neptronic TSUB00-100 Networkable Wall Mount Controller Owner’s Manual

August 16, 2024
neptronic

neptronic TSUB00-100 Networkable Wall Mount Controller

Specifications

  • Models: TSUB00-100, TSUB30-100, TSUB60-100, TSUB00-101, TSUB30-101, TSUB60-101, TSUB00-104, TSUB30-104, TSUB60-104, TSUB00-105, TSUB30-105, TSUB60-105
  • Description: Universal wall-mount controller with built-in temperature sensor for fan coil unit or heating/cooling equipment control.
  • Features:
    • Onboard Sensors
    • Network Communication
    • Modbus Support
  • Technical Specifications:
    • Temperature Sensor: Setpoint Range, Control Accuracy, Display Resolution
    • Humidity Sensor: Setpoint Range, Control Accuracy, Display Resolution
    • PIR Motion Sensor: Operating Principle, Detection Angle, Detection Distance, Detection Area
    • Other: Inputs, Outputs, Power supply, Power consumption, Proportional band, Dead band, Operating temperature, Storage temperature, Relative Humidity, Degree of protection of housing, Weight, Dimensions

Installation

Ensure proper wiring to a separate grounded transformer dedicated only to Neptronic products to prevent interference or damage.

Wiring

Follow the terminal description guide for connecting fan analog, power supply, external sources, and communication ports.

Control Setup

Utilize the onboard sensors for temperature, humidity, and motion detection to configure control sequences as needed.

Network Configuration

Set up network communication using Modbus support for seamless integration with other devices.

FAQs

Q: Can I use the controller with heating equipment?
A: Yes, the controller is designed for accurate control of both heating and cooling equipment.

Q: What is the detection range of the PIR motion sensor?
A: The PIR motion sensor has a detection distance of 4m (13ft) with a detection angle covering a wide area.

Q: How do I connect external sensors to the controller?
A: Refer to the terminal description guide for the proper connection of external sensors and power sources.

Description

The TSUB is a universal wall-mount controller with a built-in temperature sensor. The unit is designed for simple and accurate control of a fan coil unit or heating/cooling equipment. Its field configurable algorithms enable versatile implementation of required control sequences.
The controller is available with additional sensors, such as the PIR motion detection and humidity sensor, providing more functionality for the terminal device.
Equipped with an on-board humidity sensor, for accurate humidity control, this comprehensive unit also provides a dehumidification sequence compensated by auto activation of reheat output.

Features
· Fan control: 1, 2 or 3-speed (auto/on), or analog (ECM) · Optional internal/external humidity sensor input for
simple and accurate humidity control · Dehumidification sequence compensated by auto
activation of reheat output · Real time clock (RTC) with 24-hour backup · 7-day programmable schedule · Precise temperature control with configurable PI
(Proportional-Integral) function · Selectable internal or external temperature sensor · Low limit set protection (10°C / 50°F) · Occupancy and night set back (NSB) mode · Select direction on outputs · Select controller’s default display · Multi-level lockable access menu and setpoint · Selectable Fahrenheit or Celsius scale · Option of pulse/floating/on-off output on binary outputs · Internal/external occupancy input · Compressor anti-cycling delay (configurable) · T control (on request)

Onboard Sensors
· Temperature sensor (°C/°F) · Humidity sensor (%RH), select models · PIR motion detection sensor, select models
Network Communication
· BACnet® MS/TP or Modbus communication port (selectable via configuration menu)
· Select MAC address via menu or via network · Automatic baud rate detection
BACnet MS/TP®
· Automatic device instance configuration · Copy & broadcast configuration via menu or via BACnet
to other controllers · BACnet scheduler (up to 6 events per day) · Firmware upgradeable via BACnet · Supports COV (change of value)
Modbus
· Modbus @ 9600, 19200, 38400 or 57600 bps · RTU Slave, 8 bits (configurable parity and stop bits) · Connects to any Modbus master

TSUB-240109

Page | 1

Technical Specifications

Description

Temperature Sensor

Setpoint Range

10ºC to 40ºC [50ºF to 104ºF]

Control Accuracy

Temperature: ±0.4ºC [0.8ºF]

Display Resolution

±0.1ºC [0.2ºF]

Humidity Sensor (select models)

Setpoint Range

10% to 90% RH

Control Accuracy

±3.5% RH

Display Resolution

0.1%

PIR Motion Sensor (select models)

Operating Principle

Passive Infrared (PIR)

Detection Angle

100º

Detection Distance

4m [13ft]

Detection Area

4m (13ft)

100º

Networkable Wall-Mount Controller
Specification and Installation Instructions
TSUB Series

Other
Inputs
Outputs
Power supply
Power consumption
Proportional band
Dead band
Electrical connection
Operating temperature
Storage temperature
Relative Humidity
Degree of protection of housing
Weight
Dimensions: A = 4.88″ | 124mm B = 3.25″ | 83mm C = 1.75″ | 44mm D = 0.96″ | 24mm E = 2.07″ | 53mm F = 2.36″ | 60mm G = 3.28″ | 83mm H = 0.78″ | 20mm

2 Universal Inputs (0-10Vdc, 10K sensor, dry contact)

5 Binary Outputs (OptoFET, 250mA max) 2 Analog Outputs (0-10Vdc, adjustable, 5mA max)

22 to 26 Vac or Vdc 50/60Hz

1 VA max

0.5ºC to 5ºC [1ºF to 9ºF] adjustable (heat/cool/reheat independent)

0.0ºC to 5ºC [0.0ºF to 9ºF] adjustable (heat/cool/reheat independent)

0.8 mm2 [18 AWG] minimum

0ºC to 50ºC [32ºF to 122ºF]

-30ºC to 50ºC [-22ºF to 122ºF]

5 to 95% noncondensing

IP 30 (EN 60529)

135 g. [0.30 lb]

C

PIR Sensor

(Optional)

D

E

A

G

F

B

H

www.neptronic.com

Page | 2

Networkable Wall-Mount Controller
Specification and Installation Instructions
Wiring
We strongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.

JP1 RUN PGM

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 JP3
None
17 120

Terminal Description

Terminals

Fan analog

Analog Option

1-Speed Fan

2-Speed Fan

3-Speed Fan

1 COM

Common

2 24V

24V (power supply)

3 EXT SRC

External power supply

4 N/A

N/A

5 N/A

N/A

6 BO3

select any ramp*

7 BO4

select any ramp*

Fan (speed 3)

8 BO5

select any ramp*

Fan (speed 2)

Fan (speed 2)

9 BO6

select any ramp*

Fan (speed 1)

Fan (speed 1)

Fan (speed 1)

10 BO7 TB1
11 AO2
12 AO3

Fan Speed option · Modulating
0-10Vdc for ECM Motors · Steps of 3,6,9V for 3 Speed

select any ramp select any ramp

select any ramp*

13 COM

Common

14 UI1 15 UI2

Universal Input selection: · 0-10 Vdc (External sensor, humidity, CO2) · 10K Ohm (External sensor, changeover) · Dry Contact**

16 A+

BACnet communication port (A+)

17 B-

BACnet communication port (B-)

  • = select from any of the following ramps:

** = select from any of the following:

· Cooling 1 w/ fan · Cooling 2 w/ fan · Heating 1 w/ fan · Heating 2 w/ fan · Heating 2 without fan

· Cool/Heat 1 w/ fan · COR (changeover) w/ fan · Humidify w/ fan · CO2 Alarm · Off

· Off · Override · Flow Switch · Local/Remote Selector Switch · Overheat

· Dirty Filter · Window & Door Contacts · Occupancy & NSB Sensor · Changeover Input

www.neptronic.com

Page | 3

Networkable Wall-Mount Controller
Specification and Installation Instructions

Wiring – 2 Pipe Terminal Description Details

Analog

On/Off

Terminals

Fan analog

1-Speed Fan

2-Speed Fan

3-Speed Fan Fan analog

1-Speed Fan

2-Speed Fan

1 COM

Common

Common

2 24V

24V (power supply)

24V (power supply)

3 EXT SRC

External power supply

External power supply

4 N/A

N/A

N/A

5 N/A

N/A

N/A

6 BO3

select any ramp*

On/Off Valve (COr)

7 BO4

select any ramp*

Fan (speed 3)

select any ramp*

8 BO5

select any ramp*

Fan (speed 2)

Fan (speed 2)

select any ramp*

Fan (speed 2)

9 BO6

select any ramp*

Fan (speed1)

Fan (speed1)

Fan (speed1)

select any ramp*

Fan (speed1)

Fan (speed1)

10 BO7

Heating Ramp 1 (Hr1)

Heating Ramp 1 (Hr1)

3-Speed Fan
Fan (speed 3)
Fan (speed 2)
Fan (speed1)

11 AO2

Fan

Analog Local Reheat (HR1)

Fan

Analog Local Reheat (HR1)

12 AO3 13 COM 14 UI1
15 UI2
16 A+ 17 B-

Changeover with fan (COr) Common
Changeover Input (SENs) Occupancy/Night Setback (OCC/nSb) External Temperature Sensor (t10.0)
External Humidity Sensor (HU) BACnet communication port (A+) BACnet communication port (B-)

select any ramp* Common
Changeover Input (SENs) Occupancy/Night Setback (OCC/nSb) External Temperature Sensor (t10.0)
External Humidity Sensor (HU) BACnet communication port (A+) BACnet communication port (B-)

Floating

Terminals

Fan analog

1-Speed Fan

2-Speed Fan

3-Speed Fan

1 COM

Common

2 24V

24V (power supply)

3 EXT SRC

External power supply

4 N/A

N/A

5 N/A

N/A

6 BO3

Floating Valve (COr)

7 BO4

select any ramp*

Fan (speed 3)

8 BO5

select any ramp*

Fan (speed 2)

Fan (speed 2)

9 BO6

select any ramp*

Fan (speed1)

Fan (speed1)

Fan (speed1)

10 BO7

Floating Valve (COr)

11 AO2

Fan

Analog Local Reheat (HR1)

12 AO3

select any ramp*

13 COM

Common

14 UI1

Changeover Input (SENs)

15 UI2

Occupancy/Night Setback (OCC/nSb) External Temperature Sensor (t10.0)

External Humidity Sensor (HU)

16 A+

BACnet communication port (A+)

17 B-

BACnet communication port (B-)

  • = select from any of the following ramps:

= Fan Speed Option:

· Cooling 1 w/ fan · Cooling 2 w/ fan · Heating 1 w/ fan · Heating 2 w/ fan · Heating 2 without fan

· Cool/Heat 1 w/ fan · COR (changeover) w/ fan · Humidify w/ fan · CO2 Alarm · Off

· Modulating: 0-10Vdc for ECM Motors · Steps of 3,6,9V for 3 Speed

www.neptronic.com

Page | 4

Networkable Wall-Mount Controller
Specification and Installation Instructions

Wiring – 4 Pipe Terminal Description Details

Cool: Analog

Terminals

Heat: Analog

1-Speed Fan 2-Speed Fan 3-Speed Fan Fan Analog

Cool: On/Off Heat: On/Off
1-Speed Fan 2-Speed Fan 3-Speed Fan

1 COM

Common

Common

2 24V

24V (power supply)

24V (power supply)

3 EXT SRC

External power supply

External power supply

4 N/A

N/A

N/A

5 N/A

N/A

N/A

6 BO3

select any ramp*

On/Off Heating Valve (Hr1)

7 BO4

select any ramp*

Fan (speed 3)

select any ramp*

Fan (speed 3)

8 BO5

select any ramp*

Fan (speed 2)

Fan (speed 2)

select any ramp*

Fan (speed 2)

Fan (speed 2)

9 BO6

Fan (speed1)

Fan (speed1)

Fan (speed1)

select any ramp*

Fan (speed1)

Fan (speed1)

Fan (speed1)

10 BO7

select any ramp*

On/Off Cooling Valve (Cr1)

11 AO2

Heating Valve (Hr1)

Fan Speed option

Fan Speed option

select any ramp*

12 AO3

Cooling Valve (Cr1)

Heating Ramp 1 (Hr1)

13 COM

Common

Common

14 UI1

Occupancy/Night Setback (OCC/nSb)

Occupancy/Night Setback (OCC/nSb)

15 UI2

External Temperature Sensor (t10.0) External Humidity Sensor (HU)

External Temperature Sensor (t10.0) External Humidity Sensor (HU)

16 A+

BACnet communication port (A+)

BACnet communication port (A+)

17 B-

BACnet communication port (B-)

BACnet communication port (B-)

  • = select from any of the following ramps:

= Fan Speed Option:

· Cooling 1 w/ fan · Cooling 2 w/ fan · Heating 1 w/ fan · Heating 2 w/ fan · Heating 2 without fan

· Cool/Heat 1 w/ fan · COR (changeover) w/ fan · Humidify w/ fan · CO2 Alarm · Off

· Modulating: 0-10Vdc for ECM Motors · Steps of 3,6,9V for 3 Speed

Power Supply for Binary Outputs
Using Internal Power Supply for BOs

Using External Power Supply for BOs

COM 1 24V 2 EXT SRC 3

24V

Line Voltage

Jumper

COM 1 24V 2 EXT SRC 3

24V

Line Voltage

To External (Secondary) Power Supply

www.neptronic.com

Page | 5

Interface

Networkable Wall-Mount Controller
Specification and Installation Instructions

AM PM
%RH CF

Network Communication

Alarm Status

°C °F %RH

ºC: Celsius Scale ºF: Fahrenheit Scale %RH: Humidity

Heating

User Lock
Energy Saving Mode (NSB/OCC)

Programming Mode (Technician Setting)
AM PM Time

A

Automatic Mode

Cooling

Fan

Humidify/ De-humidify

Mounting Instructions
CAUTION: Remove power to avoid a risk of malfunction.
A. Remove the captive screw that’s holding the base and the front cover of the unit together. B. Lift the front cover of the unit to separate it from the base. C. Pull all wires through the holes in the base. D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections. E. Mount the control module on the base and secure using the screw.

A

B

C

D

E

Do not use the supplied screws to mount the unit to an electric box or an equivalent device. The supplied screws are only suitable for mounting the unit to the wall. Ensure to use the appropriate screws for any other application. Tighten by hand only and ensure not to overtighten the screws.
Programming Mode
The Mode Selector jumper JP1 must be set to the PGM position (Programming Mode). Refer to the Wiring section on page 3. To exit, set the jumper back to the RUN position (Operation Mode). Advance to the next or return to the previous setting in order to save a changed value.

Setting Value Advance to next setting Change value Return to previous setting
www.neptronic.com

Page | 6

Networkable Wall-Mount Controller
Specification and Installation Instructions

Symbols used in this Manual

Icon

Description

Icon

Temperature

Description Heating

Icon

Description Cooling

Icon

Description Humidity

Fan

Analog Output 2

Analog Output 3

Time

Binary Output 3

Binary Output 4

Binary Output 5

Binary Output 6

BO7

Binary Output 7

UI1

Universal Input 1

UI2

Universal Input 2

Night Set Back

Occupancy

Communication

Valve

Lock

Carbon Dioxide

Setpoint and User Control

Range: Offset: Increment:

0ºC to 50ºC Max. ± 5ºC 0.1ºC

[32ºF to 122ºF] [± 9ºF] [0.2ºF]

Compare the displayed temperature reading with a known value from a thermometer or other temperature sensing device. To offset or calibrate the sensor, use the arrow buttons to set the desired temperature reading. This is useful for controllers installed in areas where the temperature read is slightly different than the room’s actual temperature. For example, a controller placed right under the air diffuser.

Default: Range: Increment:

15ºC 10ºC to 40ºC 0.5ºC

[59ºF] [50ºF to 104ºF] [1.0ºF]

In Operation mode, you cannot decrease the setpoint to less than the value set as the minimum user point. The minimum value
is restricted by the maximum value set at Step 3, “Maximum User Setpnt”. In other words, the value that is set as the minimum cannot be greater than the maximum value.

Default: Range: Increment:

30ºC 10ºC to 40ºC 0.5ºC

[86ºF] [50 to 104ºF] [1.0ºF]

In Operation mode, you cannot increase the setpoint to more than the value set as the maximum user point. The maximum
value is restricted by the minimum value set at Step 2, “Minimum User Setpnt”. In other words, the value that is set as the maximum cannot be less than the minimum value.

Default: Range:

No (Unlocked) No (Unlocked), yES (Locked)

If set to No, the user setpoint option is not locked and the user can adjust the desired temperature setpoint. If set to yES, the user setpoint option is locked and the user cannot set the desired temperature setpoint. A lock symbol appears to indicate that the setpoint is locked.

Default: Range: Increment:

22ºC 10ºC to 40ºC 0.5ºC

[72ºF] [50ºF to 104ºF] [1.0ºF]

Set the desired temperature setpoint within the defined range. If the setpoint option was locked at Step 4, “User Setpnt locked”, a lock symbol is displayed. The setpoint value is restricted by the minimum at Step 2, “Minimum User Setpnt” and maximum at Step 3, “Maximum User Setpnt” values. In other words, the setpoint should be within the minimum and maximum setpoint range.

www.neptronic.com

Page | 7

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range:

Auto (Automatic) Auto (Automatic), HEAt (Heating Only), COOL (Cooling Only), On (Cooling or Heating), CLHt (Automatic only)

Select the control mode that you want to authorize to the user. To authorize all the available modes, select Auto (Automatic Mode). The cooling and heating symbols are also displayed. The selection made at this step determines the options available via the Control Mode (see page 35).

Default: Range:

yES (Enable) yES (Enable), No (Disable)

If set to yES, the user can set the unit to “Off” via the Control Mode (see page 35). If set to No, the “Off” selection does not appear in the Control Mode.

Default: Range:

t – Hu %RH °C (temperature, humidity, and cooling heating demand) t – Hu %RH °C (temperature, humidity), StP %RH °C (temperature, humidity setpoint), OFF (no display), t – Hu %RH °C (temperature, humidity, and cooling heating demand), StP %RH °C (temperature, humidity setpoint, and cooling
heating demand)

Select the desired information to appear on the display.

Keypad Lock Settings

Default: Range:

No (Disable) yES (Enable), No (Disable)

If set to yES, the button is locked and cannot be used by the user. If set to No, the by the user.

button is unlocked and can be used

Default: Range:

No (Disable) yES (Enable), No (Disable)

If set to yES, the used by the user.

button is locked and cannot be used by the user. If set to No, the

button is unlocked and can be

11. “Keypad Arrows Locked”

Default: Range:

No (Disable) yES (Enable), No (Disable)

If set to yES, the and buttons are locked and cannot be used by the user. If set to No, the and buttons are unlocked and can be used by the user.

Valve Settings

Default: Range:

1″ 1/2″, 3/4″, 1″

Select the desired valve size in inches for the 6-way valve from the available options.

Analog Output 2 (AO2)

Default: Range:

Hr1 (Heating Ramp 1) Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, 6w, dto, VFdt, VFdP, FAN, OFF, COr

Select the desired signal from the available options.
· Cr1 (Cooling Ramp 1) or Cr2 (Cooling Ramp 2). The Cr1 and Cr2 ramps are used for cooling. If selected, the controller performs cooling based on the cooling proportional, integral, and dead band values.
· Hr1, Hr2 (heat with fan), or Hr2 (heat without fan). The Hr1 and Hr2 ramps are used for heating. If selected, the controller performs heating based on the heating proportional, integral, and dead band values.

www.neptronic.com

Page | 8

Networkable Wall-Mount Controller
Specification and Installation Instructions

· CH1 (Cooling and Heating). If selected, the controller performs cooling regularly. If another output is set to heat, it performs heating regularly.

· HU (Humidify). If selected, the controller modulates the output based on the humidify demand.

· CO2 (Carbon dioxide). If selected, the controller will activate or deactivate the output based on carbon dioxide levels.

· 6W (6-way Valve). If selected, the controller will modulate the 6-way valve depending on the heating or cooling demand.
· dto (Delta temperature control). If selected, the controller will modulate the T control based on the inlet and outlet temperature of the water inside the fan coil unit.

· VFdt (VFD Temp Loop). If selected, the controller will modulate the VFD fan based on the selected temperature input.

· VFdP (VFD Pressure Loop). If selected, the controller will modulate the static pressure based on the reading and the pressure setpoint.

· FAN. If selected, the controller modulates the output based on the Fan demand.

· OFF. If selected, the controller does not use the output.

· COr (Changeover). If selected, the controller will modulate heating and cooling, as appropriate.

If you select OFF, Steps 14 to 18 will not be available.

If you select VFdt or VFdP, Steps 26 to 32 will not be available.

If you select CH1, Step 25, “Minimum Cool 1 Heat 1 Percent” will be available.

If you select FAN, Step 26, “Fan Spd Signal” will not be available.

Cr1

Cr2

Hr1

Hr2 (with fan)

Hr2 (without fan)

CH1

HU

CO2

6W

dto

VFdt

VFdP

FAN

OFF

COr

Default: Range: Increment:

0.0 Volt 0.0 to 10.0 Volts 0.1 Volt

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13,

). Select the desired minimum voltage

(“zero” value) for the AO2 ramp. The minimum value is restricted by the maximum value at Step 15,

. In other

words, the minimum value should be less than the maximum value.

Default: Range: Increment:

10.0 Volts 0.0 to 10.0 Volts 0.1 Volt

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13,

). Select the desired maximum voltage

(“span” value) for the AO2 ramp. The maximum value is restricted by the minimum value at Step 14,

. In

other words, the maximum value should not be less than the minimum value.

Default: Range:

MIN (Minimum voltage) MIN (Minimum voltage), OFF (0 Volt)

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13, “AO2 Ramp”). Set the analog output voltage when the controller is turned off. When set to MIN, the output will remain at the minimum voltage level defined by (Step 14, “AO2 Minimum Voltage”). When set to OFF, the output will remain at 0V.

www.neptronic.com

Page | 9

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range:

dir (Direct) dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13, to either Direct (e.g. 0 to 10Vdc), or Reverse (e.g. 10 to 0Vdc).

). Set the direction of the analog signal

Default: Range:

ANLg (Analog Output) ANLg (Analog Output), OnOF (On/Off), PuLs (Pulsing)

This option does not appear if the signal ramp for AO2 is set to OFF (Step 13, Analog Output, On/Off or Pulsing.

). Set the signal type for AO2 to either

Analog Output 3 (AO3)

Default: Range:

Hr1 (Heating Ramp 1) Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, 6W, dto, OFF, COr

Select the desired signal from the available options. The AO2 input signal has priority over AO3.

· Cr1 (Cooling Ramp 1) or Cr2 (Cooling Ramp 2). The Cr1 and Cr2 ramps are used for cooling. If selected, the controller performs cooling based on the cooling proportional, integral, and dead band values.

· Hr1, Hr2 (heat with fan), or Hr2 (heat without fan). The Hr1 and Hr2 ramps are used for heating. If selected, the controller performs heating based on the heating proportional, integral, and dead band values.

· CH1 (Cooling and Heating). If selected, the controller performs cooling regularly. If another output is set to heat, it performs heating regularly.

· HU (Humidify). If selected, the controller modulates the output based on the humidify demand.

· CO2 (Carbon dioxide). If selected, the controller will activate or deactivate the output based on carbon dioxide levels.

· 6W (6-way Valve). If selected, the controller will modulate the 6-way valve depending on the heating or cooling demand.
· dto (Delta temperature control). If selected, the controller will modulate the T control based on the inlet and outlet temperature of the water inside the fan coil unit.

· OFF. If selected, the controller does not use the output.

· COr (Changeover). If selected, the controller will modulate heating and cooling, as appropriate.

If you select OFF, Steps 20 to 24 will not be available.

If you select CH1, Step 25, “Minimum Cool 1 Heat 1 Percent” will be available.

If you select FAN, Step 26, “Fan Spd Signal” will not be available.

Cr1

Cr2

Hr1

Hr2 (with fan)

Hr2 (without fan)

CH1

HU

CO2

6w

dto

OFF

Cor

Default: Range: Increment:

0.0 Volt 0.0 to 10.0 Volts 0.1 Volt

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19,

). Select the desired minimum voltage

(“zero” value) for the AO3 ramp. The minimum value is restricted by the maximum value at Step 21,

. In other

words, the minimum value should be less than the maximum value.

www.neptronic.com

Page | 10

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range: Increment:

10.0 Volts 0.0 to 10.0 Volts 0.1 Volt

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19,

). Select the desired maximum voltage

(“span” value) for the AO3 ramp. The maximum value is restricted by the minimum value at Step 20, “AO3 Minimum Voltage”.

In other words, the maximum value should not be less than the minimum value.

Default: Range:

MIN (Minimum voltage) MIN (Minimum voltage), OFF (0 Volt)

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19, “AO3 Ramp”). Set the analog output voltage when the controller is turned off. When set to MIN, the output will remain at the minimum voltage level defined by Step 20,
“AO3 Minimum Voltage”. When set to OFF, the output will remain at 0V.

Default: Range:

dir (Direct) dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19, to either Direct (e.g. 0 to 10Vdc), or Reverse (e.g. 10 to 0Vdc).

). Set the direction of the analog signal

Default: Range:

ANLg (Analog Output) ANLg (Analog Output), OnOF (On/Off), PuLs (Pulsing)

This option does not appear if the signal ramp for AO3 is set to OFF (Step 19, Analog Ouptut, On/Off or Pulsing.

). Set the signal type for AO3 to either

Default: Range: Increment:

0 % 0 to 100% 5 %

This option appears if you have selected CH1 at Step 13, “AO2 Ramp” or at Step 19,

. Set the percentage at which

the controller sets the CH1 output during heating, provided another output has also been set to heating.

Fan Settings

Default: Range:

3 1, 2, 3

This option does not appear if you have selected FAN at Step 13, The fan symbol is also displayed.

. Select the desired number of fan speed contacts.

Default: Range:

Std (Standard) AdV (Advanced), Std (Standard)

Select between the Standard (Neptronic) and Advanced (OE1) fan speed specifications. The fan

symbol is also displayed.

Default: Range:

No (Disable) yES (Enable), No (Disable)

This option appears only if you have selected Adv at Step 27,

. Select to enable or disable the fan control

mode option. If you select No, the Fan Speed Selection Mode option is not available in Control Mode. The fan symbol is

also displayed.

