MEAN WELL DUPS20 24V Din Rail Type Uninterruptible DC-UPS Module Owner’s Manual
- August 22, 2024
- MEAN WELL
Table of Contents
MEAN WELL DUPS20 24V Din Rail Type Uninterruptible DC-UPS Module
Features
- Uninterruptible DC-UPS controller
- Parallel connection to DC BUS (Power supply+ DC-UPS Module+ Batteries+ Load)
- Suitable for 24V system, up to 20A
- 2A Battery charging current
- Allows 4AH~135AH lead-acid various batte~ capacities
- Complete diagnostic and monitoring for DC BUS OK, battery discharge, battery fail
- LED indicator for signal status
- Protections: Battery reverse polarity protection & Short circuit(By internal detection)/Battery discharge / Over discharge current
- Cooling by free air convection
- Width only by 40mm
- 3 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
The DUPS20 is a 20A DIN rail type DC-UPS module, and it is paired with a power
supply and an external battery to achieve the backup function. When the AC
mains fails or is interrupted, the load will be immediately connected to the
battery pack to avoid interruption and to ensure the continuous operation of
the entire system (the operating time depends on the capacity of the battery
pack).
The main features of DUPS20 include: fast installation, small size (only 40mm
wide)suitability for 24V battery packs and various capacities of 4AH~135AH, 2A
battery charging current, low voltage disconnect for battery protection and
more. The product is suitable for use in data centers, security systems,
emergency lighting, wireless communication UPS, central monitoring systems,
etc.
Model Encoding
SPECIFICATION
MODEL | DUPS20 |
---|---|
DC UPS INPUT | NORMAL INPUT VOLTAGE |
INPUT VOLTAGE RANGE | 24 ~ 29Vdc |
RATED CURRENT | 20A |
DC UPS OUTPUT | VOLTAGE RANGE |
DISCHARGE CURRENT RANGE | 0 ~ 20A |
CHARGING CURRENT | 2A |
BATTERY | NORMAL BATTERY VOLTAGE |
24Vdc)
BATTERY TYPE| Lead-acid battery
EXTERNAL BATTERY CAPACITIES| 4AH ~ 135AH
PROTECTION| BATTERY POLARITY| Protected by internal detection, No
Damage, recovers automatically after fault conduction is removed
SHORT CIRCUIT| This protection only works when batteries are not
connected, No Damage. External fuse is recommended when batteries are
connected.
OVER DISCHARGE CURRENT| 21~23A,After 3 sec., unit will cut-off battery
discharging by relay
BATTERY DEEP DISCHARGE| Cut-off battery discharging by relay
FUNCTION| RELAY CONTACT RATINGS (max.)| 30VDC/1A resistive load
DC BUS OK| Relay contact : Short when DC voltage between 21~29V(±2%),
relay contacts
LED(Green) : DC BUS OK : light ; DC BUS fail : dark
BATTERY FAIL
Note.2| Short when battery voltage falls below 22V(±2%) or battery
failure is observed through the battery test function, relay contacts
LED(Red) : Battery over-discharge warning or battery broken : light ; Battery
OK : dark
BATTERY DISCHARGE| Relay contact : Short when battery in discharge
condition, relay contacts
LED(Yellow) : light : Battery discharging ; dark : Battery is not discharging
or discharging current < 1.0A
ENVIRONMENT| COOLING| Free air convection
WORKING TEMP.
Note.3| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 5 ~ 95% RH non-condensing
STORAGE TEMP.| -40 ~ +85℃
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 60℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE Note.4| 2000 meters/OVC II
SAFETY & EMC **(Note.5)| SAFETY STANDARDS| UL62368-1, EAC TP TC
004 approved
WITHSTAND VOLTAGE| IP/OP – Chassis : 0.5KVac ; IP/OP- Relay : 0.5KVac ;
Relay – Chassis : 0.5KVac
ISOLATION RESISTANCE| IP/OP – Chassis, IP/OP- Relay, Relay –
Chassis:>100M Ohms / 500Vdc / 25℃/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| —–| —–
Radiated| BS EN/EN55032(CISPR32)| Class B
Voltage Flicker| —–| —–
Harmonic Current| —–| —–
EMC IMMUNITY| BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact; criteria B
Level 2, 4KV air ; Level 1, 2KV contact; criteria A
Radiated| BS EN/EN61000-4-3| Level 3, 10V/m ; criteria A
EFT / Burst| BS EN/EN61000-4-4| Level 3, 2KV ; criteria A
Surge| BS EN/EN61000-4-5| Level 3, 0.5KV(DC input ports)
Conducted| BS EN/EN61000-4-6| Level 3, 10V ; criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m ; criteria A
OTHERS| MTBF| 1252.0K hrs min. Telcordia SR-332 (Bellcore) ; 482.1K
hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 40125.2113.5mm (WHD)
PACKING| 0.31Kg; 20pcs/7.2Kg/1.16CUFT
NOTE**|
- All parameters NOT specially mentioned are measured at normal input(24V) , rated load and 25℃ of ambient temperature.
- Every 30 seconds, unit will test the battery.If the testing result is faulty, unit will turn on “Battery Fail” relay contact and “Red LED” indicator.
- Derating may be needed over high ambient temperature. Please check the derating curve for more details.
- The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
- The unit is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360*720 mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests,please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf
※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Buffering Time
Discharge Current | Buffering Time(Reference) |
---|---|
7.5AH | 12AH |
2.5A | 6500s |
5A | 3000s |
10A | 1200s |
20A | 400s |
Mechanical Specification
Terminal Pin No. Assignment (TB ) 1
Pin No. | Assignment |
---|---|
1 | BAT INPUT + |
2 | BAT INPUT – |
3 | DC INPUT – |
4 | DC INPUT + |
Terminal Pin No. Assignment (TB2)
Pin No. | Assignment | LED |
---|---|---|
1 | BAT Discharge | YELLOW |
2
3| BAT Fail| RED
4
5| DC OK| GREEN
6
Installation Instruction
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 (For reference only. Not included with unit.)
This series fits DIN rail TS35/7.5 or TS35/15. 35.
For installation details, please refer to the Instruction manual.
Suggested Application
-
Back up connection for AC interruption.
-
Combine redundancy module (DR ) to back up AC interruption or failure of PSU.
Installation Manual
Please refer to: http://www.meanwell.com/manual.html
Documents / Resources
| MEAN
WELL DUPS20 24V Din Rail Type Uninterruptible DC-UPS
Module
[pdf] Owner's Manual
DUPS20, DUPS20 24V Din Rail Type Uninterruptible DC-UPS Module, 24V Din Rail
Type Uninterruptible DC-UPS Module, Rail Type Uninterruptible DC-UPS Module,
Uninterruptible DC-UPS Module, DC-UPS Module, Module
---|---