MEAN WELL LRS-600-5 Single Output Switching Power Supply Owner’s Manual

July 20, 2024
MEAN WELL

MEAN WELL LRS-600-5 Single Output Switching Power Supply Owner’s Manual
MEAN WELL LRS-600-5 Single Output Switching Power
Supply

Feature

  • MEANWELL Patent Number:ZL202220241473.0
  • AC input range selectable by switch
  • Withstand 300VAC surge input for 5 second
  • Protections: Short circuit/Overload/Over voltage / Over temperature
  • Forced air cooling
  • Built-in cooling Fan ON-OFF control
  • 1U low profile
  • Withstand 5G vibration test
  • High operating temperature up to 65°C
  • Operating altitude up to 5000 meters (Note.10)
    • 3 years warranty
  • MTBF>1KK hrs

Applications

  • Industrial automation machinery
  • Industrial control system
  • Mechanical and electrical equipment
  • Electronic instruments, equipment’s or apparatus

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

LRS-600 series is a 600W single-output enclosed type power supply with 41mm of low profile design. Adopting the input of 115VAC or 230VAC (select by switch), the entire series provides an output voltage line of 5V, 12V, 15V, 24V, 27V, 36V and 48V.In addition to the high efficiency up to 92%, with the built-in long life fan LRS-600 can work under-20~+65°C with full load. LRS-600 has the complete protection functions and 5G anti-vibration capability: It is complied with complete international safety regulations. LRS-600 series serves as a high price-to-performance power supply solution for various industrial applications.

Model Encoding

Installation

SPECIFICATION

MODEL| LRS-600-5| LRS-600-12| LRS-600-15| LRS-600-24| LRS-600-27| LRS-600-36| LRS-600-48
---|---|---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 5V| 12V| 15V| 24V| 27V| 36V| 48V
RATED CURRENT| 100A| 50A| 40A| 25A| 22.2A| 16.6A| 12.5A
CURRENT RANGE| 0 ~ 100A| 0 ~ 50A| 0 ~ 40A| 0 ~ 25A| 0 ~ 22.2A| 0 ~ 16.6A| 0 ~ 12.5A
RATED POWER| 500W| 600W| 600W| 600W| 599.4W| 597.6W| 600W
RIPPLE & NOISE (max.) Note.2| 200mVp-p| 200mVp-p| 200mVp-p| 240mVp-p| 270mVp-p| 360mVp-p| 360mVp-p
VOLTAGE ADJ. RANGE Note.3| 4.75 ~ 5.5V| 11.4 ~ 13.2V| 14.25 ~ 16.5V| 22.8 ~ 26.4V| 25.65 ~ 29.7V| 34.2 ~ 39.6V| 45.6 ~ 52.8V
VOLTAGE TOLERANCE Note.4| ±2.0%| ±1.5%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION **Note.5| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION Note.6| ±2.0%| ±1.0%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME Note.7| 1300ms, 50ms/230VAC 1300ms,50ms/115VAC at full load
HOLD UP TIME (Typ.)| 20ms/230VAC    16ms/115VAC at full load
INPUT| VOLTAGE RANGE ****Note.8| 90 ~ 132VAC / 180 ~ 264VAC by switch               255 ~ 370VDC (swith on 230VAC)
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 86%| 90%| 90%| 91%| 91%| 92%| 92%
AC CURRENT (Typ.)| 12A/115VAC        7.5A/230VAC
INRUSH CURRENT (Typ.)| 35A/115VAC       60A/230VAC
LEAKAGE CURRENT| <2mA / 240VAC
PROTECTION (Note.9)| OVER LOAD| 105 ~ 150% rated output power
Constant current limiting, unit will shutdown after 3 sec. re-power on to recover
OVER VOLTAGE| 5.75 ~ 6.75V| 13.8 ~ 16.2V| 18 ~ 21V| 27.6 ~ 32.4V| 31 ~ 36.5V| 41.4 ~ 48.6V| 55.2 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, re-power on to recover
FUNCTION| FAN ON/OFF CONTROL (Typ.)| RTH3≧50℃ FAN ON, ≦40℃ FAN OFF
ENVIRONMENT| WORKING TEMP.| -20 ~ +65℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
OVER VOLTAGE CATEGORY| Ⅲ: According to EN61558, EN50178, EN60664-1, EN62477-1; altitude up to 2000 meters
SAFETY| ****SAFETY STANDARDS| BS IEC/UL 62368-1, EAC TP TC 004, KC62368-1(except for 5V), BIS IS13252(Part1):2010/IEC60950-1: 2005(NOTE 13),BSMI CNS15598-1,GB 4943.1,BS EN/EN61558-1,BS EN/EN61558-2-16 approved, Designed by AS/NZS 61558.1/2.16, AS/NZS 62368.1
WITHSTAND VOLTAGE| I/P-O/P:3.75KVAC I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to EAC TP TC 020, BSMI CNS15936,KC KSC 9832, KSC 9835
EMC IMMUNITY| Compliance to EAC TP TC 020,KC KSC 9832, KSC 9835
OTHERS| MTBF| 1533.4K hrs min. Telcordia SR-332(Bellcore) ; 301.7K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION| 22512441mm (LWH)
PACKING| 0.95Kg/12pcs/12.4Kg/0.77CUFT
NOTE**|

  1. A parameters NOT speciay mentioned are measured at 230VAC input,rated oad and 25℃ of ambient temperature.
  2. Rippe & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parae capacitor.
  3. Votage adjustment can ony be operated within the input range of 100~120VAC or 200-240VAC. If the votage adjustment is performed outside this range, it may cause abnorma output.
  4. Toerance : incudes set up toerance, ine reguation and oad reguation.
  5. Line reguation is measured from ow ine to high ine at rated oad.
  6. Load reguation is measured from 0% to 100% rated oad.
  7. Length of set up time is measured at cod start. Turning the power suppy on/off frequenty may ead to increase of the set up time.
  8. Derating may be needed under ow input votages. Pease refer to”Static Characteristics” sections for detais.
  9. Once protections are triggered, 4min(Typ.) of cod down time is required before restart.
  10. The ambient temperature derating of 5℃/1000m is needed for operating atitude greater than 2000m(6500ft).
  11. This power suppy does not meet the harmonic current requirements outined by EN61000-3-2. Pease do not use this power suppy under the foowing conditions:a) the end-devices is used within the European Union, andb) the end-devices is connected to pubic mains suppy with 220Vac or greater rated nomina votage, andc) the power suppy is:- instaed in end-devices with average or continuous input power greater than 75W, or- beong to part of a ighting system Exception:Power suppies used within the foowing end-devices do not need to fufi EN61000-3-2a) professiona equipment with a tota rated input power greater than 1000W;b) symmetricay controed heating eements with a rated power ess than or equa to 200W12. RCM is on vountary basis and meets reevant IEC or AS/NZS standards compying with AS/NZS 4417.1.13. Some model may not have the BIS logo, please contact your MEAN WELL sales for more information.※ Product Liabiity Discaimer:For detaied information, pease refer to https://[www.meanwell.com/serviceDisclaimer.aspx](http://www.meanwell.com/serviceDisclaimer.aspx)

Block Diagram

Installation

Derating Curve

AMBIENT TEMPERATURE \(℃\)

AMBIENT TEMPERATURE (℃)

Static Characteristics

INPUT VOLTAGE \(VAC\) 60Hz

INPUT VOLTAGE (VAC) 60Hz

Note: Due to the test method difference, the rating on label differ from derating curve as follow.
For 5V model, the output current states 100A on label when input voltage > 110Vac, and states 90A when input voltage < 110Vac, please refer to label for detail

Symbols

Symbols

User’s Manual

Documents / Resources

| MEAN WELL LRS-600-5 Single Output Switching Power Supply [pdf] Owner's Manual
LRS-600-5, LRS-600-12, LRS-600-15, LRS-600-24, LRS-600-27, LRS-600-36, LRS-600-5 Single Output Switching Power Supply, LRS-600-5, Single Output Switching Power Supply, Switching Power Supply, Power Supply
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals