.4 x 20.3 x 10.2 cm) NEMA 4X thermoplastic Includes liquid tight cable strain relief fittings:
    • 1 x 1/2” + 1 x 3/4” UF cable
    • 1 x 1/2” round cable
  • Pressure Transducer:
    • 0-150 PSI (included) 1/4” NPT Male,
    • NSF 61 rated, 4-20mA,
    • with 16.4 ft (5m) cable
  • Auxiliary Alarm Contacts:
    • N.O. 1 amp, 120 VAC Max
Part # Description 3-WIRE MOTOR RUN CAP START CAP CB
    HP Volts SFA Mfd
1094602 WELLZONE 3W-050 1/2 230 4.3 15
1094603 WELLZONE 3W-075 3/4 230 5.7 23
1094604 WELLZONE 3W-100 1 230 7.1 23
1094605 WELLZONE 3W-150 1 1/2 230 11.5 15
1094606 WELLZONE 3W-200 2 230 13.2 20
1094638 WELLZONE 3W-300 3 230 17.0 45

WARNING! ELECTRICAL SHOCK HAZARD Disconnect all power sources before servicing. Failure to do so could result in serious injury or death. This digital controller does not provide Variable Speed Pump Control or constant pressure operation. This control panel must be installed and serviced by a licensed electrician per the National Electric Code NFPA-70, and state and local electrical codes. UL Type 4X enclosures are for indoor or outdoor use. Warranty void if the panel is modified. For information regarding the operation, available options, or servicing questions, please call SJE Rhombus Technical Support. SJE Rhombus offers a five-year limited warranty. For complete terms and conditions, please visit www.sjerhombus.com. Products returned must be cleaned, sanitized, or decontaminated as necessary before shipment to ensure that employees will not be exposed to health hazards in handling said material. All applicable laws and regulations shall apply.

Features

The WellZone™ 3W digital controller provides pressure control for single-phase 3-wire submersible well pump applications. It uses a 0-150 PSI pressure transducer to monitor the discharge pressure and turns the pump ON and OFF according to adjustable Start and Stop setpoints. The LCD allows for a quick view of the system pressure, run status, hours run and pump cycles. The rotary button provides the user with a simple navigation method through the menu and program settings. It features built in pump protection including rapid cycling and dry run. It is preprogrammed to run the pump as the pressure drops below 40 PSI and stop as the pressure rises above 60 PSI. High & Low-pressure settings are available with an auxiliary alarm relay.

SJE-RHOMBUS-WellZone-Pressure-Controller-Single-Phase-3-Wire-Well-Pump-
Control-Panel-FIG-1 \(2\)SJE-RHOMBUS-WellZone-Pressure-Controller-Single-
Phase-3-Wire-Well-Pump-Control-Panel-FIG-1 \(3\)

WELLZONE PANELS

SJE P/N| DESCRIPTION| START

CAPACITOR

| RUN

CAPACITOR

| CIRCUIT

BREAKER

1094602| WELLZONE 3W-050 (230V 1/2 !P 4″0 S#A$| 40-53 %#D/250V| 15 %#D/3&0V| 15 A%P
1094603| WELLZONE 3W-0&5 (230V 3/4 !P 5″2 S#A$| 59-&1 %#D/250V| 25 %#D/3&0V| 20 A%P
1094604| WELLZONE 3W-0100

(230V 1″0 !P 6″2 S#A$

| ‘6-103 %#D/250V| 25 %#D/3&0V| 20 A%P

1094605

| WELLZONE 3W-150 (230V 1″5 !P 11″2 S#A$|

105-126 %#D/250V

|

15 %#D/3&0V

|

20 A%P

SJE-RHOMBUS-WellZone-Pressure-Controller-Single-Phase-3-Wire-Well-Pump-
Control-Panel-FIG-1 \(4\)

WELLZONE PANELS WITH KLIXON START OVERLOAD

SJE P/N| DESCRIPTION| START CAPACITOR| RUN CAPACITOR| CIRCUIT

BREAKER

1094606| WELLZONE 3W-200  230V!2 HP! 11″9 S#A$| 10%-126 &#D/2%0V| 20 &#D/3’0V| 2% A&P
109463(| WELLZONE 3W-300  230V!3 HP! 14″3 S#A$| 20(-2%0 &#D/2%0V| 4% &#D/3’0V| 30 A&P

Mounting the Control Panel

  1. Drill and fasten the top of the enclosure using an appropriate anchor.SJE-RHOMBUS-WellZone-Pressure-Controller-Single-Phase-3-Wire-Well-Pump-Control-Panel-FIG-1 \(5\)
  2. Drill and fasten the bottom of the enclosure using appropriate anchors.

