MEAN WELL RT-65 Series 65W Triple Output Switching Power Supply Owner’s Manual

August 14, 2024
MEAN WELL

MEAN WELL RT-65 Series 65W Triple Output Switching Power Supply

MEAN-WELL-RT-65-Series-65W-Triple-Output-Switching-Power-Supply-
PRODUCT

Product Usage Instructions

Installation:

  • Ensure the power supply is compatible with your device’s requirements.
  • Connect the input terminals to a suitable power source.
  • Connect the output terminals to your device following the provided specifications.

Operation:

  • Turn on the power supply using the power switch or by connecting it to the power source.
  • Monitor the LED indicator to ensure power is on.

Safety Precautions:

  • Do not operate the power supply in wet conditions to avoid electric shock.
  • Avoid overloading the power supply beyond its rated capacity.
  • If any abnormalities occur during operation, disconnect the power supply immediately.

FAQ

Frequently Asked Questions

  • Q: What should I do if the LED indicator does not light up?
    • A: Check the power source and connections to ensure proper installation. If the issue persists, contact customer support for assistance.
  • Q: How can I determine the appropriate output voltage for my device?
    • A: Refer to the specifications provided in the user manual and select the output voltage that matches your device’s requirements.
  • Q: Can I use this power supply for outdoor applications?
    • A: It is recommended to use the power supply in indoor environments to prevent damage from external elements.

Features

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • LED indicator for power on
  • 100% full load burn-in test
  • All using 105°C long life electrolytic capacitors
  • Withstand 300 VAC surge input for 5 second
  • High operating temperature up to 70°C
  • Withstand 5G vibration test
  • High efficiency, long life and high reliability
  • 3 years warranty

MEAN-WELL-RT-65-Series-65W-Triple-Output-Switching-Power-Supply-
FIG-2

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

SPECIFICATION

MODEL RT-65A RT-65B RT-65C RT-65D








OUTPUT

| OUTPUT NUMBER| CH1| CH2| CH3| CH1| CH2| CH3| CH1| CH2| CH3| CH1| CH2| CH3
DC VOLTAGE| 5V| 12V| -5V| 5V| 12V| -12V| 5V| 15V| -15V| 5V| 24V| 12V
RATED CURRENT| 6A| 2.8A| 0.5A| 5A| 2.8A| 0.5A| 5A| 2.2A| 0.5A| 4A| 1.5A| 1A
CURRENT RANGE Note.6| 0 ~ 8A| 0 ~ 3.5A| 0 ~ 1A| 0 ~ 8A| 0 ~ 3.5A| 0 ~ 1A| 0 ~ 8A| 0 ~ 3A| 0 ~ 1A| 0 ~ 8A| 0 ~ 2A| 0 ~ 1A
RATED POWER Note.6| 66.1W| 64.6W| 65.5W| 68W
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 120mVp-p| 80mVp-p| 80mVp-p| 120mVp-p| 80mVp-p| 80mVp-p| 120mVp-p| 80mVp-p| 80mVp-p| 150mVp-p| 120mVp-p
VOLTAGE ADJ. RANGE| CH1: 4.75 ~ 5.5V| CH1: 4.75 ~ 5.5V| CH1: 4.75 ~ 5.5V| CH1: 4.75 ~ 5.5V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±6.0%| ±5.0%| ±2.0%| ±6.0%| ±5.0%| ±2.0%| +8,-4%| ±5.0%| ±2.0%| +4,-10%| ±6.0%
LINE REGULATION Note.4| ±0.5%| ±1.5%| ±0.5%| ±0.5%| ±1.5%| ±0.5%| ±0.5%| ±1.5%| ±0.5%| ±0.5%| ±1.5%| ±2.0%
LOAD REGULATION Note.5| ±1.0%| ±3.0%| ±1.0%| ±1.0%| ±3.0%| ±1.0%| ±1.0%| ±3.0%| ±1.0%| ±1.0%| ±3.0%| ±4.0%
SETUP, RISE TIME| 500ms, 20ms/230VAC            1200ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)**| 60ms/230VAC            14ms/115VAC at full load




INPUT

| VOLTAGE RANGE| 88 ~ 264VAC           125 ~ 373VDC (Withstand 300VAC surge for 5sec. Without damage)
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY(Typ.)| 76%| 76%| 77%| 78%
AC CURRENT (Typ.)| 2A/115VAC           1.2A/230VAC
INRUSH CURRENT (Typ.)| COLD START 50A/230VAC
LEAKAGE CURRENT| <2mA / 240VAC



PROTECTION

| ****

OVERLOAD

| 110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed


OVER VOLTAGE

| CH1: 5.75 ~ 6.75V
Protection type : Hiccup mode, recovers automatically after fault condition is removed




ENVIRONMENT

| WORKING TEMP.| -25 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)on +5V output
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, period for 60min. each along X, Y, Z axes


SAFETY & EMC

(Note 7)

| SAFETY STANDARDS| UL62368-1, TUV BS EN/EN62368-1, BIS IS 13252(Part 1):2010/IEC 60950-1:2005, EAC TP TC 004 approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035,BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry level, EAC TP TC 020


OTHERS

| MTBF| 2720.8K hrs min.       Telcordia SR-332 (Bellcore) ;507.6K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION| 1299838mm (LWH)
PACKING| 0.44Kg; 30pcs/13.2Kg/0.72CUFT


NOTE

|

  1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.

  3. Tolerance: includes set up tolerance, line regulation and load regulation, when multi-channel output, it is recommended that CH1 load > 10%.

  4. Line regulation is measured from low line to high line at rated load.

  5. Load regulation is measured from 20% to 100% rated load, and other output at 60% rated load.

  6. Each output can work within current range. But total output power can’t exceed rated output power.

  7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
    (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

  8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).

※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Mechanical Specification

MEAN-WELL-RT-65-Series-65W-Triple-Output-Switching-Power-Supply-
FIG-3

Case No. 903 Unit:mm

Terminal Pin No. Assignment

MEAN-WELL-RT-65-Series-65W-Triple-Output-Switching-Power-Supply-
FIG-7

Block Diagram

MEAN-WELL-RT-65-Series-65W-Triple-Output-Switching-Power-Supply-
FIG-4

Derating Curve

MEAN-WELL-RT-65-Series-65W-Triple-Output-Switching-Power-Supply-
FIG-5

Output Derating VS Input Voltage

MEAN-WELL-RT-65-Series-65W-Triple-Output-Switching-Power-Supply-
FIG-6

User’s Manual

MEAN-WELL-RT-65-Series-65W-Triple-Output-Switching-Power-Supply-
FIG-2

Documents / Resources

| MEAN WELL RT-65 Series 65W Triple Output Switching Power Supply [pdf] Owner's Manual
RT-65A, RT-65B, RT-65C, RT-65D, RT-65 Series 65W Triple Output Switching Power Supply, RT-65 Series, 65W Triple Output Switching Power Supply, Triple Output Switching Power Supply, Output Switching Power Supply, Switching Power Supply, Power Supply, Supply
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals