MEAN WELL DR-UPS40 DC UPS Module User Manual
- August 23, 2024
- MEAN WELL
Table of Contents
MEAN WELL DR-UPS40 DC UPS Module
Specifications
- Model: DR-UPS40
- DC Input / DC Voltage: 24 ~ 29V
- DC Bus Rated Current: 40A
- Battery Input / Output:
- Voltage Range: 21 ~ 29V
- Current Range: 0 ~ 40A
- Charge Current: 2A
- External Battery: 4 / 7 / 12AH / 24V
- Relay Contact Rating (max.): 30VDC, 1A
- Dimensions: 55.5 x 125.2 x 100mm (WHD)
- Weight: 0.55Kg
Product Usage Instructions
Installation
- Ensure the DC UPS Module is suitable for a 24V system up to 40A. Mount the module on DIN Rail TS35 with proper spacing.
- Connect the DC input and battery input/output according to the specified voltage and current ranges.
Operation
- Monitor the LED indicators for DC BUS OK, Battery Fail, and Battery Discharge status.
- Utilize the built-in battery test function periodically.
- Ensure proper ventilation for cooling by free air convection.
Maintenance
- Regularly check the external battery status and charge if needed.
- Keep the module clean from dust and debris to prevent overheating.
FAQ
-
Q: How often should I perform the battery test function?
A: It is recommended to perform the battery test function at least once every month to ensure optimal performance. -
Q: What should I do if the Battery Fail LED is lit?
A: If the Battery Fail LED is lit, check the external battery connection and voltage range to resolve any issues. If problems persist, contact customer support for assistance.
Features
- Battery controller for DIN Rail UPS system
- Parallel connection to DC BUS
- Suitable for 24V system up to 40A
- Installed on DIN Rail TS35 / 7.5 or 15
- Built-in battery test function
- Battery polarity protection
- Relay contact signal output and LED indicator for DC BUS OK, Battery Fail, and Battery Discharge
- Cooling by free air convection
- 3 years warranty
GTIN CODE MW
Search: https://www.meanwell.com/serviceGTIN.aspx
SPECIFICATION
MODEL | DR-UPS40 |
---|---|
DC INPUT / DC BUS | DC VOLTAGE (Typ.) Note.5 |
RATED CURRENT | 40A |
BATTERY INPUT / OUTPUT | VOLTAGE RANGE (Typ.) |
CURRENT RANGE | 0 ~ 40A |
CHARGE CURRENT (Typ.) Note.4 | 2A |
EXTERNAL BATTERY (Typ.) | 4 / 7 / 12AH / 24V |
FUNCTION | RELAY CONTACT RATING (max.) |
DC BUS OK | Relay contact: Short when DC voltage between 21~29V(±3%), |
relay contacts
LED(Green) : DC BUS OK : light ; DC BUS fail : dark
BATTERY FAIL Note.2| Short when the battery voltage falls below
21.9V(±3%) or battery failure is observed through the battery test function,
relay contacts
LED(Red): Battery over-discharge warning or battery broken: light ; Battery
OK: dark
BATTERY DISCHARGE| Relay contact: Short when battery in discharge
condition, relay contacts
LED(Yellow):light : Battery discharging ; dark : Battery is not discharging or
discharging current<2.0A
ENVIRONMENT| WORKING TEMP.| -20 ~ +70℃
WORKING HUMIDITY| 20 ~ 90% RH
STORAGE TEMP., HUMIDITY| -20 ~ +85℃, 10 ~ 95% RH
VIBRATION| Component : 10 ~ 500Hz, 2G 10min./1cycle, 60min. each X, Y,
and Z axes ; Mounting: Compliance to IEC600068-2-6
SAFETY & EMC
(Note 3)
| WITHSTAND VOLTAGE| Terminal-Chassis :0.5KVAC, Relay Contacts-Terminal
:0.5KVAC
ISOLATION RESISTANCE| Terminal-Chassis :>100M Ohms / 500VDC / 25℃/ 70%
RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS
EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, heavy
industry level, criteria A, EAC TP TC 020
OTHERS| MTBF| 1365.7K hrs min. Telcordia SR-332 (Bellcore) ;
161.9K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 55.5125.2100mm (WHD)
PACKING| 0.55Kg; 20pcs/12Kg/1.49CUFT
NOTE|
- All parameters NOT specially mentioned are measured at rated load and 25℃ of ambient temperature.
- Battery failure will only function at UPS mode with the battery connected. Every 25 seconds, unit will send out test signal through the “Battery Fail” relay contact and LED indicator once the battery is fail.
- The power supply is considered a component that will be installed into the final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf
- Battery charging will be in progress when DC input > battery voltage.
- DR-UPS40 will be in operation when DC input is applied at the beginning.
- The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
- Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Mechanical Specification
Block Diagram
Derating Curve
Suggested Application
- Back up connection for AC interruption
- Combine redundancy module (DR-RDN20) to back up AC interruption or failure of PSU
File Name:DR-UPS40-SPEC 2024-01-26