Wiring the Control Panel

CAUTION! Disconnect all power to the control panel before wiring. Ensure that the incoming supply power voltage is the same as the rating of the pump motor being installed. Ensure that the rated Amps of the motor does not exceed the rating of the control panel. Ensure the HP rating and Capacitor values of the control panel are correct for the pump used.

  1. Connect the following wires to the proper terminal positions:

    • Incoming power to the circuit breaker
    • Motor/Pump power to Motor
    • Pressure transducer
    • See the wiring label inside the control panel for details.
  2. Verify the correct operation of the control panel after the installation is complete.SJE-RHOMBUS-WellZone-Pressure-Controller-Single-Phase-3-Wire-Well-Pump-Control-Panel-FIG-1 \(7\)

  3. Maximum motor cable lengths.
    Motor| Feet Motor Cable (75C) 1
    ---|---
    Vac| HP| Amps 2| 14 AWG| 12 AWG| 10 AWG| 8 AWG
    230V| 1/2HP| 4.3| 400| 650| 1000| 1600
    3/4HP| 5.7| 300| 450| 750| 1200
    1.0HP| 7.10| 250| 400| 60| 1000
    1.5HP| 11.5| 175| 300| 450| 750
    2.0HP| 13.2| 150| 250| 400| 600
    3.0HP| 17| 120| 200| 300| 450

  4. Cable length is measured from the motor to the main panelboard (Service Entrance) 75C Insulation – AWG Copper Wire only. Do not use aluminium conductors. Use with a 2-wire motor only with internal thermal protection.

  5. Typical S.F.A. (Service Factor Amps). Check the motor nameplate for actual data.

Operation Guide – PRESSURE CONTROL

SJE-RHOMBUS-WellZone-Pressure-Controller-Single-Phase-3-Wire-Well-Pump-
Control-Panel-FIG-1 \(8\) Notes:

  • A. If there is no operation for 20 sec, the display will return to the main screen.
  • B. The service function is used to alert the user when it is time to change alter or service the equipment after the accumulated run time is reached.
    • The icon will flash on the main screen when the timer is done (Filter at 0%). Push and hold the ESC button for 4 seconds to reset the alter or service time.
    • Pressure transducer = 0-150 psi
    • Digital input = Floor sensor (stop pump) or low level float (stop pump)
      PARAMETER| Description| Default| Range Min| Range Max| Unit| Function
      ---|---|---|---|---|---|---
      START| Start Pressure| 40.0| 1.0| 140.0| PSI| The pump will RUN when the pressure drops below the “START” pressure value and continue to RUN until the pressure rises above the “STOP” value. Set START <STOP. The “STOP” value should be at least 10 PSI over the “START” value.
      STOP| Stop Pressure| 60.0| 10.0| 150.0| PSI| The pump will RUN when the pressure drops below the “START” pressure value and continue to RUN until the pressure rises above the “STOP” value.
      HIGH| High Pressure| 70.0| 10.0| 150.0| PSI| High-Pressure alarm. The pump will stop if the pressure rises above this value

LOW

|

Low Pressure

|

20.0

|

0.0

|

150.0

|

PSI

| Low-Pressure alarm. If the pressure drops below this value, the “LOW TMR” timer will start. The pump will stop when the timer is done and a “LOW PRESS” alarm will be displayed.
LOW TMR| Low Pressure Timer| 30| 0| 3599s(59m:59s)| second| Low-pressure   timer. This delay timer needs to be long enough to allow the pump to pressurize the system on start-up. It can be used to detect a broken discharge pipe or significant leak. Value is in Seconds (s).
OVERLOAD| S.F.A Setting| 12.0| 4.0| 17.0| Amps| Set to the motor Service Factor Amps (SFA) value as listed on the motor nameplate. The pump will stop if it is pulling excessive amps and the “OVERLOAD” alarm will be displayed. The controller will reset the fault automatically after a cooling period. The controller will reset this fault 4 times automatically before requiring a manual reset.
DRY RUN| Dry Run Amps| 0.0| 0.0| 17.0| Amps| Pump DRY RUN protection. Set this value lower than the normal pump operating amps. 30% lower than the motor Service Factor Amps is common. Adjust up or down as this function is tested. Example: Motor SFA = 10.0A. Set the Dry Run Amps = 7.0A. Set to “0.0” to disable this function (Default)

DRY TMR

|

Dry Run Timer

|

30

|

0

|

3599s(59m:59s)

|

Seconds

| The time delay before stopping the pump on “DRY RUN” as the amps are lower than the “DRY RUN” Amps value. The timer value is in seconds (s).

RECHARGE

|

Recharge Timer

|

20

|

0

|

3599m(59h:59m)

|

Minutes

| Automatic reset timer after a “DRY RUN” trip, allowing for enough time for the well to recharge. The timer value is in minutes (m). Set to “0” to disable.
STRT/MIN| Starts Per Minute| 2| 1| 10| Cycles| Rapid cycle protection. Enter the maximum allowable pump starts per minute. If the number of starts is exceeded , the display will show “RPD CYCL” and a manual reset is required for the pump to start again.
MAX RUN| Max Run Time per cycle| 0| 0| 3599m(59h:59m)| Minutes| Set the maximum cycle time. The pump will stop and a “MAX RUN” alarm will be displayed if the cycle time is greater than this value. Set to “0” to disable (default)
NO AMPS| No Amps detect| ON| ON| ON, OFF| NA| The No amps detection function informs the user of the thermal switch trip internal to the motor. Allow the motor to cool and it will start again automatically. This detection function is disabled when set to “OFF”.
FILTER| Filter Life Timer| OFF| 0| 9999| hours| Set the estimated pump run time between filter replacements. The time is set in hours (h) and corresponds to pump running hours. A flashing wrench will appear on the screen when this timer is done. This function is disabled by default.

  *  **CAUTION:** The DY RUN protection is disabled by default. It must be set according to your pump HP and normal running Amps during start-up.  

ALARM| Fault| Pump| Auxilary| Auto/Manual Reset| Description| Action
---|---|---|---|---|---|---

LOW PRES

|

LOW PRESSURE ALARM

|

STOP

|

CLOSED

| Auto reset when PSI is back to

normal

| LOW PRESSURE ALARM

Pressure below the Low Pressure set point for longer than the Low Pressure Timer.

|

Check for leaks, broken pipes. Check the pump and motor.

HIGH PRES

|

HIGH PRESSURE ALARM

|

STOP

|

CLOSED

| Auto reset when PSI is back to

normal

| HIGH PRESSURE ALARM

Pressure greater than the High Pressure set point.

| Check pump, piping and pressure tank.

DRY RUN

|

PUMP RUNNING DRY

|

STOP

|

CLOSED

|

Manual reset or reset by recharge if not disabled

| PUMP DRY RUN ALARM

Pump DRY RUN protection. Set this value lower than the normal pump operating amps. 30% lower than the motor Service Factor Amps is common. Example: Motor SFA = 10.0A. Set the Dry Run Amps = 7.0A. Set to “0.0” to disable this function (Default).

|

If the pump is tripping on DRY RUN but there is water in the well, decrease this setting. If the pump is NOT tripping on DRY RUN, then increase this value.

RAPID CYCLE

|

PUMP RAPID CYCLING

|

STOP

|

CLOSED

|

Manual reset

|

RAPID CYCLING ALARM

This is the maximum allowable pump starts per minute. If the number of cycles per minute is exceeded, the pump will not start and the RDP CYCL alarm will be displayed.

|

Check the pressure tank for damage or incorrect pre-charge pressure. These commonly result in the pump rapid cycling. Correct or replace pressure tank.

Increase the number starts per minute for systems with small pressure tanks. Contact the pump/motor manufacturer for the max allowable starts/minutes.

MAX RUN

|

MAXIMUM RUN TIME

|

STOP

|

CLOSED

|

Manual reset

|

MAXIMUM RUN TIME ALARM Maximum runtime allowed in one cycle.

| Check for pipe leaks or faucets left open. Increase time if

necessary

NO AMPS

|

NO AMPS DETECTED

|

NONE

|

CLOSED

|

Auto reset

| NO AMPS DETECTED

No amps are detected which implies that the thermal switch internal to the motor has tripped or that the pump is not connected.

When the “NO AMPS” function is enabled, it will ignore the Low Pressure and Dry Run conditions and maintain the RUN command to the pump until the motor has cooled down

and restarts automatically.

|

If it is a motor thermal trip, then allow the motor to cool and it will start again automatically.

Investigate the cause of the motor’s internal trip. If the motor is not connected, check the motor wiring. The NO AMPS function can be disabled when set to “OFF”.

OVERLOAD

|

MOTOR OVERLOAD

|

STOP

|

CLOSED

|

Auto reset / Manual reset

| Class 10   overload protection, calculated based on the motor S.F.A. load.

The overload will automatically reset after a cooling period. It must be manually reset after four consecutive times trips.

|

Check the pump for clogging or locked rotor condition.

WATER SW

|

WATER SWITCH ACTIVE

|

STOP

|

CLOSED

|

Auto reset

| Digital input from the optional floor sensor or float switch. If the input of the water sensor is ON for more than 5 sec, shut down the pump and display “WATER SW”. This alarm will auto-reset when the

switch opens.

|

Check the water sensor or float switch. Correct the cause of water leakage or water supply before resetting the fault.

XDR OPEN

|

TRANSDUCER OPEN

|

STOP

|

CLOSED

|

Auto reset

|

PRESSURE TRANSDUCER OPEN CONNECTION

Active when the 4-20mA signal input value is < 3.0mA

| Check the transducer cable connection to the pressure sensor. Make sure it is connected properly and hand-tightened.

Check the transducer cable for damage. Replace the cable if damaged.

Check the transducer cable connections to the controller. Make sure there is a good connection.

XDR SHORT

|

TRANSDUCER SHORT

|

STOP

|

CLOSED

|

Auto reset

|

PRESSURE TRANSDUCER SHORT CIRCUIT

Active when the 4-20mA signal input

value is > 21mA

| Same as above. In addition, check the pressure transducer.

Remove it and inspect for damage. Replace if is it damaged.

RECHARGE

|

WELL IS RECHARGING

|

STOP

|

CLOSED

| Hold ESC for 4 seconds if you want to cancel the timer and re-start the pump immediately| WELL IS RECHARGING PLEASE STAND BY

This is the waiting time after the pump as tripped on the “Dry Run” fault, before performing an automatic reset.

| Wait for the recharge timer to complete.

Increase or decrease this timer value as needed to match the recovery time of your well.

CHNG FILTER| CHANGE FILTER| NONE| NONE| Hold ESC for 4 sec to reset the filter capacity to 100%| CHNG FILTER & Wrench Icon is displayed for 2 seconds every 7 seconds when the pump has run for the time listed in the user filter **setting.| Replace or clean the filter regularly to keep the pumping system running at optimal efficiency.**

Start Circuitry Overload Protector (For 2HP & 3HP only)

SJE-RHOMBUS-WellZone-Pressure-Controller-Single-Phase-3-Wire-Well-Pump-
Control-Panel-FIG-1 \(9\)

There is an additional overload (OL) protection device on 2HP and 3HP control panels. This OL device is for the protection of the START Circuitry and is located below the terminal blocks. Press the red button to reset.

  • Q: What are the symptoms when the start overload is tripped?
    • A: There is a short in the start circuitry or a locked rotor situation. The pump will not start when this overload protector has tripped. Press the red button to reset. The digital display may also display “OVERLOAD” and must be reset (Press the ESC button for 4 sec).
  • Q: How to check the circuit with a multimeter?
    • A: If the pump does not start after a reset. To verify that OL has reset, measure the resistance (ohm) from T1 and the black wires in the cap kit. It should measure continuity (<10 ohms). Check the start relay and capacitors as well.
  • Q: How to reset?
    • A: To reset, wait at least 10 minutes after the trip to allow for the unit to cool down and press the red button.
  • Q: What do you do if the start overload keeps tripping?
    • A: Check the capacitors and start the relay. Check the motor if locked. Check the ambient temperature in the control panel. The overload module will trip sooner if hot. Protect the control panel from direct sunlight.

REPLACEMENT PART NUMBERS

Part#| 1094602| 1094603| 1094604| 1094605| 1094606| 1094638
---|---|---|---|---|---|---
 | WellZone 3W-050| WellZone 3W-075| WellZone 3W-100| WellZone 3W- 150| WellZone 3W-200| WellZone 3W-300
HP| 1/2| 3/4| 1| 1 1/2| 2| 3
SFA| 4.3| 5.7| 7.1| 11.5| 13.2| 17.0
Volts| 230| 230| 230| 230| 230| 230
RUN CAP| 15mF| 23mF| 23mF| 15mF| 20mF| 45mF
Part#| 1036323| 1004023| 1004023| 1036323| 1003706| 1003829



Mars

| 12210| 12215| 12215| 12210| 12214| 12223
370V| 370V| 370V| 370V| 370V| 370V
START CAP| 43-56mF| 59-71mF| 88-108mF| 108-130mF| 108-130mF| 216-

59mF

Part#| 1098476| 1098478| 6001275| 1027120| 1027120| 1002979
Volt| 250| 250| 250| 250| 250| 250
Mars| 11942| 11943| 11945| 11946| 11946| 11952
Start Relay| HLR3800- 2AL3D| HLR3800- 2AL3D| HR3800- 2AL3D| HR3800- 2AL3D| HR3800- 2AL3D| HR3800- 2AL3D
Part#| 1098479| 1098479| 1098479| 1098479| 1098479| 1098479
Start OL|  |  |  | GA3VPA7421| GA3VRA0021|
Par#|  |  |  | 1104244| 1104245|
CB| 15A| 20A| 20A| 20A| 25A| 30A

CONTACT

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>