LUTRON Typical Wallbox Load Controls Instructions
- June 7, 2024
- Lutron
Table of Contents
LUTRON Typical Wallbox Load Controls Instructions
WIRING LEGEND:
NPUT POWER (NORMAL-EMERGENCY) INPUT POWER (NORMAL) 2 #12AWG (4 mm2) 0-10V SIGNAL: 2 #18AWG (1.0 mm2) ECOSYSTEM BUS/LOOP: LUTRON CABLE C-CBL-216-GR-1 (2
16 CONDUCTOR NON-PLENUM) OR C-PCBL-216-CL-1 (2 #16 CONDUCTOR PLENUM RATED).
OTHERWISE USE 2 #16 AWG (1.5 mm2) BY OTHERS.
1-WAY RF COMMUNICATION
2-WAY RF COMMUNICATION 2 #18AWG (1.0 mm2)
E CAT5E OR BETTER CABLE FOR LUTRON NETWORK TERMINATED WITH RJ45 CONNECTORS (TO
BE PROVIDED BY OTHERS). 328 ft (100 m) MAXIMUM RUN.
WIRING NOTES:
LUTRON LIGHTING MANAGEMENT NETWORK
WHEN A LIGHTING MANAGEMENT NETWORK (LMN) IS REQUIRED TO ENABLE COMMUNICATIONS
BETWEEN INDIVIDUAL LIGHT MANAGEMENT HUBS (LMH) AND BETWEEN LMH AND THE SYSTEM
SERVER/DESKTOP/LAPTOP (Q-MANAGER). THE LMN REQUIRES A DEDICATED LAN OR VLAN.
IT IS THE RESPONSIBILITY OF THE NETWORK PROVIDER TO ENSURE THE RELIABILITY AND
SECURITY OF THE LMN. CAT5E OR BETTER ETHERNET CABLE TO BE RUN FOR DEDICATED
LMN TERMINATED WITH RJ45 CONNECTORS (PROVIDED BY OTHERS). THE NUMBER OF
ETHERNET HOPS/SEGMENTS BETWEEN THE SERVER/DESKTOP/LAPTOP (Q-MANAGER) AND ANY
LMN NODE SHALL NOT EXCEED 6. TOTAL LENGTH OF ETHERNET CABLE SHALL NOT EXCEED
328 FT (100M) POINT-TO-POINT. IF LONGER RUNS ARE REQUIRED, MULTI-MODE FIBER
OPTIC CABLE CAN BE USED INSTEAD WITH APPROPRIATE FIBER OPTIC CONNECTORS
(PROVIDED BY OTHERS). CONSULT WITH NETWORK PROVIDER FOR STANDARD ETHERNET AND
FIBER OPTIC WIRING RULES FOR DISTANCE AND SEPARATION AS WELL AS FOR PLACEMENT
OF SWITCHES, ROUTERS, HUBS, ETC. FOR MORE INFORMATION REGARDING NETWORK
EQUIPMENT REQUIREMENTS AND NETWORK CONFIGURATION, PLEASE REFER TO THE QUANTUM
LIGHTING MANAGEMENT NETWORK SPECIFICATION SHEET OR CONTACT LUTRON. CONCEPT
DRAWING NOTES: CONTROL SYSTEM DRAWING IS PROVIDED FOR CONCEPTUAL PURPOSES ONLY
AND IS NOT INTENDED FOR CONSTRUCTION. EXACT EQUIPMENT REQUIREMENTS, INCLUDING
LOCATIONS AND QUANTITIES, SHOULD BE VERIFIED IN ACCORDANCE WITH THE MOST UP-
TO-DATE LIGHTING/ELECTRICAL REFLECTED CEILING PLANS, LIGHTING FIXTURE
SCHEDULES, PANEL SCHEDULES, CONTROL INTENT AND SPECIFICATIONS. SHADE EQUIPMENT
SHOULD BE VERIFIED IN ACCORDANCE WITH ARCHITECTURAL PLANS, SPECIFICATIONS AND
WINDOW SCHEDULES/DETAILS. LED DIMMING REQUIRES AN EXACT MATCH BETWEEN THE LED
ARRAY, DRIVER AND CONTROL. LUTRON CANNOT GUARANTEE COMPATIBILITY OR
PERFORMANCE WITHOUT TESTING THIS COMBINATION. TO CONFIRM WHAT PRODUCTS LUTRON
HAS AVAILABLE OR WHAT INTERFACES MAY BE REQUIRED, CALL 1-877-DIM-LED8 OR CHECK
LUTRON’S PRODUCT COMPATIBILITY MATRIX ON-LINE AT WWW.LUTRON.COM/LED. TO
REQUEST THE TESTING OF AN LED PRODUCT BY LUTRON MANUFACTURERS CAN FILL OUT AN
LED EVALUATION REQUEST FORM ON-LINE AT WWW.LUTRON.COM/LED OR CONTACT
LEDS@LUTRON.COM. LUTRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF LUTRON
HI-LUME A-SERIES LED DRIVERS USED WITH APPROPRIATE LUTRON CONTROLS. THE HI-
LUME A-SERIES LED DRIVER CAN BE USED ON PRODUCTS UNDER 40 WATTS WITH SUITABLE
MOUNTING LOCATIONS. PLEASE REFER TO THE SPECIFICATION SUBMITTAL SHEET FOR
FURTHER INFORMATION. IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING 0-10V
CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON.
