SCHLAGE ND-Series Electrified Locks Instructions
- June 7, 2024
- Schlage
Table of Contents
SCHLAGE ND-Series Electrified Locks Instructions
ND-Series Electrified Lock
For standard installation, see full instruction sheet.
Select the appropriate mode for the installation using the mode select switch located on the chassis. Note: When mode is switched (from EL to EU or EU to EL) the lock requires a complete lock/unlock power cycle to synchronize to the proper mode.
EL, electrically locked (fail safe):
Outside knob/lever or both outside and inside knobs/levers (depending on
function) will lock when power is applied. In the event of power failure, the
opening will be unlocked.
EU, electrically unlocked (fail secure):
Outside knob/lever or both outside and inside knobs/levers (depending on
function) will unlock when power is applied. In the event of power failure,
the opening will be locked.
Electrical requirements:
The ND-Series electrified locks are powered by DC power only. DO NOT USE AC POWER.
- Voltage: 12 or 24 V DC (maximum 26.4 V, minimum 10.8 V)
- Holding current: 10 mA
- Peak current: 230 mA
- Operating temperature: 32°F to 120°F (0°C to 49°C)
- All power requirements shown are for single lock operation.
| AWG| 14| 16| 18|
20
---|---|---|---|---|---
Voltage
|
12 V
| 500’ (152 m)| 300’ (91 m)| 200’ (61 m)|
100’ (30 m)
24 V
|
Up to 1000’ (304 m)
Note: Either lock wire may be attached to either power supply terminal (+ or -).
Troubleshooting:
If lock does not operate –
- Ensure the lock is powered with DC power.
- Ensure the input voltage is between 10.8 and 26.4 volts DC.
- Do not use AC power
Request-to-Exit (RX) Lock
RX utilizes a microswitch inside the lock case to detect rotation of the
inside knob/lever. The switch then signals the use of the opening to the
security system.
Attach wires from RX switch wire harness to an electrified hinge/EPT (not
furnished). Refer to the Allegion Connect section below for wire
identification. Electrical rating: 2 A, 30 V DC
RX Switch kit #N123-062 installation:
Attach switch assembly to pin on chassis using the screw (included with kit).
Use RX anti-rotation plate (see inset).
Allegion Connect
Allegion Connect, a factory-installed Molex® connector system, provides
simplified installation and maintenance utilizing quick-connect harnesses and
hinges. Alternatively, the Molex connector may be cut off and the lock
installed with traditional wire splicing methods.
WIRE COLOR AND FUNCTION
Pin
| Color|
Function
1
| Black Power|
(auto detects GND, +12 or +24 V DC)
2
| Red Power|
(auto detects GND, +12 or +24 V DC)
3| Purple|
RX NO (normally open)
4
|
Grey
|
RX NC (normally closed)
5
| White|
RX COM (common for RX)
6, 7, 8
| |
Not Use