VYNCO VMC351 51 Way Three Phase Series Combined Meter Boards Owner’s Manual
- May 15, 2024
- VYNCO
Table of Contents
VYNCO VMC351 51 Way Three Phase Series Combined Meter Boards
SPECIFICATIONS
Rated Operational Voltage | 415V AC maximum, 50Hz |
---|---|
Maximum Current | 100A |
Rated Insulation Voltage | 1000V |
Short Circuit Withstand | 10kA |
DIMENSIONS
Cover Assembly | 900 x 402 x 77mm |
---|---|
Base Box Dimensions | 853 x 355 x 150mm |
Overall Assembled Dimensions | Total Internal Meter Mounting Space |
130mm | Maximum Meter Depth |
WARRANTY
This product is covered by a 1 Year Vynco Warranty – proof of purchase is
required. Please contact Vynco for details of returns procedure.
NOTE: This product contains NO user serviceable parts.
SAFETY
This product complies in full with AS/NZS 61439.3.
This product should be installed by a suitably qualified person in accordance
with Australian and New Zealand wiring rules.
INSTALLATION PROCEDURE
This product is designed to be installed inside a wall cavity with a minimum
stud size of 90mm and a minimum plaster board/wall covering of 10mm. The metal
wall enclosure must be earthed. Fold out tags (x6) on the side walls of the
enclosure can be folded out to set the correct height onto the studs. Door
hinge pins are easily removable and the door can be reversed so that it swings
either left or right. This product is designed to be used with New Zealand and
Australia’s MEN system.
DO NOT install a link between the neutral bars and earth bar on circuits
dedicated to RCDs. Please ensure circuits and protective devices are
adequately identified during installation
EARTH AND NEUTRAL BUSBAR LAYOUT
| Material| Number of Bars| Double Screw Tunnels| Single
Screw Tunnels
---|---|---|---|---
Earth Bar| Brass with steel screws| 1| 3| 40
Neutral Bar| Brass with steel screws| 1| 4| 22
RCD Neutral Bar| Brass with steel screws| 8| | 3
REMOVING DOOR
STEP 1
Rotate top pin 90°.
STEP 2
Slide pin down to release door. There is no need to remove pin completely.
STEP 3
Lift and remove door.
FITTING DIAGRA
To fit into wall cavity, fold out tabs to set height of enclosure onto studs.
CUSTOMER SUPPORT
VYNCO INDUSTRIES (NZ) LIMITED CHRISTCHURCH
388 Tuam Street, Phillipstown, Christchurch, 8011 PO Box 9022, Tower Junction,
Christchurch 8149 New Zealand
P +64 3 379 9283
E sales@vynco.co.nz
VYNCO.CO.NZ
AUCKLAND
9 Levene Place, Mount Wellington PO Box 12 249, Penrose, Auckland 1061 New
Zealand P +64 9 525 6051