PRODUCTS FOLLOWING THE IEC STANDARD 60929 ARE MORE LIKELY TO PROVIDE
ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO
THE USER’S DISCRETION. IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING
PHASE CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON.
A-SERIES OR ELV PRODUCTS PROVIDING HIGH END AND LOW END TRIM ADJUSTMENTS ARE
MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT
ACCEPTABILITY IS UP TO THE USER’S DISCRETION. TYPICAL HUB FLUSH MOUNT AND
SURFACE MOUNT OPTIONS AVAILABLE
BACNET INTEGRATION AVAILABLE ON CERTAIN MODELS MINIMUM OF 10′ BETWEEN HUBS ON
THE SAME FLOOR
TYPICAL HUB FLUSH MOUNT AND SURFACE MOUNT OPTIONS AVAILABLE BACNET INTEGRATION
AVAILABLE ON CERTAIN MODELS MINIMUM OF 10′ BETWEEN HUBS ON THE SAME FLOOR
TYPICAL WALLBOX LOAD CONTROLS MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME
FLOOR
MRF2S-6ANS-WH MAESTRO WIRELESS 6A, 120V COMMERCIAL SWITCH (1 GANG US
BACKBOX BY OTHERS)
LOCATION TBD
MRF2S-8ANS120-WH MAESTRO WIRELESS 8A, 120V~ COMMERCIAL SWITCH (1 GANG US
BACKBOX BY OTHERS)
LOCATION TBD
MRF2S-8S-DV-WH MAESTRO WIRELESS 8A, 120/277V~ COMMERCIAL SWITCH (1 GANG US
BACKBOX BY OTHERS)
LOCATION TBD
MRF2S-6CL-WH MAESTRO WIRELESS MULTI-LOCATION/SINGLE-POLE
L DIMMER, 120V~ 150 W DIMMABLE CFL/LED/ 600W INCANDESCENT/HALOGEN (1 GANG US
BACKBOX BY OTHERS) LOCATION TBD
MRF2S-6ND-WH MAESTRO WIRELESS MULTI-LOCATION/SINGLE-POLE SPEC GRADE DIMMER 120V, 600W/VA INCANDESCENT/HALOGEN *NEUTRAL WIRE REQUIRED (1 GANG US BACKBOX BY OTHERS) LOCATION TBD
MRF2S-6ELV120-WH MAESTRO WIRELESS MULTI-LOCATION/SINGLE-POLE DIGITAL FADE DIMMER 120V, 600W ELECTRONIC LOW-VOLTAGE (1 GANG US BACKBOX BY OTHERS) LOCATION TBD
TYPICAL LOAD CONTROL MODULES MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME
FLOOR
RMJS-5R-DV-B POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/ (1) 5A RELAY
DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION
RMJS-5RCCO1-DV-B POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/ (1) 5A RELAY & (1) CONTACT CLOSURE OUTPUT DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-16R-DV-B POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/ (1) 16A SOFTSWITCH RELAY DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-20R-DV-B POWPAK 20A RELAY MODULE 120/277V~, 50/60 Hz CAPABLE OF SWITCHING
GENERAL PURPOSE
LOADS & 20A RECEPTACLES *SHOWN WITH DUPLEX RECEPTACLE **NOT INTENDED FOR
CONTROL OF PERMANENTLY INSTALLED LIGHTING FIXTURES 3.42″(H) X 2.82″(W) X
1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-16RCCO1-DV-B POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/ (1) 16A RELAY & (1) CONTACT CLOSURE OUTPUT DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-20RCCO1DV-B POWPAK 20A RELAY MODULE 120/277V~, 50/60 Hz CAPABLE OF SWITCHING GENERAL PURPOSE LOADS & 20A RECEPTACLES, W/ (1) CONTACT CLOSURE OUTPUT *SHOWN WITH DUPLEX RECEPTACLE **NOT INTENDED FOR CONTROL OF PERMANENTLY INSTALLED LIGHTING FIXTURES 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-8T-DV-B POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-CCO1-24-B POWPAK CCO MODULE W/ (1) CONTACT CLOSURE OUTPUT DIMENSIONS:
3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-8TN-DV-B POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
RMJS-ECO32-SZ POWPAK SINGLE ZONE CONTROL MODULE W/ ECOSYSTEM 120-277V~, 50/60
Hz (1) PARTIAL BUS SUPPLY FOR UP TO 32 BALLASTS/INTERFACES DIMENSIONS:
3.42″(H) X 2.82″(W) X 1.25″(D)(87mm X 72mm X 32mm)
LOCATION TBD TYPICAL IN-WALL SENSOR DEVICES (VACANCY-ONLY MODELS ALSO
AVAILABLE) MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR
MRF2S-8SD010-WH 120/277V~, 50/60 Hz MAESTRO SENSOR 0-10V DIMMER OCCUPANCY/VACANCY SENSOR SINGLE POLE/MULTI-LOCATION *NEUTRAL WIRE REQUIRED AUTO ON/AUTO OFF OR MANUAL ON/AUTO OFF (1 GANG US BACK BOX BY OTHERS) LOCATION TBD
MRF2S-8SS-WH 120/277V~, 50/60 Hz MAESTRO SENSOR SWITCH OCCUPANCY/VACANCY SENSOR SINGLE POLE/MULTI-LOCATION *NEUTRAL WIRE REQUIRED AUTO ON/AUTO OFF OR MANUAL ON/AUTO OFF (1 GANG US BACK BOX BY OTHERS) LOCATION TBD TYPICAL PER FIXTURE LOAD CONTROL MODULES & SENSORS MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR FCJS-010 TO WIRED SENSOR POWPAK WIRELESS FIXTURE CONTROL 120-277V~, 50/60 Hz FOR 0-10 V CONTROL DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
FCJS-ECO TO WIRED SENSOR POWPAK WIRELESS FIXTURE CONTROL 120-277V~, 50/60 Hz FOR ECOSYSTEM (1) PARTIAL BUS SUPPLY FOR UP TO 3 BALLASTS/INTERFACES DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
LOCATION TBD
FC-SENSOR POWPAK FIXTURE SENSOR OCCUPANCY 1.5″(DIA) X 0.65″(D) (38mm X 17mm) *DEVICE IS SURFACE-MOUNTED LOCATION TBD
TO FIXTURE CONTROLLER FC-VSENSOR POWPAK FIXTURE SENSOR VACANCY 1.5″(DIA) X 0.65″(D) (38mm X 17mm) *DEVICE IS SURFACE-MOUNTED LOCATION TBD TYPICAL SENSORS & REMOTE CONTROLS MAX OF 30′ TO LOAD DEVICES – MAX OF 71′ FROM VIVE HUB AND LOCATED ON THE SAME FLOOR OTHER SENSOR OPTIONS AVAILABLE (SEE SPEC SHEET)
OTHER BUTTON CONFIGURATIONS AVAILABLE (SEE SPEC SHEET FOR OPTIONS)
LRF2-DCRB-WH 434MHZ WIRELESS DAYLIGHT SENSOR 1.6″[40,6mm] (DIA) X 0.7″[17,8mm]
(D) *DEVICE IS SURFACE-MOUNTED AND BATTERY POWERED, DOES NOT REQUIRE POWER
FEED
LOCATION TBD
TYPICAL CLEAR CONNECT WIRELESS FIXTURE CONTROLS (OEM SUPPLIED) MAX OF 71′ FROM
VIVE HUB AND LOCATED ON SAME FLOOR TYPICAL WIRELESS RECEPTACLES MAX OF 71′
FROM VIVE HUB AND LOCATED ON SAME FLOOR CAR2S-20-DTR-WH 20A TAMPER
RESISTANT, DUPLEX RECEPTACLE 120V~, 50/60 Hz
DUAL SWITCHING SINGLE POLE/DOWNSTREAM W/ 431-437 MHZ CLEAR CONNECT RF (1 GANG
US BACKBOX BY OTHERS) LOCATION TBD
CAR2S-15-DTR-WH 15A TAMPER RESISTANT, DUPLEX RECEPTACLE 120V~, 50/60 Hz DUAL SWITCHING SINGLE POLE/DOWNSTREAM W/ 431-437 MHZ CLEAR CONNECT RF (1 GANG US BACKBOX BY OTHERS) LOCATION TBD
TYPICAL WIRELESS RECEPTACLES
MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR
CAR2S-20-DTR-WH 20A TAMPER RESISTANT, DUPLEX RECEPTACLE 120V~, 50/60 Hz DUAL SWITCHING SINGLE POLE/DOWNSTREAM W/ 431-437 MHZ CLEAR CONNECT RF (1 GANG US BACK BOX BY OTHERS) LOCATION TRD
CAR2S-20-STR-WH 20A TAMPER RESISTANT, SPLIT DUPLEX RECEPTACLE 120V~, 50/60 Hz HALF SWITCHING SINGLE POLE/DOWNSTREAM W/ 431-437 MHZ CLEAR CONNECT RF (1 GANG US BACKBOX BY OTHERS) LOCATION TRD
CAR2S-15-DTR-WH 15A TAMPER RESISTANT, DUPLEX RECEPTACLE 120V~, 50/60 Hz DUAL SWITCHING SINGLE POLE/DOWNSTREAM W/ 431-437 MHZ CLEAR CONNECT RF (1 GANG US BACKBOX BY OTHERS) LOCATION TRD
CAR2S-15-STR-WH 15A TAMPER RESISTANT, SPLIT DUPLEX RECEPTACLE 120V~, 50/60 HZ
HALF SWITCHING SINGLE POLE/DOWNSTREAM W/ 431-437 MHZ CLEAR CONNECT RF (1 GANG
US BACKBOX BY OTHERS) LOCATION TRD
TYPICAL UL924 LISTED EMERGENCY LOAD CONTROLS MAX OF 71′ FROM VIVE HUB AND
LOCATED ON SAME FLOOR
RMJS-16R-DV-B-EM NORMAL/EMERGENCY POWPAK RELAY MODULE 120/277V~, 50/60 Hz
W/ (1) 16A SOFTSWITCH RELAY, UL 924 LISTED DIMENSIONS: 3.42″(H) X 2.82″(W) X
1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
FCJS-010-EM TO WIRED SENSOR NORMAL/EMERGENCY POWPAK WIRELESS FIXTURE CONTROL 120-277V~, 50/60 Hz FOR 0-10 V CONTROL, UL 924 LISTED DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
FCJS-ECO-EM NORMAL/EMERGENCY POWPAK WIRELESS FIXTURE CONTROL 120-277V~, 50/60 Hz FOR ECOSYSTEM, UL 924 LISTED 1) PARTIAL BUS SUPPLY FOR UP TO 3 BALLASTS/INTERFACES DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TBD
FCJS-ECO-EM NORMAL/EMERGENCY POWPAK WIRELESS FIXTURE CONTROL 120-277V~, 50/60 Hz FOR ECOSYSTEM, UL 924 LISTED (1) PARTIAL BUS SUPPLY FOR UP TO 3 BALLASTS/INTERFACES DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm) LOCATION TRD
TYPICAL LOAD SIDE TRANSFER RELAYS PROVIDED BY LVS CONTROLS – CONTACT YOUR LUTRON REPRESENTATIVE FOR MORE INFORMATION
LUT-SHUNT-D LVS CONTROLS SHUNT RELAY FOR USE WITH 0-10V & ECOSYSTEM LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS
LUT-SHUNT LVS CONTROLS SHUNT RELAY FOR USE WITH LINE VOLTAGE SWITCHING AND DIMMING LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS
LUT-ALCR-D LVS CONTROLS ALCR DEVICE FOR USE WITH 0-10V & ECOSYSTEM LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS
LUT-ALCR LVS CONTROLS SHUNT RELAY FOR USE WITH SWITCHING LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS
LUT-ATS-D
LVS CONTROLS TRANSFER SWITCH FOR USE WITH LINE VOLTAGE DIMMING LOADS
REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS