MGC MIX-4010-DUCT Photoelectric Duct Smoke Detector Instruction Manual
- October 30, 2023
- MGC
Table of Contents
MGC MIX-4010-DUCT Photoelectric Duct Smoke Detector
The MIX-4010-D smoke detector is
designed to continuously check air obscuration and report it to the Fire-Alarm
panel using a fully digital communication protocol. The detector is compatible
with
FleX-NetTM FX-4000, FX400, and FX-401 fire alarm control panels. It has a
sensitivity range of 1.52%/ft – 2.05%/ft and comes with a dust cover for
protection during shipping and installation.
Specifications
- Normal Operating Voltage: 15 to 30VDC
- Maximum Alarm Current (LED on): 3.2mA (LED on)
- Standby Current: 160A (LED flashing)
- Temperature Range:
- Dimensions: 4 1/4 Diameter, 1 3/4 Height
- Accessories: MIX-4090 Programmer
- Detector LED Colors:
- Alarm: Red (Steady on)
- Air Sampling: Green (Flash)
- Fault: Yellow (Steady on)
Installation Instructions
This detector must be installed on the base that comes with MIX-4010-DUCT.
The detector address should be programmed using the MIX-4090 hand-held device
before inserting the detector on the base. See manual
LT-6146 for programming. Addresses 1 to 240 can be used for any device on a
SLC loop. Each device on a loop must have a unique address.
- Position the detector centrally on its adapter base ensuring it is level.
- Rotate clockwise applying gentle pressure. The detector will drop into its keyed location.
- Continue to rotate clockwise a few degrees until the detector is fully engaged in the base.
- When the detector is firmly engaged, check the alignment of the raised reference marks on the detector and on the base.
Important notes on detector installation
Disconnect loop power before installing the detector.
This detector comes with a dust cover to protect the device during shipping
and when first installed. It is not intended to provide complete protection
against contamination, therefore, detectors should be removed from their base
before construction, major re-decoration or other dust producing work is
started. Dust covers must be removed before the system becomes operational.
Smoke detectors are not to be used with detector guards unless the combination
has been evaluated and found suitable for that purpose.
DETECTOR DESCRIPTION
The MIX-4010-D smoke detector continuously checks air obscuration and reports
it to the Fire-Alarm panel using a fully digital communication protocol. The
MIX-4010-D is compatible with FleX-Net™ FX-4000, FX-400, and FX-401 fire alarm
control panels.
Before installing this device please thoroughly read this manual and refer to
the applicable codes for guidance on location, spacing and acceptable use.
Also seek guidance from the compatible control panel instructions for the
device operation modes and the configuration requirements.
Detector LED Colors
Alarm| Red (Steady on)
Air Sampling| Green (Flash)
Fault| Yellow (Steady on)
25 Interchange way, Vaughan Ontario. L4K 5W3
Phone: 905.660.4655;
Fax: 905.660.4113
Web: www.mircomgroup.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>