MGC MIX-4003-R Relay Base Instruction Manual

June 5, 2024
MGC

MGC -MIX-4003-R -Relay -Base

MGC -MIX-4003-R -Relay -Base
-product

ABOUT THIS MANUAL

This manual is included as a quick reference for installation and should be left with the owner/operator of this equipment. For further information on the use of this device with a FACP, please refer to the panel’s manual.
Note: This manual should be left with the owner/operator of this equipment.

RELAY BASE DESCRIPTION

The MIX-4003-R relay base is designed to meet UL268/ULC S529 requirements for smoke detector, UL521/ULC S530 requirements for heat detector. The MIX-4003-R must be used with a compatible MGC control panel. The device can control one independent circuit while using one address. The MIX-4003-R provides one form C (SPDT) contact rated at 2A at 30Vdc, or 0.5A at 125Vac and a compatible panel can switch discrete contacts by code command. Circuit connections to the relay contacts are not supervised by the base. MIX-4003-R supports group activation capability for fast reaction time.

Operating temperature| 0⁰C to 49⁰C

(32⁰F to 120⁰F)

---|---
Humidity range| 0% to 93%
SLC Standby Current| 1.16 mA
SLC Alarm Current| 1.18 mA
Base Diameter| 182mm [7-3/16 in]
Base Height| 32mm [ 1-1/4 in]
Terminal wire gauge| 12-22 AWG

KEY COMPONENT

MGC -MIX-4003-R -Relay -Base -fig 2

A mounting plate in figure 2 is mounted first on the electrical box and all wiring is done on integral screw connectors. The connections are apparent and can be visually inspected before the sounder base itself is mounted. Then, the enclosure containing the electronics, the sounder and the detector base can plugged-in and secured.
Note: This device should be installed as per applicable requirements of the authorities having jurisdiction.

WIRING Before installing this device seek guidance from the compatible control panel instructions for the device operation modes and the configuration requirements. It is recommended to remove power from SLC and NAC lines before performing installation.Use the information in this document to determine the total current draw of the devices. The total current draw of the devices must not exceed the NAC output capacity of the panel. In all cases, the installer should consider the voltage drop to ensure that the last device on the circuit operates within its rated voltage. Please consult fire panel installation manual for guidance on wire resistance and length. For maximum strobe operating current, please refer to Table 4. Do not loop signal circuit field wires around terminals. Electrical supervision requires wire run to be broken at each end.

  • Correct: Wire run is broken
  • Wrong: Wire is looped around terminal MGC -MIX-4003-R -Relay -Base -fig 4

Note: Wiring must be in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, section 32 and/or NFPA 70.
CAUTION
FOR SYSTEM SUPERVISION, FOR ALL TERMINAL TAPS, DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
ATTENTION
NE PAS UTILISER DE FILS EN BOUCLE SOUS LES BORNES. POUR FOURNIR UN BON SUIVI DES CONNEXIONS. INTERROMPRE LA CONTIUITÉ DES CÂBLES.
MOUNTING
MGC recommends spacing speaker strobe appliances in compliance with CAN/ULC S524 and/or NFPA72. The mounting plate is compatible with 3” by 2” single gang device boxes, 3-3/4” by 4” double gang boxes, 4” by 2” single gang utility boxes, standard 4” by 4” boxes, and standard 4” octagon boxes.

  1. Attach the mounting plate to electrical box with two mounting #8-32 x 3/4″ screws.
  2. Slide down the sounder base enclosure until the connection blades touch the clips on the mounting plate.
  3. Secure the mounting plate with securing M3 x25 mm screws.MGC -MIX-4003-R -Relay -Base -fig 5

MOUNTING DETECTOR

If the detector type and address has be visible from the outside, break the address tab inside the detector base and insert it in the outer rim of the base. See figures 7.MGC -MIX-4003-R -Relay -Base -fig
6

The detector can then be placed on the top base using the following steps (figure 8):

  1. Position the detector centrally on its adapter base ensuring it is level.
  2. Rotate clockwise applying gentle pressure. The detector will drop into its keyed location.
  3. Continue to rotate clockwise a few degrees until the detector has fully engaged in the adapter base.
  4. When the detector is firmly engaged, check the alignment of the raised reference marks on the detector and on the base (figure 9).MGC -MIX-4003-R -Relay -Base -fig 7MGC -MIX-4003-R -Relay -Base -fig 8

Model Numbers

MIX-4003-R 4000 SERIES RELAY BASE

AccessoriesMGC -MIX-4003-R -Relay -Base -fig 9

Documents / Resources

| MGC MIX-4003-R Relay Base [pdf] Instruction Manual
MIX-4003-R Relay Base, MIX-4003-R, Relay Base
---|---
| MGC MIX-4003-R Relay Base [pdf] Installation Guide
MIX-4003-R Relay Base, MIX-4003-R, Relay Base

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MGC User Manuals

Related Manuals