SONBEST SM7005 Metal Outer Shell Optical Rain Sensor User Manual
- June 1, 2024
- SONBEST
Table of Contents
SM7005 Metal Outer Shell Optical Rain Sensor
“`html
Product Information
Specifications:
- Brand: SONBEST
- Accuracy: ±5% @ 25°C
- Resolution: 0.1mm
- Maximum Rainfall Sensing Diameter: 24mm
- Working Pressure: Standard atmospheric pressure ±10%
- Communication Interface: RS485
- Default Baud Rate: 9600
- Power: DC6~24V 1A
- Running Temperature: -30°C to 85°C
Product Usage Instructions:
Wiring Instructions:
In the case of broken wires, wire the wires as shown in the
figure. If the product itself has no leads, the core color is for
reference.
How to Use:
Ensure the device is properly wired according to the wiring
instructions. To read data from the device:
-
Set up the communication protocol to RS485 MODBUS-RTU standard
format. -
Send the appropriate hexadecimal command to query data from the
device. -
Interpret the response data received from the device.
Application Solution:
Explore various application solutions for integrating the SM7005
into different systems or instruments for monitoring rainfall state
quantities.
FAQ:
Q: What is the default baud rate of the data recorder?
A: The default baud rate of the data recorder is 115200.
Q: What is the default device address when leaving the
factory?
A: The default device address is 1 when the device leaves the
factory.
“`
SM7005 User Manual
SM7005 Metal outer shell optical rain sensor
User Manual
File Version: V24.4.13
SM7005 using the standard RS485 bus MODBUS-RTU protocol,easy access to PLCDCS and other instruments or systems for monitoring rainfall state quantities.The internal use of high-precision sensing core and related devices to ensure high reliability and excellent long-term stability,can be customized RS232,RS485,CAN,4-20mA,DC0~5V10V,ZIGBEE,Lora,WIFI,GPRS and other output methods.
ShanghaiSonbest Industrial Co., Ltd
Page1
SM7005 User Manual
Technical Parameters
Technical parameter Brand Accuracy Resolution Maximu rainfall Sensing diameter
Working pressure Communication Interface Default baud rate Power Power Running
temperature
Product Size
Parameter value SONBEST ±5%@25 0.1mm 24mm 60mm Standard atmospheric pressure±10% RS485 9600 8 n 1 DC6~24V 1A DC6~24V 1A -30~85
ShanghaiSonbest Industrial Co., Ltd
Page2
SM7005 User Manual
ShanghaiSonbest Industrial Co., Ltd
Page3
SM7005 User Manual
ShanghaiSonbest Industrial Co., Ltd
Page4
SM7005 User Manual
ShanghaiSonbest Industrial Co., Ltd
Page5
SM7005 User Manual
Wiring instructions
In the case of broken wires, wire the wires as shown in the figure. If the
product itself has no leads, the core color is for reference.
How to use?
ShanghaiSonbest Industrial Co., Ltd
Page6
SM7005 User Manual
Application solution
ShanghaiSonbest Industrial Co., Ltd
Page7
SM7005 User Manual
ShanghaiSonbest Industrial Co., Ltd
Page8
SM7005 User Manual
Product List
Communication Protocol ShanghaiSonbest Industrial Co., Ltd
Page9
SM7005 User Manual
The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands
are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module
or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default
baud rate is 115200 .
1. Read data (function code 0x03)
Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends
the command: 01 03 00 00 00 01 84 0A .
Address
Function Code
Start Address
Data Length
Check Code
01
03
00 00
00 01
84 0A
For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6 , response format:
Address
Function Code
Length
Data 1
Check Code
01
03
02
00 79
79 A6
Data description: The data in the command is hexadecimal, take data 1 as an example, 00 79 is
converted to decimal value as 121, assuming the data magnification is 100, then the real value is
121/100=1.21, Others and so on.
2. Common data address table
Configuration
Register Address Register
Data Type
Value Range
Address
Description
40001
00 00
rainfall
Read Only
0~65535
40101
00 64
Model Code
Read/Write
0~65535
40102
00 65
total number of
read/write
1~20
measuring points
40103
00 66
device address
read/write
1~249
40104
00 67
baud rate
read/write
0~6
40105
00 68
communication
read/write
1~4
mode
40106
00 69
protocol type
read/write
1~10
3 Read and modify device address
(1) Read or query device address
If you don’t know the current device address and there is only one device on the bus, you can query
the device address through the commandFA 03 00 66 00 01 71 9E .
Device Address
Function Code
Start Address
Data Length
Check Code
FA
03
00 66
00 01
71 9E
FA means 250 is the general address, when you don’t know the address, you can use 250 to get the
real device address, 00 66 is the device address register.
For the correct query command, the device will respond, for example, the response data is: 01 03 02
00 01 79 84, and its format parsing is shown in the following table:
Device Address
Function Code
Start Address
Model Code
Check Code
01
03
02
00 01
79 84
In the response data, the first byte 01 represents the real address of the current device.
(2) Change device address
For example, if the current device address is 1 and we want to change it to 02, the command is: 01 06
00 66 00 02 E8 14 .
Device Address
Function Code
Register Address Target Address
Check Code
ShanghaiSonbest Industrial Co., Ltd
Page10
SM7005 User Manual
01
06
00 66
00 02
E8 14
After the change is successful, the device will return the information: 02 06 00 66 00 02 E8 27 , and its
format analysis is shown in the following table:
Device Address
Function Code
Register Address Target Address
Check Code
02
06
00 66
00 02
E8 27
In the response data, after the modification is successful, the first byte is the new device address.
Generally, after the device address is changed, it will take effect immediately. At this time, the user needs
to change the query command of his software accordingly. .
4 Read and modify baud rate
(1) Read baud rate
The default factory baud rate of the device is 9600. If you need to change it, you can change it
according to the following table and the corresponding communication protocol. For example, to read the
baud rate ID of the current device, the command is: 01 03 00 67 00 01 35 D5 , the format is parsed as
follows.
Device Address
Function Code
Start Address
Data Length
Check Code
01
03
00 67
00 01
35 D5
Read the baud rate code of the current device. Baud rate code: 1 is 2400; 2 is 4800; 3 is 9600; 4 is
19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example, the response data is: 01 03 02
00 03 F8 45, and its format analysis is shown in the following table:
Device Address
Function Code
Data Length
Baud Rate Code Check Code
01
03
02
00 03
F8 45
According to the baud rate code, 03 is 9600, that is, the baud rate of the current device is 9600.
(2) Change the baud rate
For example, change the baud rate from 9600 to 38400, that is, change the code from 3 to 5, the
command is: 01 06 00 67 00 05 F8 16 .
Device Address
Function Code
Register Address Target Baud Rate Check Code
01
06
00 67
00 05
F8 16
Change the baud rate from 9600 to 38400, that is, change the code from 3 to 5. The new baud rate will
take effect immediately, and the device will lose response at this time, and the baud rate of the device
needs to be checked accordingly Modified.
5 Read and modify correction value
(1) Read correction value
When there is an error between the data and the reference standard, we can reduce the display error
by adjusting the correction value. The correction difference can be modified in a rang e of plus or minus
1000, that is, the value range is 0-1000 or 64535 -65535. For example, when the displayed value is too
small by 100, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the
command, 100 is hexadecimal 0x64 ;If you need to reduce it, you can set a negative value, such as -100,
the corresponding hexadecimal value is FF 9C, the calculation method is 100 -65535=65435, and then
converted to hexadecimal, it is 0x FF 9C. Device The correction value starts from 00 6B. We take the first
parameter as an example to illustrate. When there are multiple parameters, the correction value is read
and modified in the same way.
Device Address
Function Code
Start Address
Data Length
Check Code
01
03
00 6B
00 01
F5 D6
ShanghaiSonbest Industrial Co., Ltd
Page11
SM7005 User Manual
For the correct query command, the device will respond, for example, the response data is: 01 03 02
00 64 B9 AF, and its format parsing is shown in the following table:
Device Address
Function Code
Data Length
Correction Value Check Code
01
03
02
00 64
B9 AF
In the response data, the first byte 01 represents the real address of the current device, and 00 6B is
the first state correction value register. If the device has multiple parameters, other parameters operate in
the same way as this The same, generally temperature and humidity have this parameter, and lighting
generally does not have this parameter.
(2) Change the correction value
For example, if the current state is too small, we want to add 1 to its real value, and add 100 to the
current value. The correction operation command is: 01 06 00 6B 00 64 F9 FD .
Device Address
Function Code
Register Address Target Address
Check Code
01
06
00 6B
00 64
F9 FD
After the operation is successful, the device will return the information: 01 06 00 6B 00 64 F9 FD , after
the successful change, the parameters will take effect immediately.
Disclaimer
This document provides all information about the product, does not grant any license to intellectual
property, does not express or imply, and prohibits any other means of granting any intellectual property
rights, such as the statement of sales terms and conditions of this product, other issues. No liability is
assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use
of this product, including the suitability for the specific use of the product, the marketability or the
infringement liability for any patent, copyright or other intellectual property rights, etc. Product
specifications and product descriptions may be modified at any time without notice.
Contact Us
Company: Shanghai Sonbest Industrial Co., Ltd
Address:Building 8,No.215 North east road,Baoshan District,Shanghai,China
SKYPE: soobuu
Email: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077
ShanghaiSonbest Industrial Co., Ltd
Page12