MEAN WELL HDR-30 series Ultra Slim Step Shape Din Rail User Manual

August 17, 2024
MEAN WELL

MEAN WELL HDR-30 series Ultra Slim Step Shape Din Rail

Product Usage Instructions

Installation

  1. Ensure the power is disconnected before installation.
  2. Mount the HDR-30 series device on a DIN rail securely.
  3. Connect the input power within the specified voltage range.

Operation

  1. Apply power within the input voltage range of 85~264VAC.
  2. Verify that the device is functioning correctly based on the load requirements.
  3. Monitor for any abnormal behavior or overheating during operation.

Maintenance

  1. Regularly inspect the device for any signs of damage or wear.
  2. Clean the device as needed to prevent dust accumulation.
  3. Ensure proper ventilation around the device for optimal performance.

FAQ

  • Q: What is the width of the HDR-30 series DIN Rail?
  • A: The HDR-30 series features an ultra-slim design with a width of 35mm (2SU).
  • Q : What is the input voltage range for the device?
  • A: The device supports a universal input voltage range of 85~264VAC, with operational capability up to 277VAC.
  • Q: Does the device have no load power consumption?
  • A : Yes, the device is designed with no load power consumption for energy efficiency.

Features

  • Ultra slim design with 35mm(2SU) width
  • Universal input 85~264VAC(277VAC operational)
  • No load power consumption<0.3W
  • Isolation class II
  • Pass LPS (Limited power source)
  • DC output voltage adjustable
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection (working temperature: -30~+70°C)
  • DIN rail TS-35/7.5 or 15 mountable
  • LED indicator for power on
  • 3 years warranty

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE

Description

HDR-30 is one economical ultra slim 30W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 35mm(2SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-30 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 90%, the entire series can operate at the ambient temperature between -30°C and 70°C under air convection. The complete prot ction functions and relevant certificates for home automation and industrial control apparatus (IEC62368-1, UL508,UL62368-1, BS EN/EN61558-2-16) make HDR-30 a very competitive power supply solution for household and industrial applications.

Model Encoding

SPECIFICATION

MODEL| HDR-30-5| HDR-30-12| HDR-30-15| HDR-30-24| HDR-30-48
---|---|---|---|---|---







OUTPUT

| DC VOLTAGE| 5V| 12V| 15V| 24V| 48V
RATED CURRENT| 3A| 2A| 2A| 1.5A| 0.75A
CURRENT RANGE| 0 ~ 3A| 0 ~ 2A| 0 ~ 2A| 0 ~ 1.5A| 0 ~ 0.75A
RATED POWER| 15W| 24W| 30W| 36W| 36W
RIPPLE & NOISE (max.) Note.2| 80mVp-p| 120mVp-p| 120mVp-p| 150mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| 4.5 ~ 5.5V| 10.8 ~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V| 43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 50ms/230VAC        500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)| 30ms/230VAC        12ms/115VAC at full load



INPUT

| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational )        120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 82%| 88%| 89%| 89%| 90%
AC CURRENT (Typ.)| 0.88A/115VAC        0.48A/230VAC
INRUSH CURRENT (Typ.)| COLD START 25A/115VAC        45A/230VAC



PROTECTION

| ****

OVERLOAD

| 105 ~ 160% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed

Constant current limiting within 50% ~100% rated output voltage, recovers automatically after the fault condition is removed


OVERVOLTAGE

| 5.75 ~ 7.5V| 15 ~ 18V| 18.8 ~ 22.5V| 30 ~ 36V| 57.6~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover





ENVIRONMENT

| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVERVOLTAGE CATEGORY| Ⅲ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters










SAFETY & EMC

(Note 4)

| SAFETY STANDARDS| UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1,IEC62368-1, EAC TP TC 004, BSMI CNS14336-1 approved;

Design refers to TUV BS EN/EN62368-1

WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH




EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-







EMC IMMUNITY

| BS EN/EN55035,  BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, Criteria A
EFT/Burst| BS EN/EN61000-4-4| Level 3, Criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, Criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, Criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30% dip 25 periods,

>95% interruptions 250 periods


OTHERS

| MTBF| 3670.4K hrs min.     Telcordia SR-332 (Bellcore) ; 968.1K hrs min.     MIL-HDBK-217F (25℃)
DIMENSION| 359054.5mm (WHD)
PACKING| 0.13Kg;96pcs/14.2Kg/1.04CUFT
NOTE| 1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.

3.  Tolerance : includes set up tolerance, line regulation and load regulation.

4.  The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

5.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Derating Curve

Output Derating VS Input Voltage

Mechanical Specification

(Unit: mm , tolerance ± 0.5mm

Terminal Pin No. Assignment

Pin No. Assignment Pin No. Assignment
1 +V 3 AC/L
2 -V 4 AC/N

Installation Manual

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals