MEAN WELL HRP-200 Series 200W Single Output with PFC Function User Guide

August 16, 2024
MEAN WELL

HRP-200 Series 200W Single Output with PFC Function

“`html

Product Specifications

  • Model: HRP-200 series

  • Output Power: 200W

  • Input: Universal AC input / Full range

  • Active PFC Function: PF>0.95

  • Efficiency: Up to 89%

  • Protections: Short circuit, Overload, Over voltage, Over
    temperature

  • Cooling: Free air convection

  • Low Profile: 1U, 38mm

  • Constant Current Limiting Circuit

  • Remote Sense Function

  • Warranty: 5 years

Product Usage Instructions:

Installation:

  1. Ensure the input voltage matches the product
    specifications.

  2. Connect the output terminals to your device following the
    correct polarity.

  3. Ensure proper ventilation around the power supply for effective
    cooling.

Operation:

  1. Switch on the power supply using the designated power
    switch.

  2. Monitor the LED indicators for any alerts or issues.

  3. Avoid overloading the power supply beyond its rated
    capacity.

Maintenance:

  1. Regularly clean the power supply unit to prevent dust
    accumulation.

  2. Check for any loose connections or abnormal sounds during
    operation.

  3. Refer to the user manual for troubleshooting steps in case of
    malfunctions.

Frequently Asked Questions (FAQ):

Q: What is the warranty period for the HRP-200 series?

A: The product comes with a 5-year warranty.

Q: How can I adjust the output voltage of the power

supply?

A: The voltage adjustment range is specified in the manual.
Follow the provided guidelines for adjusting the voltage within the
allowed range.

Q: What should I do in case of a short circuit?

A: The power supply is equipped with short circuit protection.
Disconnect the load and identify the cause of the short circuit
before reconnecting.

“`

200W Single Output with PFC Function

HRP-200 series

GTIN CODE

Features :

User’s Manual

Universal AC input / Full range

Built-in active PFC function, PF>0.95

High efficiency up to 89%

Withstand 300VAC surge input for 5 seconds

Protections: Short circuit / Overload / Over voltage / Over temperature

Cooling by free air convection

Built-in constant current limiting circuit

1U low profile 38mm

Built-in remote sense function

5 years warranty

MW Search: https://www.meanwell.com/serviceGTIN.aspx
SPECIFICATION

AS/NZS 62368.1

Bauart gepruft Sicherheit
egelma ge od o s be wac g
www. tuv.com ID 2000000000
BS EN/EN62368-1 TPTC004

IEC62368-1

MODEL

HRP-200-3.3 HRP-200-5 HRP-200-7.5 HRP-200-12 HRP-200-15 HRP-200-24 HRP-200-36 HRP-200-48

DC VOLTAGE RATED CURRENT CURRENT RANGE

3.3V 40A 0 ~ 40A

5V 35A 0 ~ 35A

7.5V 26.7A 0 ~ 26.7A

12V 16.7A 0 ~ 16.7A

15V 13.4A 0 ~ 13.4A

24V 8.4A 0 ~ 8.4A

36V 5.7A 0 ~ 5.7A

48V 4.3A 0 ~ 4.3A

OUTPUT

RATED POWER

132W

175W

200.3W

200.4W

201W

RIPPLE & NOISE (max.) Note.2 80mVp-p

90mVp-p

100mVp-p 120mVp-p 150mVp-p

VOLTAGE ADJ. RANGE

2.8 ~ 3.8V 4.3 ~ 5.8V 6.8 ~ 9V

10.2 ~ 13.8V 13.5 ~ 18V

VOLTAGE TOLERANCE Note.3 ±2.0%

±2.0%

±2.0%

±1.0%

±1.0%

LINE REGULATION

±0.5%

±0.5%

±0.5%

±0.3%

±0.3%

LOAD REGULATION

±1.5%

±1.0%

±1.0%

±0.5%

±0.5%

SETUP, RISE TIME

1000ms, 50ms/230VAC 2500ms, 50ms/115VAC at full load

HOLD UP TIME (Typ.)

16ms/230VAC 16ms/115VAC at full load

201.6W 150mVp-p 21.6 ~ 28.8V ±1.0% ±0.2% ±0.5%

205.2W 250mVp-p 28.8 ~ 39.6V ±1.0% ±0.2% ±0.5%

206.4W 250mVp-p 40.8 ~ 55.2V ±1.0% ±0.2% ±0.5%

VOLTAGE RANGE Note.5 85 ~ 264VAC

FREQUENCY RANGE

47 ~ 63Hz

120 ~ 370VDC

POWER FACTOR (Typ.)

PF>0.95/230VAC PF>0.99/115VAC at full load

INPUT EFFICIENCY (Typ.)

80%

84%

86%

88%

88%

88%

89%

89%

AC CURRENT (Typ.) INRUSH CURRENT (Typ.)

2.1A/115VAC 1.1A/230VAC 35A/115VAC 70A/230VAC

LEAKAGE CURRENT

<1.2mA / 240VAC

OVERLOAD PROTECTION
OVER VOLTAGE

105 ~ 135% rated output power

Protection type : Constant current limiting, recovers automatically after fault condition is removed

3.96 ~ 4.62V 6 ~ 7V

9.4 ~ 10.9V 14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V 41.4 ~ 48.6V

Protection type : Shut down o/p voltage, re-power on to recover

57.6 ~ 67.2V

OVER TEMPERATURE WORKING TEMP.

Shut down o/p voltage, recovers automatically after temperature goes down -40 ~ +70 (Refer to “Derating Curve”)

WORKING HUMIDITY

20 ~ 90% RH non-condensing

ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85, 10 ~ 95% RH

TEMP. COEFFICIENT

±0.03%/ (0 ~ 50

VIBRATION

10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes

SAFETY STANDARDS

UL62368-1,TUV BS EN/EN62368-1, AS/NZS62368.1, EAC TP TC 004 approved

SAFETY & WITHSTAND VOLTAGE

EMC (Note 4)

ISOLATION RESISTANCE EMC EMISSION

I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020

EMC IMMUNITY MTBF

Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11,BS EN/EN55035,heavy industry level, EAC TP TC 020 1830.6K hrs min. Telcordia SR-332 (Bellcore) ; 209.5K hrs min. MIL-HDBK-217F (25)

OTHERS NOTE

DIMENSION

1999838mm (LWH)

PACKING

0.77Kg; 18pcs/14.9Kg/0.87CUFT

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1F & 47F parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf ) 5. Derating may be needed under low input voltages. Please check the derating curve for more details. 6. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft).
Product Liability DisclaimerFor detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

File Name:HRP-200-SPEC 2024-01-26

200W Single Output with PFC Function

HRP-200 series

Mechanical Specification

Case No.902E Unit:mm
197

7

9

3.5

3-M3 L=5
3.5 15 26

Terminal Pin No. Assignment

Pin No. Assignment Pin No. Assignment

1

AC/L

4,5 DC OUTPUT -V

2

AC/N

6,7 DC OUTPUT +V

3

FG

Connector Pin No. Assignment (CN100) :

HRS DF11-6DP-2DS or equivalent

Pin No. Assignment Mating Housing Terminal

1

NC

2

NC

3

NC

HRS DF11-6DS HRS DF11-**SC

4

NC

or equivalent or equivalent

5

+S

6

-S

8.2

9.5

9 18.5

1

2

3

4

5

6

7

LED

3.5

CN100

SVR1

4.5

57.5

6.5

13max. 28

80

4-M3 L=5 120
199 190
151

Block Diagram

EMI

I/P

FILTER

FG

ACTIVE INRUSH CURRENT LIMITING

RECTIFIERS &
PFC
O.T.P.
PFC CONTROL

POWER SWITCHING
O.L.P.
PWM CONTROL

RECTIFIERS &
FILTER
DETECTION CIRCUIT
O.V.P.

Derating Curve

Output Derating VS Input Voltage

18 9.5 3.5 28.5 38

PWM fosc :70KHz
+S +V -V -S

85.5

98

LOAD (%) LOAD(%)

112050

100

90

80 80

60

70

60 40
50 20
40

-40

0

10

20

30

40

50

60

70 (HORIZONTAL)

85

100

125

135

155

264

AMBIENT TEMPERATURE ()

INPUT VOLTAGE (V) 60Hz

File Name:HRP-200-SPEC 2024-01-26

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals