VYNCO VMC368 68 Way Three Phase Series Combined Meter Boards Instruction Manual
- June 7, 2024
- VYNCO
Table of Contents
VYNCO VMC368 68 Way Three Phase Series Combined Meter Boards
SPECIFICATIONS
SPECIFICATIONS
Rated Operational Voltage| 415V AC maximum, 50Hz
Maximum Current| 100A
Rated Insulation Voltage| 1000V
Short Circuit Withstand| 10kA
DIMENSIONS
DIMENSIONS
Cover Assembly| 1005 x 402 x 77mm
Base Box Dimensions| 958 x 355 x 150mm
Overall Assembled Dimensions| 1005x 402 x 171mm
Total Internal Meter Mounting Space| 310 x 320 x 139mm
Maximum Meter Depth| 130mm
EARTH AND NEUTRAL BUSBAR LAYOUT
EARTH AND NEUTRAL BUSBAR LAYOUT
| Material| Number of Bars| Double Screw Tunnels| Single
Screw Tunnels
Earth Bar| Brass with steel screws| 2| 3| 40
Neutral Bar| Brass with steel screws| 1| 4| 14
RCD Neutral Bar| Brass with steel screws| 10| 1| 3
REMOVING DOOR
-
STEP 1
Rotate top pin 90°. -
STEP 2
Slide pin down to release door. There is no need to remove pin completely. -
STEP 3
Lift and remove door.
FITTING DIAGRAM
To fit into wall cavity, fold out tabs to set height of enclosure onto studs.
WARRANTY
This product is covered by a 1 Year Vynco Warranty – proof of purchase is required. Please contact Vynco for details of returns procedure.
NOTE : This product contains NO user serviceable parts.
SAFETY
- This product complies in full with AS/NZS 61439.3.
- This product should be installed by a suitably qualified person in accordance with Australian and New Zealand wiring rules.
INSTALLATION PROCEDURE
- This product is designed to be installed inside a wall cavity with a minimum stud size of 90mm and a minimum plaster board/wall covering of 10mm.
- The metal wall enclosure must be earthed. Fold out tags (x6) on the side walls of the enclosure can be folded out to set the correct height onto the studs.
- Door hinge pins are easily removable and the door can be reversed so that it swings either left or right. This product is designed to be used with
- New Zealand and Australia’s MEN system.
- DO NOT install a link between the neutral bars and earth bar on circuits dedicated to RCDs. Please ensure circuits and protective devices are adequately identified during installation.