RAB Field Adjustable TOMO Linear Lighting
Specifications
- Models: TOMO-2FT, TOMO-4FT, TOMO-8FT
- Installation Types: Surface Mounting, Canopy Kit-to-Fixture
- Energy Efficiency: LED lighting
Product Usage Instructions
Surface Mounting Installation
- Secure the Surface Mounting Plate to the Junction Box.
- Remove Silicone Plugs from each end of the Housing Cover.
- Pull out the End Caps and separate the Housing Cover from the Lens and Tray Assembly.
- Pull supply wires through the Surface Mounting Plate and make electrical splices to fixture leads.
- Align and secure the Surface Mount Adapter Plate to the Housing Cover using provided screws.
- Follow appropriate wiring instructions per code.
- Reassemble by pushing Lens and Tray Assembly into the Housing Cover and secure with End Caps and Silicone Plugs.
Canopy Kit-to-Fixture Installation
- Remove End Caps and slide the Lens Tray Assembly from the Housing Cover to release Tray Assembly.
- For Canopy Mounting, remove Knockouts on the Housing Cover.
- Insert Cable Couplers through the Cable Coupler Knockouts from inside the Housing Cover.
- Secure the Cable Couplers with Cable Coupler Nuts onto the Housing Cover.
Frequently Asked Questions
- Q: What should I do if the fixture leads are not long enoughfor my installation?
- A: If the fixture leads are not long enough, you may need to extend them using UL rated wire connectors as required by NEC and local code.
- Q: Can I use this product in damp locations?
- A: This product is suitable for damp locations, but it is recommended to follow all local electrical codes and regulations for installation in such environments.
- Q: How do I clean the lens of the fixture?
- A: To clean the lens, gently wipe it with a soft cloth dampened with water or a mild cleaning solution. Avoid using harsh chemicals or abrasive materials that may damage the lens.
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com
Models
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE
REFERENCE. RAB fixtures must be wired in accordance with the National
Electrical Code and all applicable local codes. Proper grounding is required
for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE
INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF
THE PRODUCT AND THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining fixture.
No user serviceable parts inside. The fixture is suitable for indoor
applications. Suitable for damp locations. Ceiling, Canopy and Pendant mount
only.
SURFACE MOUNTING
- Secure Surface Mounting Plate to Junction Box (by others). (Additional attachment to the ceiling may be needed for longer fixtures). 8ft TOMO includes a 2nd Surface Mounting Plate and Surface Mount Adapter Plate (see Fig. 2).
- Remove Silicone Plugs located on each end of the Housing Cover as shown in Fig. 2 (do not discard Silicone Plugs).
- Pull the End Caps out of each end of the fixture as shown in Fig. 1. Separate the Housing Cover from the Lens and Tray Assembly by sliding the Housing Cover either right of left to unlock from Key Slots as shown in Fig. 3. Pre-installed Tether Cables (2) will prevent Lens and Tray Assembly from separating from Housing Cover (Fig. 1).
- Pull supply wires from Junction Box (by others) through center of Surface Mounting Plate. Use appropriate UL rated wire connectors as required by NEC and local code to make electrical splices to fixture leads.
- Align Surface Mount Adapter Plate to the Housing Cover. Using (4) Screws (provided) secure Surface Mount Adaptor Plate and Housing Cover to the Surface Mounting Plate.
- Follow appropriate wiring instructions per code (Fig. 13).
- Push Lens and Tray Assembly into the Housing Cover. Align Keys into Key Slots and slide to the right or left to lock the Housing Cover into the Lens and Tray Assembly. Snap on End Caps and insert Silicone Plugs into Housing Cover.
WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sharp objects.
INSTALLATION
CANOPY KIT-TO-FIXTURE INSTALLATION
- Remove End Caps. Slide Lens Tray Assembly from Housing Cover to release Tray Assembly by sliding the fixture to the right to unlock from Key Slots as shown in Fig. 3. Pre-installed Tether Cables (2) will prevent Lens and Tray Assembly from separating from Housing Cover as shown in Fig. 1.
- For Canopy Mounting, remove (2) Knockouts on theHousing Cover as shown in Fig. 4.
- Insert Cable Couplers from the inside of the Housing Cover through the two respective Cable Coupler Knockouts as shown in Fig. 5.
- Secure the Cable Couplers with Cable Coupler Nuts onto the Housing Cover as shown in Fig. 5.
- Insert the Cable into the Cable Couplers. Adjust the length of the Cable and tighten the Locknuts and trim any excess cable inside the fixture.
- Pull supply wires through Power Cord Knockout and make connection inside the fixture. Pass the Power Cord and Cable through the Canopy Rings. Adjust the length of the Power Cord and tighten it on the Canopy with Strain Reliefs (Fig. 6).
- Mount all Canopies to the Fixture with appropriate Cable length.
- Follow appropriate wiring instructions per NEC and local code (Fig. 13).
CANOPY-TO-SURFACE MOUNTING
- Slide the Power Cord through the hole on the Canopy and tighten with Strain Relief.
- Connect wires per NEC and local code as shown in wiring diagram (Fig. 13). Push all wires back into the Junction Box. Be careful not to pinch wires. Mount the Cross Bar on Junction Box.
- Mount the Canopy to the Junction Box. Push the Cable Coupler on the 1/4-20 Stud and tighten the Coupler.
- Canopy and Cable without Power Cord can be mounted with a 1/4 -20 Stud and hardware appropriate to mounting surface.
- Push Lens and Tray Assembly into the Housing Cover. Align Keys into Key Slots and slide to the left to lock the Housing Cover into the Lens and Tray Assembly. Snap on End Caps.
WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sharp objects.
CONTINUOUS RUN MOUNTING (PENDANT)
Multiple fixtures can be mounted together using TOMO CONNECT (sold separately).
Note: Continuous Run Mounting is not available with LIGHTCLOUD® /LC, /LC/E, /LCB suffix.
- For the continuous run, remove fixture End Caps (Fig. 7). Pop out Silicone Plugs, push Fixtures together using TOMO CONNECT (ordered separately) between fixtures for quick connect installation (Fig. 8). TOMO CONNECT is provided with (2) Fixing Screws. Install Fixing Screws in Silicone Plug points. Only (1) one Fixture needs to be electrically hard wired from above (Fig. 9).
- CAUTION: The maximum number of fixtures allowed to be linked together is indicated in table below (120V through 277V only).
WARNING: To prevent wiring damage or abrasion, do not expose wiring to sharp objects.
Catalog # | Maximum Number of Linked Fixtures |
---|---|
TOMO-2 | Up to 28 fixtures |
TOMO-4 | Up to 14 fixtures |
TOMO-8 | Up to 7 fixtures |
FIELD ADJUSTMENT
Follow the instructions below to change the fixture Color Temperature (CCT) and Power (W) from the factory settings.
- Factory Settings: TOMO-2 18W / 4000K
- TOMO-4 36W / 4000K
- TOMO-8 72W / 4000K
- Remove End Caps. Slide Lens Tray Assembly from Housing Cover to release Tray Assembly from Housing Cover by sliding the fixture to the right to unlock from Key Slots as shown in Fig. 3. Pre-installed Tether Cables (2) will prevent Lens and Tray Assembly from separating from Housing Cover as shown in Fig. 1.
- Locate the selector switches inside the Lens & Tray Assembly as shown (Fig. 10, 11, 12) for TOMO-2, TOMO-4 TOMO-8. Note: TOMO-8 is equipped with two (2) Color Temperature (CCT) switches and two (2) Power (W) switches.
- Select Color Temperature (CCT) and/or Power (W) by sliding the respective switch to the desired value.
- After the switch is positioned to the desired setting, push Lens and Tray Assembly into the Housing Cover. Align Keys into Key Slots and slide to the left to lock the Housing Cover intothe Lens and Tray Assembly. Snap on End Caps.
WARNING: To prevent wiring damage or abrasion, donot expose wiring to edges of sharp objects.
LIGHTCLOUD® BLUE
Lightcloud Blue is a Bluetooth mesh wireless lighting control system that allows you to control various compatible devices. With RAB’s patented Rapid Provisioning technology, devices can be quickly and easily commissioned for residential and large commercial applications using the Lightcloud Blue mobile app. Each device in a system can communicate with any other device, eliminating the need for a Gateway or Hub and maximizing the control system’s reach. Lightcloud Blue devices should be placed within the specified range to communicate within the Bluetooh Mesh network. Up to 60 feet between standard building materials. Up to 200 feet clear line of sight. Reset to Factory Settings: To enable pairing or reset the device, locate the device identification button at the top of the Controller under the Lightcloud logo. Press and hold this button for 10 seconds or until the indicator light begins flashing red. and the fixture will also on/off 5 times.
LED Indicators:
- Blinking Red = Looking for a network
- Solid Green = Connected to network
WIRING
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. For 0-10V dimming, follow the wiring directions as shown in Fig. 14.
- Connect the black fixture lead to the LINE supply lead.
- Connect the white fixture lead to the COMMON supply lead.
- Connect the GROUND wire from the fixture to the supply ground.
- Connect the purple fixture lead to the (V+) DIM lead.
- Connect the pink fixture lead to the (V-) DIM lead.
- Cap the yellow fixture lead, if present. Do NOT connect.
WIRING
WARNING: Lightcloud Blue-enabled fixtures require constant power and shouldn’t be placed down the circuit from any switching devices. Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. For 0-10V Dimming, follow the wiring directions shown in (Fig. 15).
- Connect the Black fixture lead to the LINE supply lead.
- Connect the White fixture lead to the COMMON supply lead.
- Connect the GROUND wire from the fixture to the supply ground.
- Connect the Purple wire from the fixture to the supply ground.
- Connect the Pink (Grey) wire from the fixture to the supply ground.
NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink(grey)) to line voltage or supply ground. To test, double-click the Lightcloud Blue button to turn on and off the fixture shown in (Fig. 13) .
CONTROLLING LIGHTCLOUD® BLUE DEVICE
- Confirm your device is powered on.
- Download the Lightcloud Blue app from the Apple App Store or Google Play store.
- Launch the App and create an account or sign into an existing account.
- Tap the “add device” icon in the app to start connecting devices.
- Follow the remaining steps in the app. Create areas, groups, and scenes to organize and control your devices
PIR MODELS (INTERNAL)
See regular PIR (non-Smart) factory settings below (optional remote sold separately for custom settings, CAT# TOMO-REMOTE).
Factory Settings:
- Hold Time: 1 Minute
- Stand-by period: 1 Minute
- Stand-by dimming level: 10%
- Constant Lux: 50Lux
- Detection range: Disabled
MICRO SENSOR SETUP & INSTALLATION
- The PIR Micro Sensor (28751) is only compatible with select sensor-ready fixtures. Visit www.rablighting.com to see the full compatibility list.
- Mount the PIR Micro Sensor (28751) with the screw/tape included. Example shown using RAB’s TOMO fixture (Fig. 16).
- Connect the Micro Sensor (28751) (Fig. 16, Fig. 17) Lightcloud Blue Controller: Use the adapter to connect the sensor to the
controller. Plug both RJ09 from Sensor and Controller to adapter
DETECTION PATTERN
CLEANING & MAINTENANCE
CAUTION : Be sure the fixture temperature is cool enough to touch.
Do not clean or maintain while the fixture is energized.
- Clean acrylic lens with a non-abrasive cleaning solution.
- Do not open the fixture to clean the LEDs. Do not touch the LEDs.
TROUBLESHOOTING
- Check that the line voltage at the fixture is correct. Refer to wiring directions.
- Is the fixture grounded properly?
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
BATTERY BACKUP MODELS
WIRING
CAUTION: FOR BATTERY BACKUP FIXTURE (TOMO-4/TOMO-8) Voltage could be present in BATTERY. To prevent high voltage from being present on output leads, Inverter Connector must be open. Do not join BATTERY connector until installation is complete and AC power is supplied to the emergency driver (Fig. 14).
NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required. The emergency driver must be fed from the same branch circuit as the LED driver.
CAUTION: Do not use any supply voltage other than 120-277V 50/60 HZ.
- Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
- If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
- If using a SWITCHED circuit, connect the SWITCHED HOT AC fixture lead to the external control.
- For 0-10V dimming, connect DIM (+) purple lead and DIM (-) pink lead to 0-10V dimmer connections.
- Connect the GROUND lead from the fixture to the supply ground. Do not connect GROUND to the output leads.
- All unused leads must be capped and insulated.
- After installation is complete, supply AC power to the fixture and connect the BATTERY (Fig. 18).
- When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.
- Once the BATTERY has charged for at least one hour, a short-duration test may be performed by pressing the test button (Fig. 15).
- After the battery has been charged for 24 hours, a long-duration test can be performed by shutting the power to the fixture.
OPERATION
- When AC power is applied, the charging indicator light is illuminated indicating that the BATTERY is being charged.
- When power fails, the standby power automatically switches to backup mode at reduced power resulting in lower illumination. The emergency driver supplies power in standby mode for a minimum of 90 minutes.
- When AC power is restored, the emergency driver automatically returns to charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:
- Visually inspect the charging indicator light monthly. It should be illuminated.
- Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
- Conduct a 90-minute discharge test once a year. The fixture would operate at reduced illumination for a minimum of 90 minutes.
TROUBLESHOOTING
- Is the fixture grounded properly?
- If the charging indicator light does not illuminate after pressing the Test Button (Fig. 19), check if battery is connected properly.
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>