VYNCO 88DP Dimmer Switch Installation Guide

May 15, 2024
VYNCO

VYNCO 88DP Dimmer Switch Installation

VYNCO-88DP-Dimmer-Switch-Installation-product

Specifications

  • Rated Supply Voltage: 220 – 240V AC
  • Rated Frequency: 50Hz
  • Compatible Loads: Dimmable LEDs, Incandescent, Halogen
  • Maximum Load: 300W
  • Minimum Load: 3W
  • Dimming Technology: Internal Protection Safety Compliance
  • Safety Compliance: AS/NZS 60669.2.1:2020 SAA230645

MULTIPLE DIMMERS IN A PLATE – DERATING

No. of Dimmers| Maximum Load per Dimmer
1 Gang| 300W
2 Gang| 250W
3 Gang| 200W

Product Usage Instructions

Safety

Ensure the circuit is safety isolated before installation.
All wiring should be carried out by a licensed/ registered electrician or similarly qualified person wiring and installed according to the AS/NZS 3000 wiring rules.
The 88DP product must be fitted to a wall plate and installed in a suitable enclosure (mounting block or flush box). The input terminals should not be accessible when the product is being used.
The integrated ON/OFF press switch does not isolate the power supply. The power must be switched off at the circuit breaker (MCB) before servicing the Dimmer or Load.

Fitment

Securely press the mech into the switch plate and connect wiring as per the wiring diagram provided.

Compatible Loads

Compatible loads for TE mode include Integral Dimmable LED lamps, Dimmable LED lighting with compatible Electronic Transformers, Incandescent lighting, MV Halogen lamps, and LV Halogen Lighting with Electronic Transformers.

Compatible loads for LE mode (Auto change to LE mode) include Lighting with Iron-core Transformers (Max.50W) and Small motor loads, ceiling sweep fans (Max.50W).

Installation Procedure

  1. Ensure the circuit is safely isolated.
  2. Securely press the mech into the switch plate.
  3. Connect wiring as per the wiring diagram.
  4. Secure the switch plate to a suitable flush or mounting block with the screw fasteners.
  5. Turn on the power and test for correct operation.

Operation

The dimmer operates as an On/Off switch by short press of the Push Button. Press and hold the Push Button to dim up or release and hold to dim down until minimum level.

Warranty

This product is covered by the standard 2 Year Vynco Warranty. Proof of purchase is required. Contact Vynco for details of returns procedure.

Function Default Instructions

Adjust the minimum dimming level to a minimum of 20% brightness. To adjust, with the lights ON, set the minimum brightness level to the required level (minimum 20%), then press the dimmer knob 5 times in quick succession. The push button backlight will flash 3 times to confirm the new setting.

Safety

All wiring should be carried out by a licensed/ registered electrician or similarly qualified person wiring and installed according to the AS/NZS 3000 wiring rules.
The 88DP product must be fitted to a wall plate and installed in a suitable enclosure (mounting block or flush box). The input terminals should not be accessible when the product is being used.
The integrated ON/OFF press switch does not isolate the power supply. The power must be switched off at the circuit breaker (MCB) before servicing the Dimmer or Load.

FITMENT

Indoor use only. Suitable for:

  • Suitable for 1-way and Multi-way dimming and switching.
  • Incandescent lighting: Max load 300W
  • Dimmable LED lighting: Max load 300W
  • Fits all Vynco Switch Plates

COMPATIBLE LOADS

VYNCO-88DP-Dimmer-Switch-Installation-fig-1

NOTE: When connect with IRON-CORE transformers or MOTOR-LOADS, Only Leading Edge mode (LE) could be applied, the TEauto mode can not be used in this case.
Multiple compatible loads can be used as long as the total lamp wattage does not exceed the maximum load rating of the dimmer. Some lamps may exhibit unexpected performance characteristics when cold. Dimming performance should improve after the lamp warms up. Or in case of lamp appears unstable status, it could be changed to LE mode.

INSTALLATION PROCEDURE

  • Isolate the power before installation.
  • Switch power ON only after complete installation and testing of the circuit.

STEP 1. Ensure the circuit is safety isolated.
STEP 2. Securely press the 88DP mech into the Switch plate.
STEP 3. Connect wiring as per the wiring diagram:
STEP 4. Secure switch plate to a suitable flush or mounting block with the screw fasteners.
STEP 5. Turn on power and test for correct operation.
NOTE: The Dimmer must always be connected to the LINE side of the Load.
Do not connect more than one Master Dimmer (88DP) on a circuit. Always use Slave Switches (88SPM) in multi-way installations.
A maximum of 10 Slave Switches can be used on any one circuit.

WIRING DIAGRAMS

One Way Operation

VYNCO-88DP-Dimmer-Switch-Installation-fig-1

OPERATION

The dimmer operates as an On/Off switch by short press of the Push Button. Press and hold the Push Button to dim up or release and hold to dim down until minimum level.
The default settings can be adjusted to suit the installation via the settings below.
Only change the settings at the Master Push Button.

FUNCTION DEFAULT INSTRUCTIONS

A

| Adjust the minimum dimming level. (Note, if the minimum brightness level is set below 20%, the lights will still switch on at 20%)|

20%

| With the lights ON, adjust the minimum brightness to the required level, then press the dimmer knob 5 times in quick succession.

The push button backlight will flash 3 times to confirm that the new

minimum level has been saved.

B| Enable/Disable the push button backlight. (In this mode the push button backlight will always stay on).|

ON

| With the lights ON, press the push button 4 times in quick succession. The push button backlight will flash 3 times to confirm that the backlight has been disabled.

C

|

Clear the minimum dimming level.

|

20%

| With the lights ON, press the push button 7 times in quick succession. The push button backlight will flash 3 times to confirm that the minimum level is now 0%.

Note: A new minimum dimming level is required after clearing, otherwise it will reset to the factory default setting.

D|

Reset all functions to factory defaults.

|

NONE

| With the lights ON, press the push button 9 times in quick succession. The push button backlight will flash 3 times to confirm that the dimmer settings have been changed to factory defaults.

E

| Setting the TE or LE Mode.

BLUE LE Mode (Halogens and small motors) ORANGE TE Mode (LEDs, Incandescent)

|

TEauto

|

With the lights ON, press the push button 6 times in quick succession. The push button backlight will flash 3 times to confirm that the dimmer mode has been changed to LE mode or TE mode.

WARRANTY

This product is covered by the standard 2-Year Vynco Warranty – proof of purchase is required. Please contact Vynco for details of returns procedure.
NOTE: This product contains NO user-serviceable parts.

FAQ

Q: Can I connect more than one Master Dimmer on a circuit?

A: No, only one Master Dimmer should be connected on a circuit. Use Slave Switches in multi-way installations.

Q: What happens if I connect incompatible loads?

A: Connecting incompatible loads may result in unexpected performance characteristics or instability. Ensure to use only compatible loads as specified in the manual.