MEAN WELL ELG-75 Series 48-75W Constant Voltage Plus Current LED Driver Owner’s Manual

August 15, 2024
MEAN WELL

MEAN WELL ELG-75 Series 48-75W Constant Voltage Plus Current LED Driver

Specifications

  • Model:
    • ELG-75-12
    • ELG-75-24
    • ELG-75-36
    • ELG-75-42
    • ELG-75-48
  • DC Voltage:
    • 12V
    • 24V
    • 36V
    • 42V
    • 48V
  • Rated Current:
    • 5A (12V)
    • 3.15A (24V)
    • 2.1A (36V)
    • 1.8A (42V)
    • 1.6A (48V)

Product Usage Instructions

Installation

  1. Ensure the power source is turned off before installation.
  2. Connect the LED driver to the appropriate power source based on the DC voltage requirement.
  3. Securely mount the LED driver in a well-ventilated area to prevent overheating.

Adjusting Voltage and Current

The voltage and current can be adjusted for A/AB-Type drivers using the built- in potentiometer.

Regulation and Setup

The LED driver has specific setup and regulation times that ensure optimal performance. Refer to the manual for detailed information.

FAQ

  • Q: How do I adjust the voltage and current on the LED driver?
    A: You can adjust the voltage and current for A/AB-Type drivers using the built-in potentiometer. Refer to the manual for specific ranges.

  • Q: What is the maximum number of PSUs that can be used on a 16A circuit breaker?
    A: The maximum number of PSUs is 5 units for a circuit breaker of type B and 8 units for a circuit breaker of type C at 230VAC.

Features

  • Constant Voltage + Constant Current mode output
  • Metal housing design with functional Ground
  • Built-in active PFC function
  • Class 2 power unit
  • No load / Standby power consumption <0.5W
  • 1P67 / 1P65 rating for indoor or outdoor installations
  • Function options: output adjustable via potentiometer; 3 in 1 dimming (dim-to-off); Smart timer dimming; DALI
  • Typical lifetime>50000 hours
  • 5 years warranty

Applications

  • LED street lighting
  • LED architectural lighting
  • LED bay lighting
  • LED floodlighting
  • Type “HL” for use in Class I, Division 2 hazardous (Classified) location.

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

ELG-75 series is a 75W AC/DC LED driver featuring the dual mode constant voltage and constant current output. ELG-75 operates from 100~305VAC and offers models with different rated voltage ranging between 12V and 48V. Thanks to the high efficiency up to 90%, with the fanless design, the entire series is able to operate for -40°C ~ +85°C case temperature under free air convection. The design of metal housing and IP67/P65 ingress protection level allows this series to fit both indoor and outdoor applications. ELG-75 is equipped with various function options, such as dimming methodologies, so as to provide the optimal design flexibility for LED lighting system

Model Encoding

SPECIFICATION

MODEL|  | ELG-75-12| ELG-75-24| ELG-75-36| ELG-75-42| ELG-75-48
---|---|---|---|---|---|---










OUTPUT

| DC VOLTAGE| 12V| 24V| 36V| 42V| 48V
CONSTANT CURRENT REGION Note.2| 6 ~ 12V| 12 ~ 24V| 18 ~ 36V| 21 ~ 42V| 24 ~ 48V
RATED CURRENT| 5A| 3.15A| 2.1A| 1.8A| 1.6A


RATED POWER **Note.5**

| 200VAC ~ 305VAC
60W| 75.6W| 75.6W| 75.6W| 76.8W
100VAC ~ 180VAC
48W| 60W| 60W| 60W| 60W
RIPPLE & NOISE (max.) **Note.3| 150mVp-p| 200mVp-p| 250mVp-p| 250mVp-p| 250mVp-p
VOLTAGE ADJ. RANGE| Adjustable for A/AB-Type only (via built-in potentiometer)
10.8 ~ 13.2V| 21.6 ~ 26.4V| 32.4 ~ 39.6V| 37.8 ~ 46.2V| 43.2 ~ 52.8V
CURRENT ADJ. RANGE| Adjustable for A/AB-Type only (via built-in potentiometer)
2.5 ~ 5A| 1.57 ~ 3.15A| 1.05 ~ 2.1A| 0.9 ~ 1.8A| 0.8 ~ 1.6A
VOLTAGE TOLERANCE Note.4| ±3.0%| ±3.0%| ±2.5%| ±2.5%| ±2.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±2.0%| ±1.0%| ±1.0%| ±0.5%| ±0.5%
SETUP, RISE TIME Note.6| 500ms, 100ms/115VAC, 230VAC
HOLD UP TIME (Typ.)**| 10ms/ 230VAC 10ms/ 115VAC(at full load)








INPUT

| VOLTAGE RANGE **Note.5**| 100 ~ 305VAC             142 ~ 431VDC

(Please refer to “STATIC CHARACTERISTIC” section)

FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR| PF≧0.97/115VAC, PF≧0.95/230VAC, PF≧0.92/277VAC@full load

(Please refer to “POWER FACTOR (PF) CHARACTERISTIC” section)

TOTAL HARMONIC DISTORTION| THD<  20%(@load≧50%/115VC,230VAC; @load≧75%/277VAC)

(Please refer to “TOTAL HARMONIC DISTORTION(THD)” section)

EFFICIENCY (Typ.)| 86%| 88%| 89%| 90%| 90%
AC CURRENT| 0.7A / 115VAC         0.45A / 230VAC        0.38A/277VAC
INRUSH CURRENT(Typ.)| COLD START 50A(twidth=350 μ s measured at 50% Ipeak) at 230VAC ; Per NEMA 410
MAX. No. of PSUs on 16A CIRCUIT BREAKER| 5 units (circuit breaker of type B) / 8 units (circuit breaker of type C) at 230VAC
LEAKAGE CURRENT| <0.75mA / 277VAC
NO LOAD / STANDBY POWER CONSUMPTION| No load power consumption <0.5W for Blank / A / Dx / D2-Type Standby power consumption <0.5W for B / AB / DA-Type




PROTECTION

| OVER CURRENT| 95 ~ 108%
Constant current limiting, recovers automatically after fault condition is removed
SHORT CIRCUIT| Hiccup mode, recovers automatically after fault condition is removed
OVER VOLTAGE| 14 ~ 18V| 28 ~ 34V| 41 ~ 48V| 47 ~ 54V| 54 ~ 62V
Shut down output voltage, re-power on to recover
OVER TEMPERATURE| Shut down output voltage, re-power on to recover




ENVIRONMENT

| WORKING TEMP.| Tcase=-40 ~ +85℃ (Please refer to “ OUTPUT LOAD vs TEMPERATURE” section)
MAX. CASE TEMP.| Tcase=+85℃
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +80℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 60℃)
VIBRATION| 10 ~ 500Hz, 5G 12min./1cycle, period for 72min. each along X, Y, Z axes




SAFETY & EMC

| ****

SAFETY STANDARDS

| UL8750(type”HL”), CSA C22.2 No. 250.13-12; IEC/BS EN/EN/AS/NZS 61347-1, IEC/BS EN/EN/AS/NZS 61347-2-13 independent, BS EN/EN62384;EAC TP TC 004;BIS IS15885(for 12A/12DA/12B/24A/24B/24DA/36A/36B/42A/42B/48A/48B only); IP65 or IP67; GB19510.1, GB19510.14; KC61347-1,KC61347-2-13 approved
DALI STANDARDS| Compliance to IEC62386-101,102,(207 by request) for DA Type only
WITHSTAND VOLTAGE| I/P-O/P:3.75KVAC  I/P-FG:2.0KVAC  O/P-FG:1.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55015,BS EN/EN61000-3-2 Class C (@load≧50%) ; BS EN/EN61000-3-3; GB/T 17743, GB17625.1; EAC TP TC 020; KC KN15,KN61547
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11; BS EN/EN61547, light industry level (surge immunity Line-Earth 6KV,

Line-Line 4KV);EAC TP TC 020; KC KN15,KN61547


OTHERS

| MTBF| 3451.7K hrs min. Telcordia SR-332 (Bellcore) 331.3Khrs min.        MIL-HDBK-217F (25℃)
DIMENSION| 1806335.5mm (LWH)
PACKING| 0.8Kg;16pcs/13.4Kg/0.67CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated current and 25℃ of ambient temperature.

2. Please refer to “DRIVING METHODS OF LED MODULE”.

3. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

4. Tolerance : includes set up tolerance, line regulation and load regulation.

5. De-rating may be needed under low input voltages. Please refer to “STATIC CHARACTERISTIC” sections for details.

6. Length of set up time is measured at first cold start. Turning ON/OFF the driver may lead to increase of the set up time.

7. The driver is considered as a component that will be operated in combination with final equipment. Since EMC performance will be affected by the complete installation, the final equipment manufacturers must re-qualify EMC Directive on the complete installation again.

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf)

8. This series meets the typical life expectancy of >50,000 hours of operation when Tcase, particularly tc point (or TMP, per DLC), is about 70℃ or less.

9. Please refer to the warranty statement on MEAN WELL’s website at http://www.meanwell.com

10. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

11. For any application note and IP water proof function installation caution, please refer our user manual before using.

https://www.meanwell.com/Upload/PDF/LED_EN.pdf

※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

DRIVING METHODS OF LED MODULE

This series is able to work in either Constant Current mode (a direct drive way) or Constant Voltage mode (usually through additional DC/DC driver) to drive the LEDs.

DIMMING OPERATION

3 in 1 dimming function (for B/AB-Type)
Output constant current level can be adjusted by applying one of the three methodologies between DIM+ and DIM-:
0 ~ 10VDC, or 10V PWM signal or resistance. ‧Direct connecting to LEDs is suggested. It is not suitable to be used with additional drivers. ‧Dimming source current from power supply: 100μA (typ.)

Applying additive 0 ~ 10VDC

Applying additive 10V PWM signal (frequency range 100Hz ~ 3KHz):

Applying additive resistance

Note:

  1. Min. dimming level is about 8% and the output current is not defined when 0%< Iout<8%.
  2. The output current could drop down to 0% when dimming input is about 0kΩ or 0Vdc, or 10V PWM signal with 0% duty cycle.

DALI Interface (primary side; for DA-Type)

  • Apply DALI signal between DA+ and DA-.
  • DALI protocol comprises 16 groups and 64 addresses.
  • First step is fixed at 8% of output.

Smart timer dimming function (for Dxx-Type by User definition)

MEAN WELL Smart timer dimming primarily provides the adaptive proportion dimming profile for the output constant current level to perform up to 14 consecutive hours. 3 dimming profiles hereunder are defined accounting for the most frequently seen applications. If other options may be needed, please contact MEAN WELL for details.
Ex : ◎ D01-Type: the profile recommended for residential lighting

TIME matches Operating Time in the diagram whereas LEVEL matches Dimming Level.
Example : If a residential lighting application adopts D01-Type, when turning on the power supply at 6:00pm, for instance:

  1. The power supply will switch to the constant current level at 100% starting from 6:00pm.
  2. The power supply will switch to the constant current level at 70% in turn, starting from 0:00am, which is 06:00 after the power supply turns on.
  3. The power supply will switch to the constant current level at 50% in turn, starting from 1:00am, which is 07:00 after the power supply turns on.
  4. The power supply will switch to the constant current level at 70% in turn, starting from 5:00am, which is 11:00 after the power supply turns on.

The constant current level remains till 8:00am, which is 14:00 after the power supply turns on.

Ex: ◎ D02-Type: the profile recommended for street lighting

TIME matches Operating Time in the diagram whereas LEVEL matches Dimming Level.
Example : If a street lighting application adopts D02-Type, when turning on the power supply at 5:00pm, for instance:

  1. The power supply will switch to the constant current level at 50% starting from 5:00pm.
  2. The power supply will switch to the constant current level at 80% in turn, starting from 6:00pm, which is 01:00 after the power supply turns on.
  3. The power supply will switch to the constant current level at 100% in turn, starting from 8:00pm, which is 03:00 after the power supply turns on.
  4. The power supply will switch to the constant current level at 60% in turn, starting from 1:00am, which is 08:00 after the power supply turns on.
  5. The power supply will switch to the constant current level at 80% in turn, starting from 4:00am, which is 11:00 after the power supply turns on. The constant current level remains till 6:30am, which is 14:00 after the power supply turns on.

Ex: ◎ D03-Type: the profile recommended for tunnel lighting

TIME matches Operating Time in the diagram whereas LEVEL matches Dimming Level.
Example : If a tunnel lighting application adopts D03-Type, when turning on the power supply at 4:30pm, for instance:

  1. The power supply will switch to the constant current level at 70% starting from 4:30pm.
  2. The power supply will switch to the constant current level at 100% in turn, starting from 6:00pm, which is 01:30 after the power supply turns on.
  3. The power supply will switch to the constant current level at 70% in turn, starting from 5:00am, which is 11:00 after the power supply turns on.

The constant current level remains till 6:30am, which is 14:00 after the power supply turns on.

OUTPUT LOAD vs TEMPERATURE(Note.9)

STATIC CHARACTERISTIC

POWER FACTOR (PF) CHARACTERISTIC

TOTAL HARMONIC DISTORTION (THD)

EFFICIENCY vs LOAD

ELG-75 series possess superior working efficiency that up to 90% can be reached in field applications.
48V Model, Tcase at 75℃

LIFE TIME

Mechanical Specification

  • Note1: Please connect the case to PE for the complete EMC deliverance and safety use.
  • Note2: Please contact MEAN WELL for input wiring option with PE

Recommend Mounting Direction

INSTALLATION MANUAL

Please refer to:http://www.meanwell.com/manual.html

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals