MEAN WELL HDR-100 Ultra Slim Step Shape DIN Rail Power Supply User Manual

August 17, 2024
MEAN WELL

MEAN WELL HDR-100 Ultra Slim Step Shape DIN Rail Power Supply

Product Usage Instructions

Installation

  1. Ensure the power source is turned off before installation.
  2. Mount the Ultra Slim Step Shape DIN Rail in a suitable location using appropriate mounting hardware.
  3. Connect the input wires to the designated terminals following the provided wiring diagram.

Powering Up

  1. After installation, turn on the power source and verify the input voltage falls within the specified range.
  2. The Ultra Slim Step Shape DIN Rail should now be ready for use.

Maintenance

  1. Regularly inspect the device for any signs of damage or wear.
  2. Keep the device clean and free from dust accumulation to ensure optimal performance.

FAQ

  • Q: What is the operational voltage range of the Ultra Slim Step Shape DIN Rail?
  • A: The operational voltage range is 85~264VAC, with 277VAC operational capability.
  • Q : Is the Ultra Slim Step Shape DIN Rail suitable for use in industrial settings?
  • A : Yes, the product meets various safety standards making it suitable for industrial applications.
  • Q: How can I check the no-load power consumption of the device?
  • A: The no-load power consumption information should be available in the product specifications or user manual.

Features

  • Ultra slim design with 70mm(4SU) width
  • Universal input 85~264VAC(277VAC operational)
  • No load power consumption< 0.3W
  • Isolation class I
  • Pass LPS (Limited power source) for Blank type
  • DC output voltage adjustable
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection (working temperature:-30~+70°C)
  • DIN rail TS-35/7.5 or 15 mountable
  • LED indicator for power on
  • 3 years warranty

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

HDR-100 is one economical ultra slim 100W DIN rail power supply series, adapted to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 70mm(4SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-100 is designed with plastic housing that can effectively prevent users from electric hazards. With working efficiency up to 90%, the entire series can operate at the ambient temperature between -30°C and 70°C under air convection. The complete protection functions and relevant certificates for home automation and industrial control apparatus (IEC62368-1,UL508, UL62368-1, BS EN/EN61558-2-16)make HDR-100 a very competitive power supply solution for household and industrial applications.

Model Encoding

Type Description Note
Blank 92W max, Pass LPS with a narrower output adjustable range In stock
N 100W max, Non-LPS with a wider output adjustable range In stock

SPECIFICATION

MODEL| HDR-100-12| HDR-100-12N| HDR-100-15| HDR-100-15N| HDR-100-24| HDR-100-24N| HDR-100-48| HDR-100-48N
---|---|---|---|---|---|---|---|---








OUTPUT

| DC VOLTAGE| 12V| 15V| 24V| 48V
RATED CURRENT| 7.1A| 7.5A| 6.13A| 6.5A| 3.83A| 4.2A| 1.92A| 2.1A
CURRENT RANGE| 0 ~ 7.1A| 0 ~ 7.5A| 0 ~ 6.13A| 0 ~ 6.5A| 0 ~ 3.83A| 0 ~ 4.2A| 0 ~1.92A| 0 ~ 2.1A
RATED POWER| 85.2W| 90W| 92W| 97.5W| 92W| 100.8W| 92.2W| 100.8W
RIPPLE & NOISE (max.) Note.2| 120mVp-p| 120mVp-p| 150mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| Pass LPS| 12 ~ 13V| 15 ~ 17V| 24 ~ 25.5V| 48 ~ 48.7V
Non LPS| 12~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V| 43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 60ms/230VAC         500ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)| 30ms/230VAC     12ms/115VAC at full load




INPUT

| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational )        120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 88%| 89%| 90%| 90%
AC CURRENT (Typ.)| 3A/115VAC      1.6A/230VAC
INRUSH CURRENT (Typ.)| COLD START 35A/115VAC         70A/230VAC



PROTECTION

| ****

OVERLOAD

| HDR-100 : 102 ~ 110% rated output power ; HDR-100-xxN : 105 ~ 150% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed

Constant current limiting within 50% ~100% rated output voltage, recovers automatically after the fault condition is removed


OVER VOLTAGE

| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~ 64.8V
Protection type: Shut down o/p voltage, re-power on to recover





ENVIRONMENT

| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVER VOLTAGE CATEGORY| Ⅲ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters











SAFETY & EMC

(Note 5 )

| SAFETY STANDARDS| UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1

approved; Design refer to TUV BS EN/EN62368-1

WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH




EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current (Note 5)| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-







EMC IMMUNITY

| BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, Criteria A
EFT/Burst| BS EN/EN61000-4-4| Level 3, Criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, Criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, Criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30% dip 25 periods,

>95% interruptions 250 periods


OTHERS

| MTBF| 3271.9K hrs min.      Telcordia SR-332 (Bellcore) ; 856.5K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION| 709054.5mm (WHD)
PACKING| 0.27Kg; 48pcs/13.74Kg/0.96CUFT





NOTE

| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.

3.  Tolerance : includes set up tolerance, line regulation, and load regulation.

4.  Harmonic current test at 90% load for HDR-100-xxN.

5. The power supply is considered an independent unit, but the final equipment still needs to confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

6.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).

※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Derating Curve VS Ambient Temperature

Output Derating VS Input Voltage

Mechanical Specification

(Unit: mm , tolerance ± 0.5mm)

Installation Manual

Please refer to: http://www.meanwell.com/manual.html

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals