MGC 400-WP Series Weather Protected Notification Appliances Instruction Manual

May 15, 2024
MGC

MGC-LOGO

MGC 400-WP Series Weather Protected Notification Appliances

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
\(9\)

Product Information

Specifications

  • Operating temperature: –
  • Humidity range: –
  • Strobe flash rate: 1 Hz
  • Nominal voltage: Regulated 24 VDC / 24 VFWR
  • Operating voltage range (RMS): 16-33 VDC/VFWR
  • Input terminal wire gauge: 22 AWG to 12 AWG
  • Installation environment: Outdoor environment wet location

Description
The 400 series weather-protected horn, strobe, and horn/strobe NAC devices provide a wide range of audible and visual settings in a single compact device. Audible settings include Temporal 3, Continuous, March Time, and 20 BPM tones adjustable for Low or High volume settings. Candela settings can be field-configured for 15, 30, 75, 110, 185, and 15/75 cd.

Kit Includes

  • Mounting plate #4-40 x 3/8 screw
  • Shorting clip
  • 8-32 x 3/4 screws (x2) and #6-32 x 3/4 screws (x2)

  • Protective cover

Setting the Candela (FS-400-RR-WP and FHS-400-RR-WP only)

  1. Pull out the plastic selector tab from the back of the device.
  2. Re-insert the selector tab into the notch labeled with the desired candela setting.

Setting the DIP Switches

Note: DIP switches 2 and 3 are not used. By default, they are OFF.

NOTE for DIP switch 1: Use NON-SYNCHRONIZED when synchronization is not needed. Use SYNCHRONIZED when synchronization is required.

Input
Regulated 24 VDC/FWR (Non-synchronized)

  • DIP Switch 1: ON

Synchronized: OFF (default)

  • DIP Switch 4: OFF
  • DIP Switch 5: ON (default)
  • DIP Switch 6: ON (default)

Shorting Clip
In order to test the wiring, place the shorting clip on the middle two terminals after wiring. Remove before mounting.

Wiring
From FACP + or previous – device to next device end of line.

Weather-Protected Enclosure
CAUTION
: Do not remove rubber gasket.

Frequently Asked Questions (FAQ)

  • Q: Can the candela settings be adjusted in the field?
    A: Yes, the candela settings can be field-configured for different values.

  • Q: What are the available audible settings?
    A: The audible settings include Temporal 3, Continuous, March Time, and 20 BPM tones that can be set for Low or High volume settings.

  • Q: How should I test the wiring before mounting the device?
    A: Use the provided shorting clip on the middle two terminals after wiring to test the connections.

400-WP Series Weather Protected Notification Appliances

About this Manual
This manual is included as a quick reference for installation. For further information on the use of this device with an FACU, please refer to the panel’s manual.

Note: This manual should be left with the owner/operator of this equipment.
This manual covers the following models:
FH-400-RR-WP Weather protected wall/ceiling mounted horn, red FS-400-RR-WP Weather protected wall mounted strobe, red FHS-400-RR-WP Weather protected wall mounted horn/strobe, red

Notes

  • DO NOT PAINT OR ALTER FACTORY APPLIED FINISH IN ANY WAY.
  • Input terminal wire gauge: 22 AWG to 12 AWG.
  • Use the information in this document to determine the total current draw of the devices. The total current draw of the devices must not exceed the power supply of the FACU. In all cases, the installer should consider the voltage drop to ensure that the last device on the circuit operates within its rated voltage.
  • Maximum line resistance for a single wall mounted unit at 15 candela is 150 Ω.
  • Wiring must be in accordance with CSA C22.1 Section 32, NFPA 70, and NFPA 72.
  • These devices cannot operate on coded power supplies.

Description
The 400 series weather-protected horn, strobe and horn/strobe NAC devices provide a wide range of audible and visual settings in a single compact device. The audible settings include Temporal 3, Continuous, March Time and 20 BPM tones that can each be set for Low or High volume settings. The candela settings can be field-configured for 15, 30, 75, 110, 185, and 15/75 cd.

Dimensions

  • 8 5/8” (219 mm) W
  • 7 7/16” (189 mm) H
  • 4 5/8” (117 mm) D

Specifications

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
01

The Kit Includes

Figure 1 Included parts

Setting the Candela (FS-400-RR-WP and FHS-400-RR-WP only)

The candela can be set to 15, 30, 75,110, 185, and 15/75. The factory default setting is 15.

  1. Pull out the plastic selector tab from the back of the device.
  2. Re-insert the selector tab into the notch that is labeled with the desired candela setting.

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
\(2\)

Setting the DIP Switches

Note: DIP switches 2 and 3 are not used. By default they are OFF.
NOTE for DIP switch 1: Use NON-SYNCHRONIZED when the appliances do not need to be synchronized. Use SYNCHRONIZED when synchronization is required, either through an external sync module or compatible FACU or PSU supporting MGC sync protocol.

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
02

Shorting Clip
In order to test the wiring, place the shorting clip on the middle two terminals after wiring.
Remove the shorting clip before mounting the device.MGC-400-WP-Series-
Weather-Protected-Notification-Appliances- \(3\)

Wiring

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
\(4\)

Weather-Protected Enclosure

The enclosure is rated for Outdoor Environment Wet Location. -40 °C to +66 °C (-40 F to 151 F)

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
\(5\)

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
\(6\)

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
\(7\)

Mounting to the Wall or Ceiling

MGC recommends spacing notification appliances in compliance with CAN/ULC S524 and NFPA 72.
Mount the unit directly to the wall or ceiling depending on the model. When mounting on the wall, mount the enclosure with the word TOP at the top, and mount the device with the MGC nameplate at the top.

  1. Before mounting, disassemble the unit as show in figure 7.
  2. Secure the enclosure directly to the wall or ceiling.
  3. Attach the mounting plate to the holes marked NAC in the enclosure with the 2 included screws.
  4. Snap the horn, strobe, or horn/strobe on to the mounting plate and secure it with the securing screw. Snap the nameplate over the screw.
  5. Secure the transparent cover over the assembly with the 4 included screws.

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
\(7\)

Figure 7 Mount a horn, strobe, and horn/strobe in enclosure

Removing the Device from the Mounting Plate
To remove the device from the mounting plate, remove the nameplate and the securing screw, then insert a flathead screwdriver into the slot between the device and the mounting plate, and rotate the screwdriver.

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
\(9\)

Operating RMS Currents (mA)
FS-400-RR-WP Strobe Operating RMS Currents (mA)

Candela| Regulated 24 VDC

(16-33 VDC)

| Regulated 24 VFWR

(16-33 VFWR)

---|---|---
15| 28| 64
30| 44| 106
75| 108| 189
15/75| 109| 189
110| 115| 189
185
| 221| 241

  • For General Signaling only

FH-400-RR-WP Horn Operating RMS Currents (mA)

MGC-400-WP-Series-Weather-Protected-Notification-Appliances-
03

FHS-400-RR-WP Horn/Strobe Operating RMS Currents (mA)

| Regulated 24 VDC| Regulated 24 VFWR
---|---|---
Candela| Coded Tone *, High Volume **| Continuous Tone, High Volume| Coded Tone *, High Volume **| Continuous Tone, High Volume
15| 38| 51| 69| 73
30| 52| 65| 99| 102
75| 112| 125| 189| 194
15/75| 113| 126| 190| 196
110| 115| 130| 190| 199
185
| 204| 225| 236| 243

  • Coded Tone is representative of Temporal, March, and 20 BPM tones.
  • High volume is representative of low volume.
  • For General Signaling only

Audible Ratings
Overall Sound Pressure Level (Reverberant) @ 10 feet (dBA) for FH-400-RR-WP, FHS-400-RR-WP

Volume| 16 VDC| 24 VDC| 33 VDC| 16 VFWR| 24 VFWR| 33 VFWR
---|---|---|---|---|---|---
High| 83.1| 85.6| 85.8| 79.7| 81.5| 82.6
Low| 77| 80.6| 82| 75.3| 77.6| 79.3

Testing conducted on continuous tone, representative of Temporal, Coded, and 20 BPM tones.

Directional Sound Characteristics for FH-400-RR-WP, FHS-400-RR-W

Horizontal Axis|
---|---
± 29°| -3 dbA
± 48°| -6 dbA
± 90°| -9.9 dbA
|
Vertical Axis|
± 46°| -3 dbA
± 72°| -6 dbA
± 90°| -7.3 dbA

Light Output for FHS-400-RR-WP and FS-400-RR-WP

Note: The following values are shown as percentages of the rated light output at any candela setting.

Degrees % of Candela Rating
Horizontal Dispersion Vertical Dispersion, Wall to Floor
±0 184
±5 178
±10 173
±15 169
±20 162
±25 153
±30 147
±35 143
±40 136
±45 140
±50 150
±55 128
±60 75
±65 75
±70 57
±75 61
±80 69
±85 77
±90 63
Compound±45° 51

Warranty

Purchase of all MGC products is governed by: https://www.mircom.com/product- warranty
https://www.mircom.com/purchase-terms-and-conditions https://www.mircom.com /software-license-terms-and-conditions

Canada
25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 888-660-4655 5

U.S.A
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Tel: 905-660-4655
888-660-4655

www.mircomgroup.com LT-6511 Rev. 0 Jan. 2024