MEAN WELL DDRH-60 series Din Rail Type Dc-Dc Converter Installation Guide
- September 16, 2024
- MEAN WELL
Table of Contents
- MEAN WELL DDRH-60 series Din Rail Type Dc-Dc Converter
- Features
- Applications
- Description
- Model Encoding
- SPECIFICATION
- Block Diagram
- Derating Curve
- Static Characteristics
- DC OK Relay Contact
- Mechanical Specification
- External FUSE wiring instruction
- Installation Instruction
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
MEAN WELL DDRH-60 series Din Rail Type Dc-Dc Converter
Features
- 150~ 1500Vdc 10:1 ultra – wide input range
- 57mm slim width
- 4KVac 1/0 high isolation(Reinforced isolation)
- Protections: Short circuit / Overload / Over voltage / Over temperature DC input under voltage / DC input reverse polarity
- Fanless design, cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- -30~+80°C ultra-wide operating temperature (> +55°C derating)
- Overvoltage category Il
- Operating altitude up to 5000 meters
- DC OK relay contact
- DC output voltage adjustable(+20%)
- Fully encapsulated
- 3 years warranty
Applications
- Photovoltaic power generation
- Renewable energy system
- High voltage freqency conversion
- Industrial control system
- Semiconductor fabrication equipment
- Electro-mechanical apparatus
- DC bus centralized application
- Energy storage system(ESS)
- Charging pile
- Third rail
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
DDRH-60 series is a 150 ~ 1500Vdc high reliable ultra-high input DIN rail type DC-DC converter that can supply stable working voltage for the load. It is suitable to be mounted on TS-35/7.5 or TS-35/15 rails. The main features are as follows: easy-to-install DIN rail type, narrow width(57mm) in a slim design, -30~+80° C wide range operating temperature, 4KVAC high isolation voltage, operation at 5000m altitude, high efficiency, low ripple & noise, complete protections and so on. DDRH-60 is compliant with UL1741 and BS EN/EN61000-6-2 standards regarding immunity for industrial environments. It is suitable for industrial automation, surveillance, and telecommunication and can be widely deployed in the applications of new energy generation such as solar power, windmill power generation, for instances, photovoltaic power systems, high voltage inverting, DC bus centralized applications,s and so forth.
Model Encoding
SPECIFICATION
MODEL | DDRH-60-5 | DDRH-60-12 | DDRH-60-24 | DDRH-60-48 |
---|
OUTPUT
| DC VOLTAGE| 5V| 12V| 24V| 48V
RATED CURRENT| 10A| 5A| 2.5A| 1.25A
CURRENT RANGE| 0 ~ 10A| 0 ~ 5A| 0 ~ 2.5A| 0 ~ 1.25A
RATED POWER| 50W| 60W| 60W| 60W
RIPPLE & NOISE (max.) **Note.2| 100mVp-p| 120mVp-p| 150mVp-p| 200mVp-p
VOLTAGE ADJ. RANGE| 5 ~ 6V| 12 ~ 15V| 24 ~ 29V| 48 ~ 54V
VOLTAGE TOLERANCE Note.3| ±1.5%| ±1.5%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.5%| ±0.5%| ±0.5%| ±0.5%
EXTERNAL CAPACITANCE LOAD (Max.)**| 6000μF| 4000μF| 2500μF| 1000μF
INPUT
| VOLTAGE RANGE Note.4| 150 ~ 1500Vdc
EFFICIENCY (Typ.)
| 200Vdc| 80%| 83%| 86%| 87%
800Vdc| 81%| 85%| 87%| 88%
1500Vdc| 76%| 81%| 84%| 83%
INRUSH CURRENT (max.)| COLD START 120A /1500Vdc 80A/800Vdc
30A/150Vdc
PROTECTION
| ****
OVERLOAD
| 105 ~ 135% rated output power
Protection type : Hiccup up mode when output voltage<55%, recovers
automatically after condition is removed;
Constant current limiting, recovers automatically after fault condition is removed within 55% ~ 100% rated output voltage
OVER VOLTAGE
| 6.6 ~ 8.4V| 16.5 ~ 21V| 30 ~ 38V| 55 ~ 60V
Protection type : Hiccup up mode, recovers automatically after fault condition
is removed
OVER TEMPERATURE| Protection type : Hiccup up mode, recovers
automatically after fault condition is removed
DC INPUT
| REVERSE POLARITY| By internal Bridge Diode, no damage, recovers
automatically after fault condition removed
UNDER VOLTAGE LOCKOUT| Under voltage protection range:120 ~
130Vdc , Under voltage release range:130 ~ 146.5Vdc
FUNCTION| DC OK SIGNAL| Relay contact rating(max.) : 30V / 1A
resistive
ENVIRONMENT
| WORKING TEMP.| -30 ~ +80℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +80℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 55℃)
VIBRATION| Component: 10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
OPERATING ALTITUDE Note.5| 5000 meters /OVCⅡ
OVER VOLTAGE CATEGORY| Ⅱ; According to EN62109-1; altitude up to 5000
meters
SAFETY & EMC
(Note.7)
| SAFETY STANDARDS| UL1741, CSA C22.2 No.107.1-16 , IEC62109-1(LVD) ,
EAC TP TC 004 approved
WITHSTAND VOLTAGE| I/P-O/P:4KVAC O/P-DC OK:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, 100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION
| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32)| Class A
Radiated| BS EN/EN55032(CISPR32)| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-
EMC IMMUNITY
| BS EN/EN55035, BS EN/EN61000-6-2
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, 10V, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, 2KV, criteria A
Surge| BS EN/EN61000-4-5| Level 4, 2KV/Vin+ ~ Vin-, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, 10V, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A, criteria A
Voltage Dips and interruptions
| ****
BS EN/EN61000-4-11
| >95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
OTHERS
| MTBF| 454.5K hrs min. MIL-HDBK-217F (25℃); 1439.7K hrs
min. Telcordia TR/SR-332 (Bellcore) (25℃)
DIMENSION| 5793.5105mm (WHD)
PACKING| 0.8Kg; 16pcs/12.8Kg/0.84CUFT
NOTE
| 1. All parameters NOT specially mentioned are measured at 600Vdc input, rated load, and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation, and load regulation.
4. Derating may be needed under low input voltage. Please check the derating curve for more details.
5. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).
6. Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
7. The power supply is considered a component that will be installed into the final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Static Characteristics
DC OK Relay Contact
- Contact Close
- PSU turns ON / DC OK.
- Contact Open
- PSU turns OFF / DC Fail.
- Contact Ratings (max.)
- 30V/1A resistive load.
Mechanical Specification
External FUSE wiring instruction
Installation Instruction
Installation Manual
- Please refer to: http://www.meanwell.com/manual.html
- File Name : DDRH-60-SPEC 2024-07-09
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>