SJE RHOMBUS Friendly Series IFS Three Phase Simplex Control Panel Instruction Manual
- October 27, 2023
- SJE RHOMBUS
Table of Contents
Series IFS Three Phase Simplex Control Panel
Instruction Manual
Friendly Series IFS Three Phase Simplex Control Panel
Panel layout may vary with options. Reg. Cdn Pat. & TM Off C-Level™ Sensor US
Patent No. 8,336,385; 8,567,242; 8,650,949.
The IFS simplex control panel utilizes an innovative circuit board design to
control one 208/240/480 VAC three phase pump in water and sewage applications.
IFS panels feature an easy-to-use touch pad on inner door for programming and
system monitoring.
The panel configuration can be easily converted in the field to either a timed
dose or demand dose. Available with the Essonne ® float system. The panel can
utilize the C-Level™ sensor for continuous level monitoring. It senses the
level in the tank and sends a signal to the panel. Pump activation levels can
be adjusted by using the panel touch pad. C-Level™ CL40 sensor operating range
is 3-39.9 inches (7.6-101.3 cm). C-Level™ CL100 operating range is 3-99.5
inches (7.6-252.7 cm).
TOUCH PAD FEATURES
A. Level Status indicators illuminate when floats or set points are activated;
alarm will activate if a float operates out of sequence
B. HOA (Hand-Off-Automatic) buttons control pump mode with indication; Hand
mode defaults to Automatic when stop level or redundant off level is reached
C. Pump Run indicator will illuminate when pumps are called to run
D. LED Display for system information including: level in inches or
centimeters (C-Level™ only), mode, pumps elapsed time (ham), events (cycles),
alarm counter, float error count, timed dose override counter (timed dose
only), and ON/OFF times (timed dose only)
E. NEXT push button toggles display
F. UP and SET push buttons set pump ON/OFF times (timed dose only) and
activation levels (C-Level™ only)
COMPONENTS
- Enclosure base measures 14 x 12 x 6 inches (35.56 x 30.48 x 15.24 cm); NEMA 4X (ultraviolet stabilized thermoplastic with removable mounting feet for outdoor or indoor use)
- Red LED beacon provides 360° visual check of alarm condition
- Exterior Alarm Test/Normal/Silence switch allows horn and light to be tested and horn to be silenced in an alarm condition; alarm automatically resets once alarm condition is cleared
- Motor protective switch provides adjustable overload, branch circuit protection and pump disconnect
- IEC motor contactor controls pump by switching electrical lines
- Multi-tap transformer (208/240/480 VAC primary) provides 120 VAC control alarm voltage or 600 VAC primary transformer
- Float connection terminal block
- Control Power indicator/fuse indicator light illuminates if control power is present in panel; alarm will activate if control fuse is blown
- Alarm Power indicator/fuse indicator light illuminates if alarm power is present in panel
- Large incoming power connection terminal block
- Terminal block float wiring label
- Ground lugs
- Alarm horn provides audio warning of alarm condition (83 to 85 decibel rating) (Not shown)
Note: Options, voltage, and amp range selected may change enclosure size
and component layout.
Note: Schematic/Wiring Diagram and Pump Specification Label are located
inside the panel.
INSTALLER FRIENDLY SERIES ®THREE PHASE SIMPLEX – Demand or timed dose
float controlled system for pump control and system monitoring.
IFS | 5 | 1 | W | 8AC | ||
---|---|---|---|---|---|---|
CONTROL PANEL | MODEL TYPE | ALARM PACKAGE | ENCLOSURE RATING | PUMP FULL LOAD | ||
AMPS | FLOAT SWITCH APPLICATION | OPTIONS (LISTED BELOW) | ||||
CONTROL PANEL | ✓ | IFS | ||||
--- | --- | --- | --- | |||
MODEL TYPE | ✓ | 5 | Three Phase Simplex (includes Option 8AC as standard) | |||
ALARM PACKAGE | ✓ | 1 | Alarm Package (includes test/normal/silence switch, |
fuse, red light, & horn)
ENCLOSURE RATING| ✓| W| Weatherproof, NEMA 4X (engineered thermoplastic)
PUMP FULL LOAD AMPS| 208/240/480V| 600V
| 001| 1.0 – 1.6 FLA| | 005| 1.0 – 1.6 FLA
| 101| 1.6 – 2.5 FLA| | 105| 1.6 – 2.5 FLA
| 201| 2.5 – 4.0 FLA| | 205| 2.5 – 4.0 FLA
| 301| 4.0 – 6.3 FLA| | 305| 4.0 – 6.3 FLA
| 401| 6.0 – 10.0 FLA| | 405| 6.0 – 10.0 FLA
| 511| 9.0 – 14.0 FLA| | 515| 9.0 – 14.0 FLA
| 611| 13.0 – 18.0 FLA| | 615| 13.0 – 18.0 FLA
| 621| 17.0 – 23.0 FLA| | 625| 17.0 – 23.0 FLA
| 701| 20.0 – 25.0 FLA| | 705| 20.0 – 25.0 FLA
FLOAT SWITCH APPLICATION| | H| Floats – Pump Down (select Option 17
below)
| E| Essonne® Float Switch System (select Option 33 or 34 below)
| X| No Floats
| C| C-Level™ Sensor (select Option 24 or 29) Select Option 3E and/or 4A & 4D
for high water alarm and/or redundant off floats
NOTE: Pump down applications only. Industry practices suggest that a secondary device, such as a float switch, be used for redundant activation of the high level alarm and pump shut off when using the C-Level™ sensor.
PRICING WORK SHEET
IFS Three Phase, Simplex Base Price………..
Alarm Package…………………………………………..
Enclosure Rating………………………………………
Pump Full Load Amps……………………………
Float Switch Application………………………….
Total Options………………………………………..
TOTAL LIST PRICE…………………………..
| OPTIONS| DESCRIPTION| OPTIONS| DESCRIPTION
---|---|---|---|---
| 3A| Alarm Flasher| 17C| Sensor Float® / Internally Weighted (per Float) –
Mercury
| 3B| Manual Alarm Reset| 17D| Sensor Float® / Externally Weighted (per Float)
– Mercury
| 3E| High Water Alarm Float (must also select Option 17)
Only Available with Float Switch Application = C| 17G| SJE
MilliAmpMaster™ / Pipe Clamp (per Float) – Mechanical
17H| SJE MilliAmpMaster™ / Externally Weighted (per Float) – Mechanical
| 4A| Redundant Off (must also select Option 4D if floats are required)| 17J|
Sensor Float® / Pipe Clamp (per Float) – Mercury
| 4D| Redundant Off Float (must also select Option 4A and Option 17)| 24E|
C-Level™ CL40 Sensor with 4’ Vent Tube and 20’ Cord
| 5A| Thermal Cutout/Heat Sensor Auto Reset (for pumps with thermal switch
leads)| 24F| C-Level™ CL40 Sensor with 4’ Vent Tube and 40’ Cord
24G| C-Level™ CL40 Sensor with 8’ Vent Tube and 20’ Cord
| 5E| Seal Failure Circuit and Red Indicator (2 Wire)| 24H| C-Level™ CL40
Sensor with 8’ Vent Tube and 40’ Cord
| 6A| Auxiliary Alarm Contact, Form C| 24X| No C-Level™ CL40 Sensor
✓| 8AC| Display Board – Includes: ETM Counter, Events (Cycles)
Counter, Alarm Counter (included as standard)| 29A| C-Level™ CL100 Sensor
with 10’ Vent Tube and 20’ Cord
29B| C-Level™ CL100 Sensor with 10’ Vent Tube and 40’ Cord
| 10E| Lockable Latch – NEMA 4X| 29X| No C-Level™ CL100 Sensor
| 10G| Lightning Arrestor| 33D ■| Essonne® 3-Port, 25’, with 10’ Floats (3) /
Pipe Clamp
| 10K| Anti-condensation Heater| 33E ■| Essonne® 3-Port, 50’, with 10’ Floats
(3) / Pipe Clamp
| 11C| Additional NEMA 1 Remote Alarm Panel (must also select Option 6A)| 33G
■| Essonne® 3-Port, 25’, with 20’ Floats (3) / Pipe Clamp
| 11D| Additional NEMA 4X Remote Alarm Panel (must also select Option 6A)| 33H
■| Essonne® 3-Port, 50’, with 20’ Floats (3) / Pipe Clamp
| 16A| 10’ Cord in Lieu of 20’ Cord (per Float)| 34D ■| Essonne® 4-Port, 25’,
with 10’ Floats (3) / Pipe Clamp, Sealing Plug
| 16B| 15’ Cord in Lieu of 20’ Cord (per Float)| 34E ■| Essonne® 4-Port, 50’,
with 10’ Floats (3) / Pipe Clamp, Sealing Plug
| 16C| 30’ Cord in Lieu of 20’ Cord (per Float| 34G ■| Essonne® 4-Port, 25’,
with 20’ Floats (3) / Pipe Clamp, Sealing Plug
| 16D| 40’ Cord in Lieu of 20’ Cord (per Float)| 34H ■| Essonne® 4-Port, 50’,
with 20’ Floats (3) / Pipe Clamp, Sealing Plug
Essonne® mechanically-activated, narrow angle float switches with quick release connections
www.sjerhombus.com
email:customer.service@sjeinc.com
SEE PRICE BOOK FOR PRICING
9500055I Rev 05/21
© 2020 SJE, Inc. All Rights Reserved.
SJE Rhombus is a trademark of SJE, Inc.
www.sjerhombus.com **
Toll Free 888-342-5753
**
Documents / Resources
| SJE
RHOMBUS Friendly Series IFS Three Phase Simplex Control
Panel
[pdf] Instruction Manual
Friendly Series IFS Three Phase Simplex Control Panel, IFS Three Phase Simplex
Control Panel, Three Phase Simplex Control Panel, Simplex Control Panel
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>