MEAN WELL HRP-150N series Power Supplies External Internal Owner’s Manual

August 16, 2024
MEAN WELL

MEAN WELL HRP-150N series Power Supplies External Internal

Product Information

Specifications

  • Model: HRP-150N series
  • Output Power: 150W
  • Input Voltage: 85~264VAC
  • Output Voltage: 12V, 24V, 36V, 48V
  • Efficiency: Up to 89%
  • Protections: Short circuit, Overload, Over voltage, Over temperature
  • Cooling: Free air convection
  • Warranty: 5 years

Product Usage Instructions

Installation

  1. Ensure input voltage is within the specified range of 85~264VAC.
  2. Connect the output terminals to the device requiring power, observing correct polarity.
  3. Ensure proper ventilation around the power supply for efficient cooling.

Operation

  1. Power on the HRP-150N by connecting it to a compatible AC power source.
  2. Monitor the output voltage to ensure it meets the requirements of the connected device.
  3. In case of any abnormality, refer to the user manual for troubleshooting steps.

Maintenance

  1. Regularly check for dust accumulation and clean the unit if necessary to prevent overheating.
  2. Inspect the connections periodically to ensure they are secure and free from corrosion.

FAQ

  • Q: What is the warranty period for the HRP-150N series?
    A: The HRP-150N series comes with a 5-year warranty.

  • Q: What are the typical applications of the HRP-150N power supply?
    A: The HRP-150N is commonly used in industrial automation machinery, control systems, diagnostic facilities, and telecommunication equipment.

Features

  • Universal AC input / Full range
  • Built-in active PFC function, PF>0.95
  • 250% peak power capability
  • High efficiency up to 89%
  • Withstand 300VAC surge input for 5 seconds
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • 1U low profile 38mm
  • Built-in remote sense function
  • 5 years warranty

Applications

  • Industrial automation machinery
  • Industrial control system
  • Mechanical and electrical equipment
  • Diagnostic or biological facilities
  • Test or measurement systems
  • Telecommunication equipment

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

HRP-150N is a 150W single output type AC/DC power supply. This series operates for 85~264VAC input voltage and offers the models with the DC output mostly demanded from the industry. Each model is cooled by free air convection, working for the temperature up to 70°C without cover. Moreover, HRP-150N provides 250% short-duration peak power for motor applications and electromechanical loads requiring much higher power during start-up.

Model Encoding

SPECIFICATION

MODEL| HRP-150N-12| HRP-150N-24| HRP-150N-36| HRP- 150N-48
---|---|---|---|---
OUTPUT| DC VOLTAGE| 12V| 24V| 36V| 48V
RATED CURRENT| 13A| 6.5A| 4.3A| 3.3A
CURRENT RANGE| 0 ~ 13A| 0 ~ 6.5A| 0 ~ 4.3A| 0 ~ 3.3A
RATED POWER| 156W| 156W| 154.8W| 158.4W
RIPPLE & NOISE (max.) **Note.2| 120mVp-p| 150mVp-p| 200mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| 10.2 ~ 13.8V| 21.6 ~ 28.8V| 28.8 ~ 39.6V| 40.8 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±1.5%| ±1.5%| ±1.5%| ±1.5%
LINE REGULATION| ±0.3%| ±0.2%| ±0.2%| ±0.2%
LOAD REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME| 3000ms, 50ms/230VAC            3000ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)| 16ms/230VAC            16ms/115VAC at full load
INPUT| VOLTAGE RANGE Note.4| 85 ~ 264VAC           120 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| PF>0.95/230VAC            PF>0.98/115VAC at full load
EFFICIENCY (Typ.)| 88%| 88%| 89%| 89%
AC CURRENT (Typ.)| 1.7A/115VAC          0.9A/230VAC
INRUSH CURRENT (Typ.)| 35A/115VAC           70A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
PROTECTION| OVERLOAD| Normally works within 105 ~ 200% rated output power for more than 5 seconds and then shut down o/p voltage, re-power on to recover
Constant current limiting for output power >280% rated for more than 5 seconds and then shut down o/p voltage, re-power  on to recover
OVERVOLTAGE| 14.4 ~ 16.8V| 30 ~ 34.8V| 41.4 ~ 48.6V| 57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after temperature goes down
ENVIRONMENT| WORKING TEMP.| -40 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -50 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.04%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
OPERATING ALTITUDE Note.6| 5000 meters
SAFETY & EMC**

(Note 5)

| SAFETY STANDARDS| UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004, AS/NZS 62368.1 approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032| Class B
Radiated| BS EN/EN55032| Class B
Harmonic current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —–
EMC IMMUNITY| BS EN/EN55035 , BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact
RF field| BS EN/EN61000-4-3| Level 3, 10V/m
EFT/ Burst| BS EN/EN61000-4-4| Level 3, 2KV
Surge| BS EN/EN61000-4-5| Level 4, 4KV/Line-FG; 2KV/Line-Line
Conducted| BS EN/EN61000-4-6| Level 3, 10V
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m
Voltage Dips and Interruptions| BS EN/EN61000-4-11| 95% dip 0.5 periods, 30% dip 25 periods, 95% interruptions 250 periods


OTHERS

| MTBF| 1740.3K hrs min.       Telcordia SR-332 (Bellcore) ; 221.7K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION| 1599738mm (LWH)
PACKING| 0.54Kg; 24pcs/12.96Kg/0.9CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.

3. Tolerance: includes set up tolerance, line regulation and load regulation.

4. Derating may be needed under low input voltages. Please check the derating curve for more details.

5. The power supply is considered a component that will be installed into the final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re- confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).

※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Derating Curve

Output Derating VS Input Voltage

Function Manual

  1. Remote Sense
    The remote sensing compensates voltage drop on the load wiring up to 0.5V.

  2. Peak Power

Mechanical Specification

Installation Manual
Please refer to: http://www.meanwell.com/manual.html

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals