MGC BB-4002R Back Box and Red Door Instruction Manual
- August 17, 2024
- MGC
Table of Contents
- BB-4002R Back Box and Red Door
- Specifications:
- Product Usage Instructions:
- Mounting Instructions:
- BB-4002R Dimensions and Wiring:
- BB-4006R Dimensions and Wiring:
- Cable Routing Guidelines:
- Q: Can I use BB-4002R for more than 2 MIX-4000-M Series
- Q: Are the back boxes weatherproof?
- Q: What is the purpose of the optional ground screw in
BB-4002R Back Box and Red Door
“`html
Specifications:
Models: BB-4002R, BB-4006R
Description: Multi Module Enclosures
BB-4002R: Back Box and Red Door for 1 or 2
MIX-4000-M Series Modules
BB-4006R: Back Box and Red Door for up to 6
MIX-4000-M Series Modules
Product Usage Instructions:
Mounting Instructions:
Refer to the module manual for specific mounting
instructions.
BB-4002R Dimensions and Wiring:
Back view: 12 3/4 x 9 7/5 inches
Bottom view: 9 31/32 x 3 13/16 inches
Front view: 4 knockouts on top, 4 knockouts on bottom
BB-4006R Dimensions and Wiring:
Dimensions: 12 1/2 x 8 1/2 x 10 1/2 inches
Optional ground screw
Knockouts on top, bottom, and sides
Cable Routing Guidelines:
-
Maintain a separation of at least 1/4″ (6.4 mm) between
power-limited and non-power-limited wiring. -
Follow the provided examples for cable routing in both BB-4002R
and BB-4006R. -
Use the designated areas for power-limited and
non-power-limited wiring as indicated in the manual.
Frequently Asked Questions (FAQ):
Q: Can I use BB-4002R for more than 2 MIX-4000-M Series
Modules?
A: No, BB-4002R is designed for a maximum of 2 modules. For more
modules, consider using BB-4006R.
Q: Are the back boxes weatherproof?
A: The back boxes are not weatherproof. They are intended for
indoor use only.
Q: What is the purpose of the optional ground screw in
BB-4006R?
A: The optional ground screw is provided for grounding purposes
to ensure electrical safety.
“`
BB-4002R and BB-4006R
Multi Module Enclosures
BB-4002R: Back Box and Red Door for 1 or 2 MIX-4000-M Series Modules BB-4006R:
Back Box and Red Door for up to 6 MIX-4000-M Series Modules Refer to the
module manual for mounting instructions.
BB-4002R Dimensions and Wiring
12 3/4″
9″ 7 1/5″”
Back view
3 13/16″
9 31/32″ 4 knockouts on top
Bottom view
Knockouts
Front view
4 knockouts on bottom LT-6736 Rev 0 June 2023 Page 1 of 5
BB-4006R Dimensions and Wiring
12 1/2″ 8 1/2″
10 1/2″ 23″
20 1/4″
5 19/32″
Optional ground screw (use either ground screw)
2 knockouts on top
3 knockouts on the side
Knockouts on back
3 knockouts on the side
Ground screw
2 knockouts on bottom
LT-6736 Rev 0 June 2023 Page 2 of 5
Cable Routing in BB-4002R Example #1
Maintain a separation of 1/4″ (6.4 mm) minimum between power-limited and non-
power-limited wiring at all times.
Gray area (solid outline) marks the location for all non-power-limited wiring.
Cable Routing in BB-4002R Example #2
Maintain a separation of 1/4″ (6.4 mm) minimum between power-limited and non-
power-limited wiring at all times.
Gray area (solid outline) marks the location for all non-power-limited wiring.
Minimum 1/4″
Min. 1/4″
Minimum 1/4″
Green area (dotted outline) marks the location for all power-limited wiring.
Right side of box is reserved for all power limited wiring.
Green area (dotted outline) marks the location for all power-limited wiring.
Right side of box is reserved for all power limited wiring.
LT-6736 Rev 0 June 2023 Page 3 of 5
Cable Routing in BB-4006R Example #1
Maintain a separation of 1/4″ (6.4 mm) minimum between power-limited and non- power-limited wiring at all times. Gray area (solid outline) marks the location for all non-power-limited wiring.
Green area (dotted outline) marks the location for all power-limited wiring.
Right side of box is reserved for all power limited wiring.
Minimum 1/4″ Minimum 1/4″
LT-6736 Rev 0 June 2023 Page 4 of 5
Cable Routing in BB-4006R Example #2
Maintain a separation of 1/4″ (6.4 mm) minimum between power-limited and non-
power-limited wiring at all times.
Gray area (solid outline) marks the location for all non-power-limited wiring.
Green area (dotted outline) marks the location for all power-limited wiring.
Right side of box is reserved for all power limited wiring.
Minimum 1/4″
Min. 1/4″
Min. 1/4″ Minimum 1/4″
Minimum 1/4″ Min. 1/4″
Min. 1/4″ Minimum 1/4″
Minimum 1/4″ Min. 1/4″
Min. 1/4″
LT-6736 Rev 0 June 2023 Page 5 of 5