Default: Range:

No (Disable) yES (Enable), No (Disable)

www.neptronic.com

Page | 11

Networkable Wall-Mount Controller
Specification and Installation Instructions

Select to enable or disable the fan display information. If you select Yes, the Fan demand (fan icon) does not appear on the display and the Fan Speed Selection Mode is disabled. The fan symbol is also displayed.

Default: Range:

yES (Enable) yES (Enable), No (Disable)

If set to yES, the user can set the fan speed to “Automatic” via the Fan Speed Selection Mode (see page 36). If set to No, the “Automatic” speed does not appear in the Fan Speed Selection Mode. The fan symbol is also displayed.
If you select yES, Step 31 “Fan Auto Timeout Seconds” will be available.
If you select No, Step 31 “Fan Auto Timeout Seconds” will not be available.

Default: Range: Increment:

120 seconds 0 to 255 seconds 1 second

This option appears only if you have selected yES at Step 30, delay when there is no demand. The fan symbol is also displayed.

. Select the desired value for the automatic shutoff

Default: Range: Increment:

0 second 0 to 255 seconds 1 second

Select the desired damping factor value for the fan. The fan

symbol is also displayed.

Binary Output 3 (BO3)

Default: Range:

Hr1 (Heating Ramp 1) Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr

Select the desired ramp from the available options.

· Cr1 (Cooling Ramp 1) or Cr2 (Cooling Ramp 2). The Cr1 and Cr2 ramps are used for cooling. If selected, the controller performs cooling based on the cooling proportional, integral, and dead band values.

· Hr1, Hr2 (heat with fan), or Hr2 (heat without fan). The Hr1 and Hr2 ramps are used for heating. If selected, the controller performs heating based on the heating proportional, integral, and dead band values.

· CH1 (Cooling and Heating). If selected, the controller performs cooling regularly. If another output is set to heat, it performs heating regularly.

· HU (Humidify). If selected, the controller modulates the output based on the humidify demand.

· CO2 (Carbon dioxide). If selected, the controller will activate or deactivate the output based on carbon dioxide levels.

· OFF. If selected, the controller does not use the output.

· COr (Changeover). If selected, the controller will modulate heating and cooling, as appropriate.

If you select OFF, Steps 34 to 39 will not be available.

Cr1

Cr2

Hr1

Hr2 (with fan)

Hr2 (without fan)

CH1

HU

CO2

OFF

COr

www.neptronic.com

Page | 12

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range:

OnOF (On/Off) tPm (Pulsing), OnOF (On/Off), FLot (Floating)

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, “BO3 Ramp”). Select the signal type for BO3 to either Pulsing, On/Off or Floating.

Default: Range: Increment:

100 seconds 15 to 250 seconds 5 seconds

This option only appears if the signal type for BO3 is set to FLot (Step 34, “BO3 Signal Type”). Set the time required for the valve actuator to complete a stroke.

Default: Range: Increment:

50% of the demand 15 to 80% 1%

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, “BO3 Ramp”) and if the signal type for BO3 is
set to either tPm or FLot (Step 34, “BO3 Signal Type”). Select the percentage at which you want BO3 to close (at % of demand of the ramp selected at Step 33, “BO3 Ramp”).

Default: Range: Increment:

25% of the demand 0 to (BO3 Close)-4% 1%

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, “BO3 Ramp”) and if the signal type for BO3 is
set to either tPm or FLot (Step 34, “BO3 Signal Type”). Select the percentage at which you want BO3 to open (at % of demand of the ramp selected at Step 33, “BO3 Ramp”).

Default: Range:

dir (Direct) dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, “BO3 Ramp”) and if the signal type for BO3 is set to either tPm or FLot (Step 34, “BO3 Signal Type”). Set the direction of the binary signal to either Direct or Reverse.

Default: Range: Increment:

0 minute 0 to 15 minutes 1 minute

This option does not appear if the signal ramp for BO3 is set to OFF (Step 33, “BO3 Ramp”) and if the signal type for BO3 is set to either tPm or FLot (Step 34, “BO3 Signal Type”). Select the closing delay for BO3 output.

Binary Output 4 (BO4)
The Binary Output 4 settings appear only if you have selected either fan speed 1 or 2 at Step 26, “Fan Spd Signal” or VFdP, VFdt or FAN at Step 13, “AO2 Ramp”.

Default: Range:

OFF Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr

Select the desired ramp from the available options. Same as BO3 options. If you select OFF, Steps 41 to 45 will not be available.

Default: Range:

OnOF (On/Off) tPm (Pulsing), OnOF (On/Off)

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40,”BO4 Ramp”). Select the signal type BO4 to either Pulsing or On/Off.

www.neptronic.com

Page | 13

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range: Increment:

20% of the demand 15 to 80% 1%

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40,”BO4 Ramp”) and if the signal type for BO4 is set
to tPm (Step 41, “BO4 Signal Type”). Select the percentage at which you want BO4 to close (at % of demand of the ramp selected at Step 40,”BO4 Ramp”).

Default: Range: Increment:

0% of the demand 0 to (BO4 Close)-4% 1%

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40,”BO4 Ramp”) and if the signal type for BO4 is set
to tPm (Step 41, “BO4 Signal Type”). Select the percentage at which you want BO4 to open (at % of demand of the ramp selected at Step 40,”BO4 Ramp”).

Default: Range:

dir (Direct) dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40,”BO4 Ramp”) and if the signal type for BO4 is set to tPm (Step 41, “BO4 Signal Type”). Set the direction of the binary signal to either Direct or Reverse.

Default: Range: Increment:

0 minute 0 to 15 minutes 1 minute

This option does not appear if the signal ramp for BO4 is set to OFF (Step 40,”BO4 Ramp”) and if the signal type for BO4 is set to tPm (Step 41, “BO4 Signal Type”). Select the closing delay for BO4 output.

Binary Output 5 (BO5)
The Binary Output 5 settings appear only if you have selected either fan speed 1 at Step 26, “Fan Spd Signal” or VFdP, VFdt or FAN at Step 13, “AO2 Ramp”.

Default: Range:

OFF Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr

Select the desired ramp from the available options. Same as BO3 options. If you select OFF, Steps 47 to 51 will not be available.

Default: Range:

OnOF (On/Off) tPm (Pulsing), OnOF (On/Off)

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, “BO5 Ramp”). Select the signal type for BO5 to either Pulsing or On/Off.

Default: Range: Increment:

20% of the demand 15 to 80% 1%

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, “BO5 Ramp”) and if the signal type for BO5 is
set to tPm (Step 47, “BO5 Signal Type”). Select the percentage at which you want BO5 to close (at % of demand of the ramp selected at Step 46, “BO5 Ramp”).

Default: Range: Increment:

0% of the demand 0 to (BO5 Close)-4% 1%

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, “BO5 Ramp”) and if the signal type for BO5 is
set to tPm (Step 47, “BO5 Signal Type”). Select the percentage at which you want BO5 to open (at % of demand of the ramp selected at Step 46, “BO5 Ramp”).

www.neptronic.com

Page | 14

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range:

dir (Direct) dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, “BO5 Ramp”) and if the signal type for BO5 is set to tPm (Step 47, “BO5 Signal Type”). Set the direction of the binary signal to either Direct or Reverse.

Default: Range: Increment:

0 minute 0 to 15 minutes 1 minute

This option does not appear if the signal ramp for BO5 is set to OFF (Step 46, “BO5 Ramp”) and if the signal type for BO5 is set to tPm (Step 47, “BO5 Signal Type”). Select the closing delay for BO5 output.

Binary Output 6 (BO6)

The Binary Output 6 settings appear only if you have selected either FAN, VFdt or VFdP at Step 13,

.

Default: Range:

OFF Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, 6w, dto, VFdt, VFdP, OFF, COr

Select the desired ramp from the available options. Same as BO3 options. The VFdt and VFdP options are available only if you have selected them at Step 13, “AO2 Ramp”.

If you select OFF, Steps 53 to 57 will not be available.

· 6W (6-way Valve). If selected, the controller will modulate the 6-way valve depending on the heating or cooling demand.
· dto (Delta temperature control). If selected, the controller will modulate the T control based on the inlet and outlet temperature of the water inside the fan coil unit.

· VFdt (VFD Temp Loop). If selected, the controller will modulate the VFD fan based on the selected temperature input.

· VFdP (VFD Pressure Loop). If selected, the controller will modulate the static pressure based on the reading and the pressure setpoint.

Default: Range:

OnOF (On/Off) tPm (Pulsing), OnOF (On/Off)

This option does not appear if the signal ramp for BO6 is set to OFF (Step 52, “BO6 Ramp”). Select the signal type for BO6 to either Pulsing or On/Off.

Default: Range: Increment:

20% of the demand 15 to 80% 1%

This option does not appear if the signal ramp for BO6 is set to OFF ((Step 52, “BO6 Ramp”) and if the signal type for BO6 is
set to tPm (Step 53, “BO6 Signal Type”). Select the percentage at which you want BO6 to close (at % of demand of the ramp selected at (Step 52, “BO6 Ramp”).

Default: Range: Increment:

0% of the demand 0 to (BO6 Close)-4% 1%

This option does not appear if the signal ramp for BO6 is set to OFF ((Step 52, “BO6 Ramp”) and if the signal type for BO6 is
set to tPm (Step 53, “BO6 Signal Type”). Select the percentage at which you want BO6 to open (at % of demand of the ramp selected at (Step 52, “BO6 Ramp”).

Default: Range:

dir (Direct) dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO6 is set to OFF ((Step 52, “BO6 Ramp”) and if the signal type for BO6 is set to tPm (Step 53, “BO6 Signal Type”). Set the direction of the binary signal to either Direct or Reverse.

www.neptronic.com

Page | 15

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range: Increment:

0 minute 0 to 15 minutes 1 minute

This option does not appear if the signal ramp for BO6 is set to OFF ((Step 52, “BO6 Ramp”) and if the signal type for BO6 is set to tPm (Step 53, “BO6 Signal Type”p). Select the closing delay for BO6 output.

Binary Output 7 (BO7)
The Binary Output 7 settings do not appear if the BO3 signal type is set to FLot at Step 34, “BO3 Signal Type”.

Default: BO7 Range:

OFF Cr1, Cr2, Hr1, Hr2 (heat with fan), Hr2 (heat without fan), CH1, HU, CO2, OFF, COr

Select the desired ramp from the available options. Same as BO3 options. If you select OFF, Steps 59 to 63 will not be available.

Default: BO7 Range:

OnOF (On/Off) tPm (Pulsing), OnOF (On/Off)

This option does not appear if the signal ramp for BO7 is set to OFF (Step 58, “BO7 Ramp”). Select the signal type for BO7 to either Pulsing or On/Off.

Default: BO7 Range:
Increment:

20% of the demand 15 to 80% 1%

This option does not appear if the signal ramp for BO7 is set to OFF (Step 58, “BO7 Ramp”) and if the signal type for BO7 is set to tPm (Step 59, “BO7 Signal Type”). Select the percentage at which you want BO7 to close (at % of demand of the ramp selected at Step 58, “BO7 Ramp”).

Default:

0% of the demand

BO7 Range:

0 to (BO6 Close)-4%

Increment: 1%

This option does not appear if the signal ramp for BO6 is set to OFF (Step 58, “BO7 Ramp”) and if the signal type for BO7 is set to tPm (Step 59, “BO7 Signal Type”). Select the percentage at which you want BO7 to open (at % of demand of the ramp selected at Step 58, “BO7 Ramp”).

Default: BO7 Range:

dir (Direct) dir (Direct), rEV (Reverse)

This option does not appear if the signal ramp for BO7 is set to OFF (Step 58, “BO7 Ramp”) and if the signal type for BO7 is set to tPm (Step 59, “BO7 Signal Type”). Set the direction of the binary signal to either Direct or Reverse.

Default: BO7 Range:
Increment:

0 minute 0 to 15 minutes 1 minute

This option does not appear if the signal ramp for BO7 is set to OFF (Step 58, “BO7 Ramp”) and if the signal type for BO7 is set to tPm (Step 59, “BO7 Signal Type”). Select the closing delay for BO7 output.

Proportional and Deadband Settings

Default: Range: Increment:

2.0ºC 0.5ºC to 5.0ºC 0.5ºC

[4ºF] [1ºF to 9ºF] [1ºF]

Select the desired proportional band value of the changeover ramp. The cooling

and heating

symbols are also displayed.

www.neptronic.com

Page | 16

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default:

0.3ºC

Range:

0.0ºC to 5.0ºC

Increment: 0.1ºC

[0.6ºF] [0ºF to 9ºF] [0.2ºF]

Select the desired dead band value of the changeover ramp. The cooling

and heating

symbols are also displayed.

Default:

2.0ºC

Range:

0.5ºC to 5.0ºC

Increment: 0.5ºC

[4ºF] [1ºF to 9ºF] [1ºF]

Select the desired proportional band value of the heating ramp 1. The heating

symbol is also displayed.

Default:

0.3ºC

Range:

0.0ºC to 5.0ºC

Increment: 0.1ºC

[0.6ºF] [0ºF to 9ºF] [0.2ºF]

Select the desired dead band value of the heating ramp 1. The heating

symbol is also displayed.

Default:

2.0ºC

Range:

0.5ºC to 5.0ºC

Increment: 0.5ºC

[4ºF] [1ºF to 9ºF] [1ºF]

Select the desired proportional band value of the heating ramp 2. The heating

symbol is also displayed.

Default:

0.3ºC

Range:

0.0ºC to 5.0ºC

Increment: 0.1ºC

[0.6ºF] [0ºF to 9ºF] [0.2ºF]

Select the desired dead band value of the heating ramp 2. The heating

symbol is also displayed.

Default: Range: Increment:

2.0ºC 0.5ºC to 5.0ºC 0.5ºC

[4ºF] [1ºF to 9ºF] [1ºF]

Select the desired proportional band value of the cooling ramp 1. The cooling

symbol is also displayed.

Default: Range: Increment:

0.3ºC 0ºC to 5.0ºC 0.1ºC

[0.6ºF] [0ºF to 9ºF] [0.2ºF]

Select the desired dead band value of the cooling ramp 1. The cooling

symbol is also displayed.

Default: Range: Increment:

2.0ºC 0.5ºC to 5.0ºC 0.5ºC

[4ºF] [1ºF to 9ºF] [1ºF]

Select the desired proportional band value of the cooling ramp 2. The cooling

symbol is also displayed.

Default:

0.3ºC

Range:

0.0ºC to 5.0ºC

Increment: 0.1ºC

[0.6ºF] [0ºF to 9ºF] [0.2ºF]

Select the desired dead band value of the cooling ramp 2. The cooling

symbol is also displayed.

Default: Range: Increment:

2 minutes 0 to 15 minutes 1 minute

To protect the compressor, set the delay in minutes before activating or reactivating the cooling output. The cooling is also displayed.

symbol

www.neptronic.com

Page | 17

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default:

0 seconds

Range:

0 to 250 seconds

Increment: 5 seconds

Set the desired value for heating integration factor compensation. The heating

symbol is also displayed.

Default:

0 seconds

Range:

0 to 250 seconds

Increment: 5 seconds

Set the desired value for cooling integration factor compensation. The cooling

symbol is also displayed.

Default: Range: Increment:

0 minutes 0 to 120 minutes 1 minute

Time required in minutes before a changeover can take place. The cooling

and heating

symbols are also displayed.

Universal Input 1 (UI1)

Default: UI1 Range:

OFF OFF, t10.0, SENs, noCL, noHt, OAS, t10V, CO2, OCC, nSb, oVrd, win, door, dFt, FLS, oVht, SEL, FrFb, HU, P10V, t012, dt1t, dt1u, dt0t, dt0u

Select the input signal type for UI1(Universal Input 1).

· OFF. If selected, the controller does not use the input.
· t10.0. If selected, the controller uses a 10k type III external temperature sensor. If you select t10.0, Step 88, will be available.

· SENs. If selected, heating mode activates when the temperature read by the external sensor is above the Changeover

Setpoint and cooling mode activates when the temperature read by the external sensor is below the Changeover Setpoint.

If you select SENs, Step 89,

will be available.

· NoCL. If selected, the heating mode activates when the contact is closed and cooling mode activates when the contact is opened.

· NoHt. If selected, the cooling mode activates when the contact is closed and heating mode activates when the contact is opened.
· OAS. If selected, the controller uses a 10k type III outside air sensor. Note that the temperature read cannot be used as the control temperature.

· t10v. If selected, the controller uses a 0 to 10 Vdc external temperature sensor. If you select t10v, Step 79,

, 86,

, 87,

, 88,

will be available.

· CO2. If selected, the controller uses a 0 to 10 Vdc CO2 sensor. If you select CO2, Step 90, available.

will be

· OCC. If selected, the controller activates the occupancy status.

· nSb. If selected, the controller activates the night set back status.

· oVrd. If selected, the controller activates an alarm to indicate that there has been an override and the controller is forced into OFF mode.

· win. If selected, the controller activates an alarm to indicate that the window is open. If you select win, Steps 106,

and 107,

will be available.

· door. If selected, the controller activates an alarm to indicate that the door is open. If you select door, Steps 108,

and 109,

will be available.

· dFt. If selected, the controller activates an alarm to indicate that the filter is dirty. · FLS. If selected, the controller activates an alarm to indicate that the airflow is absent. The controller shuts off all outputs. · oVht. If selected, the controller activates an alarm to indicate that the heating equipment has overheated. The controller
shuts off the heating outputs. · SEL. If selected, the controller activates the Local mode. The controller shuts off fan outputs. · FrFb. If selected, the controller senses the pulse feedback of the ECM motor. · HU. If selected, the controller activates the humidity mode. · P10V (Pressure 0-10V). If selected, the controller uses a 0 to 10Vdc pressure static sensor. If you select P10V, Step 79,
“UI1 Minimum Voltage” and Step 93, “Pressur Maximum Range” will be available.

www.neptronic.com

Page | 18

Networkable Wall-Mount Controller
Specification and Installation Instructions

· t012 (Extern Temp TT012). If selected, the controller uses a 10k type 24 external temperature sensor. If you select t012,

Step 88,

will be available.

· dt1t (Delta Temp Inlet 10K). If selected, the controller uses a 10K type 3 temperature sensor. The controller selects this temperature as the inlet temperature in the T control mode.

· dt1u (Delta Temp Outlet 0-10V). If selected, the controller uses a 0 to 10 Vdc temperature sensor. The controller selects this temperature as the inlet temperature in the T control mode.

· dt0t (Delta Temp Outlet 10K). If selected, the controller uses a 10K type 3 temperature sensor. The controller selects this temperature as the outlet temperature in the T control mode.

· dt0u (Delta Temp Outlet 0-10V). If selected, the controller uses a 0 to 10 Vdc temperature sensor. The controller selects this temperature as the outlet temperature in the T control mode.

If you select one of the following options: OFF, t10.0, SENs, noCL, noHt, OAS, t10V, CO2, HU, P10V, or t012, Steps 80 and 81 will not be available.

OFF

t10.0

SENs

noCL

noHt

OAS

t10V

CO2

OCC

nSb

oVrd

win

door

dFt

FLS

oVht

SEL

FrFb

HU

PI0u

t012

dt1t

dt1u

dt0t

dt0u

Default: UI1 Range:

2.0 0.0, 2.0

This option appears only if you have selected either P10V or t10V at Step 78, UI1.

. Select the minimum voltage for

Default: UI1 Range:

NO (Normally Open) NO (Normally Open), NC (Normally Close)

This option appears only if you have selected any one of the options: OCC, nSb, oVrd, win, door, dFt, FLS, oVht, SEL at

Step 78,

. Select the desired contact option.

www.neptronic.com

Page | 19

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default:

120 seconds

UI1 Range:

0 to 3600 seconds

Increment: 10 seconds

This option appears if you have selected any one of the options: oVrd, win, door, dFt, FLS, oVht, SEL at Step 78,

. Set the delay in seconds before the state of input for UI1 is changed.

Universal Input 2 (UI2)

Default:

OFF

UI2 Range:

OFF, t10.0, SENs, noCL, noHt, OAS, t10V, CO2, OCC,

nSb, oVrd, win, door, dFt, FLS, oVht, SEL, HU, P10V, t012

Select the input signal type for UI2 (Universal Input 2). Same options as Step 78,

priority over UI2. If you select the same input signal type as UI1, UI2 will not be functional.

. The UI1 input signal has

If you select one of the following options: OFF, noCL, noHt, OAS or HU, Steps 83 to 92 will not be available.

If you select t10.0, Steps 83 to 87 will not be available.

If you select t10V, Steps 84 and 85 will not be available.

If you select SENs, Steps 83 to 88 will not be available.

If you select CO2, Steps 83 to 89 and 93 to 103 will not be available.

If you select P10V or t10V, Step 83, “UI2 Minimum Voltage” will be available.

If you select P10V, Step 93, “Pressur Maximum Range” will be available.

Default: UI2 Range:

2.0 0.0, 2.0

This option appears only if you have selected either P10V or t10V at Step 82, “UI2 Signal Type”. Select the minimum voltage for UI2.

Default: UI2 Range:

NO (Normally Open) NO (Normally Open), NC (Normally Close)

This option appears only if you have selected any one of the options: OCC, nSb, oVrd, win, door, dFt, FLS, oVht, SEL at

Step 82,

. Select the desired contact option.

Default: UI2 Range:
Increment:

120 seconds 0 to 3600 seconds 10 seconds

This option appears if you have selected any one of the options: oVrd, win, door, dFt, FLS, oVht, SEL at Step 82, . Set the delay in seconds before the state of input for UI2 is changed.

Temperature Settings

Default: Range: Increment:

0ºC -40.0ºC to 0ºC 0.5ºC

[32ºF] [-40ºF to 32ºF] [1ºF]

This option appears only if you have selected t10V at Step 78,

or Step 82,

external temperature value. The minimum value is restricted by the maximum value set at Step 87,

words, the value that is set as the minimum cannot be greater than the maximum value.

. Set the minimum . In other

Default:

50ºC

[122ºF]

Range:

50ºC to 100ºC [122ºF to 212ºF]

Increment: 0.5ºC

[1ºF]

This option appears only if you have selected t10V at Step 78,

or Step 82,

external temperature value. The maximum value is restricted by the minimum value set at Step 86,

words, the value that is set as the maximum cannot be less than the minimum value.

. Set the maximum . In other

www.neptronic.com

Page | 20

Networkable Wall-Mount Controller
Specification and Installation Instructions

Range: Offset: Increment:

-40.0ºC to 100ºC [-40ºF to 212ºF]

Max. ± 5ºC

[± 9ºF]

0.1ºC

[0.2ºF]

This option appears only if you have selected t10.0, t10V, or t012 at Step 78,

or Step 82,

. The

display shows the temperature read by the external temperature sensor. Adjust the offset by comparing it with a known value (e.g. thermometer). If the sensor is not connected or short circuited, the unit displays the sensor’s limit.

Default: Range:

24.0ºC 10.0ºC to 40.0ºC

[75ºF] [50ºF to 104ºF]

Increment: 0.5ºC

[1ºF]

This option appears only if you have selected SENs at Step 78,

or Step 82,

. Set the desired

changeover temperature setpoint. Note that the heating mode activates when the temperature read by the external sensor is

above the changeover setpoint and cooling mode activates when the temperature read by the external sensor is below the

changeover setpoint.

CO2 Sensor Settings
The CO2 Sensor Settings appear only for the following conditions: if you have selected CO2 at Step 78, “UI1 Signal Type” or Step 82, “UI2 Signal Type”.

Default:

2000 PPM

Range:

100 to 5000 PPM

Increment: 50 PPM

Select the maximum range value for carbon dioxide (CO2).

Default: Range: Increment:

800 PPM 100 to 2000 PPM 10 PPM

Indicates the maximum limit of the CO2 concentration beyond which an alarm is activated. The setpoint value is restricted by the maximum range at Step 90, “CO2 Maximum Range”.

Default: Range:

No (Disable) No (Disable), YES (Enable)

Select whether to enable or disable the display of the CO2 value.

VFD Pressure Settings
The VFD Pressure Settings appear only if you have selected VFdP at Step 13, “AO2 Ramp” and P10V at Step 78, or Step 82, “UI2 Signal Type”.

Default: Range: Increment:

2000 Pa 200 to 200.0 Pa 50 Pa

This option appears if you have selected P10V at Step 78,

or Step 82, “UI2 Signal Type”. Select the maximum

range for pressure. If the value is higher than 10,000, the value will be divided by 100 and shows a decimal point. For example,

10,000 will be displayed as 100.0 and 10050 will be displayed as 100.5.

Default: Range: Increment:

500 Pa 100 to pressure maximum range (value set at Step 93) 1 Pa

Select the setpoint value for VFD pressure. If the value is higher than 10,000, the value will be divided by 100 and shows a decimal point. The increment is displayed as 0.1. The fan symbol is also displayed.

www.neptronic.com

Page | 21

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range: Increment:

50 Pa 0 to 100 Pa 1 Pa

Select the desired dead band value for VFD pressure. The fan

symbol is also displayed.

Default: Range: Increment:

200 Pa 100 to 500 Pa 1 Pa

Select the desired proportional band value for VFD pressure. The fan

symbol is also displayed.

Default:

0 seconds

Range:

0 to 250 seconds

Increment: 5 seconds

Set the desired value for VFD pressure integral seconds. The fan

symbol is also displayed.

VFD Temperature Settings
The VFD Temperature Settings appear only if you have selected VFdt at Step 13, “AO2 Ramp”.

Default: Range:

VFd (VFD Temp Setpoint) VFd (VFD Temp Setpoint), CtrL (User Temp Setpoint)

Select the desired setpoint source for the VFD temperature control. The fan symbol is also displayed.

Default: Range: Increment:

22.0ºC

[72ºF]

10.0ºC to 40.0ºC [50ºF to 104ºF]

0.5ºC

[1ºF]

Select the desired VFD temperature setpoint. The fan symbol is also displayed.

Default: Range: Increment:

0.3ºC 0.0ºC to 5.0ºC 0.1ºC

[0.6ºF] [0ºF to 9ºF] [0.2ºF]

Select the desired VFD temperature dead band value. The fan

symbol is also displayed.

Default: Range: Increment:

2.0ºC 0.5ºC to 5.0ºC 0.1ºC

[3.6ºF] [1ºF to 9ºF] [0.2ºF]

Select the desired VFD temperature proportional band value. The fan

symbol is also displayed.

Default:

0 seconds

Range:

0 to 250 seconds

Increment: 5 seconds

Set the desired value for VFD temperature integral seconds. The fan

symbol is also displayed.

Default: Range:

itS (internal) itS (internal), EtS (External)

Select the source for VFD temperature control. · itS. If selected, the controller will be controlled by its internal temperature sensor. · EtS. If selected, the controller will be controlled by an external temperature sensor.

www.neptronic.com

Page | 22

Networkable Wall-Mount Controller
Specification and Installation Instructions

Temperature Control Source Settings

Default: Range:

itS (internal) itS (internal), EtS (External), nEt (Network)

Select the source for temperature control. · itS. If selected, the controller will be controlled by its internal temperature sensor. · EtS. If selected, the controller will be controlled by an external temperature sensor. · nEt. If selected, the controller will be controlled by the temperature sent via the BMS. If you select itS or EtS, Step 105, “Network Timeout Minutes” will not be available. If you select nEt, Step 105, “Network Timeout Minutes” will be available.

Default: Range: Increment:

5 minutes 0 to 60 minutes 1 minute

This option appears only if you have selected nEt at Step 104,

. Select the duration in minutes after which

the controller will go to OFF mode if it does not receive the temperature value via BMS.

Window and Door Settings

Default: Range:

StP (Setpoint/override enabled) StP (Setpoint/override enabled), OFF

This option appears only if you have selected win at Step 78, symbol is also displayed.

or Step 82, “UI2 Signal Type”. The alarm

· StP. If selected, the controller uses the NSB/No Occupancy setpoints when the window is open.

· OFF. If selected, the controller is forced into OFF mode when the window is open.

Default: Range:

AUto (Automatic) AUto (Automatic), LO (Low), mEd (Medium), HI (High)

This option appears only if you have selected win at Step 78,

or Step 82, “UI2 Signal Type”. Select the fan

speed mode when the window is open. The fan and alarm symbols are also displayed.

Default: Range:

StP (Setpoint/override enabled) StP (Setpoint/override enabled), OFF

This option appears only if you have selected door at Step 78,

or Step 82, “UI2 Signal Type”.

· StP. If selected, the controller uses the NSB/No Occupancy setpoints when the door is open.

· OFF. If selected, the controller is forced into OFF mode when the door is open.

Default: Range:

AUto (Automatic) AUto (Automatic), LO (Low), mEd (Medium), HI (High)

This option appears only if you have selected door at Step 78,

or Step 82, “UI2 Signal Type”. Select the fan

speed when the door is open. The fan and alarm symbols are also displayed.

Night Set Back (NSB)

Default: Range: Increment:

120 minutes 0 to 180 minutes 15 minutes

This option appears only if you have selected nSb at Step 78,

or Step 82, “UI2 Signal Type”. When in Night Set

Back (NSB) Mode, the user can override Night Set Back (NSB) (see page 36) for the duration of this delay. To disable night set back override, set the delay to 0. The moon symbol is displayed to indicate Night Set Back (NSB) Mode.

www.neptronic.com

Page | 23

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range:

AUto (Automatic) AUto (Automatic), LO (Low), mEd (Medium), HI (High)

This option appears only if you have selected nSb at Step 78, speed mode for night set back. The fan symbol is also displayed.

or Step 82, “UI2 Signal Type”. Select the fan

Default: Range:

StP (Setpoint/override enabled) StP (Setpoint/override enabled), OFF

This option appears only if you have selected nSb at Step 78,

or Step 82, “UI2 Signal Type”.

· StP. If selected, the controller uses the NSB setpoints when in Night Set Back (NSB) Mode. (see page 36).

· OFF. If selected, the controller is forced into OFF mode when in Night Set Back (NSB) Mode. (see page 36).

Default: Range: Increment:

16ºC 10ºC to 40ºC 0.5ºC

[61ºF] [50ºF to 104ºF] [1ºF]

This option appears only if you have selected nSb at Step 78,

or Step 82, “UI2 Signal Type”. Set the heating

setpoint that will be used when the system is in Night Set Back (NSB) Mode (see page 36). The heating setpoint value is

restricted by the cooling setpoint value at Step 114,

. The moon and heating symbols are also displayed.

Default:

28ºC

[82ºF]

Range:

10ºC to 40ºC [50ºF to 104ºF]

Increment: 0.5ºC

[1ºF]

This option appears only if you have selected nSb at Step 78,

or Step 82, “UI2 Signal Type”. Set the cooling

setpoint that will be used when the system is in Night Set Back (NSB) Mode (see page 36). The cooling setpoint value is

restricted by the heating setpoint value at Step 113,

. The moon and cooling symbols are also

displayed.

Occupancy (OCC)

Default: Range: Increment:

30 minutes 0 to 240 minutes 1 minute

This option appears only if you have selected OCC at Step 78,

or Step 82, “UI2 Signal Type”. Set the minimum

time in minutes the controller must remain in the occupied state before it can be enabled to enter or re-enter the No Occupancy

Mode (see page 36). The moon symbol is also displayed.

Default: Range: Increment:

120 minutes 0 to 180 minutes 15 minutes

This option appears only if you have selected OCC at Step 78,

or Step 82, “UI2 Signal Type”. When in no

occupancy mode, the user can override the No Occupancy Mode (see page 36) up to the duration of this delay by pressing the

button. To disable the no occupancy override, set the delay to 0. The moon symbol is displayed to indicate the No

Occupancy Mode.

Default: Range:

AUto (Automatic) AUto (Automatic), LO (Low), mEd (Medium), HI (High)

This option appears only if you have selected OCC at Step 78,

or Step 82, “UI2 Signal Type”. Select the fan

speed mode for no occupancy mode. The fan symbol is also displayed.

Default: Range:

StP (Setpoint/override enabled) StP (Setpoint/override enabled), OFF

This option appears only if you have selected OCC at Step 78, symbol is also displayed.

or Step 82, “UI2 Signal Type”. The moon

www.neptronic.com

Page | 24

Networkable Wall-Mount Controller
Specification and Installation Instructions

· StP. If selected, the controller uses the No OCC setpoints when in No Occupancy Mode (see page 36). · OFF. If selected, the controller is forced into OFF mode when in No Occupancy Mode (see page 36). If you select OFF, Steps 119 and 120 will not be available.

Default: Range: Increment:

16ºC

[61ºF]

10ºC to 40ºC [50ºF to 104ºF]

0.5ºC

[1ºF]

This option appears only if you have selected OCC at Step 78,

or Step 82, “UI2 Signal Type”. Set the heating

setpoint that will be used when the system is in Night Set Back (NSB) Mode/No Occupancy Mode/Window Open Mode/Door

Open Mode. The heating setpoint value is restricted by the cooling setpoint value at Step 120,

. The moon

and heating symbols are also displayed.

Default: Range: Increment:

28ºC

[82ºF]

10ºC to 40ºC [50ºF to 104ºF]

0.5ºC

[1ºF]

This option appears only if you have selected OCC at Step 78,

or Step 82, “UI2 Signal Type”. Set the cooling

setpoint that will be used when the system is in Night Set Back (NSB) Mode/No Occupancy Mode/Window Open Mode/Door

Open mode. The cooling setpoint value is restricted by the heating setpoint value at Step 119, “No OCC Heating Setpnt”. The

moon and cooling symbols are also displayed.

Humidity Settings
The Humidity Settings appear only for the following conditions: if you have selected HU at Step 78, “UI1 Signal Type” or Step 82, “UI2 Signal Type” or for the models with the built-in humidity sensor, unless otherwise specified.

Offset: Range: Increment:

± 5% 10% RH to 90% RH 0.1% RH

This option appears only if you have selected HU at Step 78, “UI1 Signal Type” or Step 82, “UI2 Signal Type”. The display shows the relative humidity percentage read by the external humidity sensor. Adjust the offset by comparing it with a known value humidistat. If the sensor is not connected or short circuited, unit displays the sensor’s limits. The humidify symbol is also displayed.

Offset: Range: Increment:

± 5% 10% RH to 90% RH 0.1% RH

This option appears only for the models with the humidity sensor. Compare the displayed humidity percentage reading with a known value from a humidistat. This is useful for the humidistats installed in areas where the humidity reading is slightly
different than the room’s actual humidity. For example, a humidistat placed right under the air diffuser. The humidify symbol is also displayed.

Default: Range:

OFF OFF, Auto (Automatic humidify and dehumidify), dEHU (dehumidify only), Hu (humidify only)

· OFF (Disabled). If selected, the controller disables all humidify and dehumidify functions. · AuTo (Automatic humidify and dehumidfy). If selected, the ramp of at least one analog or binary output must be set to Hu
(humidify) and another output must be set to COOl (cooling). · dEHU (Dehumidify only). If selected, the ramp of at least one analog or binary output must be set to COOl (cooling). · Hu (Humidify only). If selected, the ramp of at least one analog or binary output must be set to Hu (humidify). If you select OFF, Steps 126 to 135 will not be available. If you select Hu or deHU, Step 126, “Humidty User Setpnt Minimum” will be available.

Default: Range:

No No, Yes

This option appears only if you have selected OFF at Step 123, “Humidty Control Mode”. Select whether to display humidity value or not. If set to No, the controller will not show the humidity value and if set to Yes, it will display the humidity value.

www.neptronic.com

Page | 25

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range:

irh Erh, irh

This option appears only for models with the built-in humidity sensor, while also having selected HU at Step 78, “UI1 Signal Type” or Step 82, “UI2 Signal Type”. Select the source for humidity control.
· irh. If selected, the controller will be controlled by its internal humidity sensor.
· Erh. If selected, the controller will be controlled by an external humidity sensor.

Default: Range: Increment:

30% RH 10% RH to 90% RH 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 123,

. In Operation Mode, you

cannot decrease the setpoint to less than the value set as the minimum humidity setpoint. The minimum value is restricted by

the maximum value set at Step 127,

. In other words, the value that is set as the minimum cannot be

greater than the maximum value.

Default: Range: Increment:

65% RH 10% RH to 90% RH 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 123,

. In Operation mode, you

cannot increase the setpoint to more than the value set as the maximum humidity setpoint. The maximum value is restricted by

the minimum value set at Step 126,

. In other words, the value that is set as the maximum cannot be

less than the minimum value.

Default: Range:

No (Unlocked) No (Unlocked), Yes (Locked)

This option appears only if you have selected AuTo, Hu or deHU at Step 123,

. If set to No, the user

setpoint option is not locked and the user can adjust the desired humidity setpoint. If set to Yes, the user setpoint option is

locked and the user cannot set the desired humidity setpoint. A lock symbol appears to indicate that the setpoint is locked.

Default: Range: Increment:

40% RH 10% RH to 90% RH 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 123,

. Set the desired humidity

setpoint. If the setpoint option was locked at Step 128,

, a lock symbol is displayed. The setpoint

value is restricted by the minimum at Step 126,

and maximum at Step 127,

values.

Default: Range: Increment:

30% RH 10% RH to 65% RH 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 123,

, and also nSb at Step 78,

or Step 82, “UI2 Signal Type”. Adjust the humidify setpoint during Night Set Back (NSB) Mode. The humidify

setpoint is restricted by the dehumidify value at Step 131,

. The moon and humidify symbols are also

displayed.

Default:

45% RH

Range:

10% RH to 65% RH

Increment: 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 123,

, and also nSb at Step 78,

or Step 82, “UI2 Signal Type”. Adjust the dehumidify setpoint during Night Set Back (NSB) Mode. The

dehumidify setpoint is restricted by the humidify setpoint at Step 130, symbols are also displayed.

. The moon and dehumidify

www.neptronic.com

Page | 26

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range: Increment:

30% RH 10% RH to 65% RH 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 123,

, and also OCC at Step 78,

or Step 82, “UI2 Signal Type”. Adjust the humidify setpoint during No Occupancy Mode. The humidify setpoint is

restricted by the dehumidify value at Step 133,

. The moon and humidify symbols are also displayed.

Default: Range: Increment:

45% RH 10% RH to 65% RH 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 123,

, and also OCC at Step 78,

or Step 82, “UI2 Signal Type”. Adjust the dehumidify setpoint during No Occupancy Mode. The dehumidify

setpoint is restricted by the humidify setpoint at Step 132,

. The moon and dehumidify symbols are

also displayed.

Default: Range: Increment:

5% RH 3% RH to 10% RH 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 123,

. Set the desired

proportional ramp value for the humidity control. This value applies to both humidification and dehumidification.

Default: Range: Increment:

1% RH 0% RH to 5% RH 0.5% RH

This option appears only if you have selected AuTo, Hu or deHU at Step 123, value for the humidity control. This value applies to both humidification and dehumidification.

. Set the desired dead band

Anti Freeze

Default: Range:

No (Disable) No (Disable), Yes (Enable)

If this option is enabled, heating starts automatically when the temperature drops to 4°C [39°F], even if the controller is in Cooling or OFF mode. Once the temperature reaches 5°C [41°F], the heating stops.

Delta Temperature

Default: Range:

OFF On, OFF

Select whether to enable or disable the T control based on the inlet and outlet temperature of the water inside the fan coil unit.

Default:

5°C [41°F]

Range:

-12°C to 12°C [10.4°F to 53.6°F]

Increment: 0.01°C [0.018°F]

This option appears only if you have selected On at Step 137, the T temperature control mode.

Backlight and Contrast Adjustment

. Set the desired value of the setpoint for

Default: Range: Increment:

50 0 to 100 5

Select the backlight or contrast level in the user mode (controller is in operation). Use the decrease the backlight or contrast level.

and buttons to increase or

www.neptronic.com

Page | 27

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range: Increment:

50 0 to 100 5

Select the backlight or contrast level in the occupied mode (controller is idle and occupancy state is active). Use the and buttons to increase or decrease the backlight or contrast level.

Default: Range: Increment:

50 0 to 100 5

Select the backlight or contrast level in the not occupied mode (controller is idle and occupancy state is inactive). Use the and buttons to increase or decrease the backlight or contrast level.

Network Settings

Default: Range:

bAC (BACnet) bAC (BACnet), mOd (Modbus)

Select the desired network protocol.

BACnet

Default: Range:

Yes (Enabled) Yes (Enabled), No (Disabled)

Enable or disable Auto Baud Rate Detection. When enabled, the controller automatically configures its baud rate by detecting the network speed upon connection to the network.

Default: Range:

No default (information display only) 9.6k, 19.2k, 38.4k, 76.8k

If you enabled Auto Baud Rate Detection at Step 143, baud rate.

the controller displays the automatically detected

Default: Range: Increment:

0 0 to 254 1

Select the desired MSTP MAC Address. Each device on the network must have a unique MAC address.

Default: Range: Increment:

127 1 to 127 1

Select the desired MSTP MAX address for the master device.

Default: Range:

No (Disable) No (Disable), Yes (Enable)

Select Yes to copy the configuration of the existing device to other devices of the same type on the network. If you select No,

go to Step 151,

.

Default: Range: Increment:

0 0 to 254 1

Select the first address you want to copy to. For example, if you select MAC address 1 as the “begin address” and 54 as the “end address”, all the devices from 1 to 54 will receive the configuration of the current device.

www.neptronic.com

Page | 28

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range: Increment:

“begin address” “begin address” + 63 1

Select the last address you want to copy to. You cannot copy more than 64 addresses at once.

www.neptronic.com

Page | 29

Networkable Wall-Mount Controller
Specification and Installation Instructions

Range:

“Copy Config” followed by one of these results: “Succeed”, “Progerr”, “Typeerr”, “Modlerr”, “Memerr”, “Slave”, “Commerr”

Displays “Succeed” if the addresses have been copied successfully. Otherwise, an error message appears with the associated MAC address. You can scroll through the addresses and see the error message associated with each address. See below for a complete list of error messages.”copy config succeed” Copy config was successful.
“copy config progerr”
Copy config failed because the target device is in Program Mode.

“Copy config” results
MAC address of Associated device
Use arrow keys to scroll through each
address

Indicates error

“copy config typeerr”
Copy config failed because the target device is not the same as the source device. For example, copying an EVC configuration to an EFC device.

copy config modlerr”
Copy config failed because the model number of the source device and the target device is not the same. For example, copying a TSUB configuration to an EFCB.

“copy config mem err” Copy config failed because the software/application version of the source device and the target device is not the same.

“copy config Slave”
The target device has a slave address and it cannot respond to the master. Manually verify that the configuration was copied correctly or avoid using a slave address (128 – 254).

“copy config commerr”
Copy config failed because the target device did not respond after 3 attempts. Either the address does not exist or there is a problem with the wiring or with noise.

Default: Range:

No No, Yes

To change the device instance, select Yes and continue to the next step. If you select No, the device instance will be modified

automatically according to the MAC address (the menu starts over at Step 1,

).

Default: Range: Increment:

“current value” 0 to 4194302
1

Use the arrow keys to change the value and press the digit. Ensure that you provide a unique device instance.

Modbus

button to move to the next digit or press

to move to the previous

Default: Range:

Yes (Automatic) No (Manual), Yes (Automatic)

Enable or disable Modbus Auto Baud Rate Detection. When enabled, the controller automatically configures its baud rate by detecting the network speed upon connection to the network.

Default: Range:

No default (information display only) 9.6k, 19.2k, 38.4k, 57.6k

If you enabled Modbus Auto Baud Rate Detection at Step 153, detected baud rate.

, the controller displays the automatically

Default: Range:

NP2s (no parity, 2 stop bits) EP1s (even parity, 1 stop bit), OP1s (odd parity, 1 stop bit), NP2s (no parity, 2 stop bits)

www.neptronic.com

Page | 30

Networkable Wall-Mount Controller
Specification and Installation Instructions

Select the desired parity and number of stop bits for the modbus communication.

Default: Range: Increment:

1 1 to 246 1

Select the desired Modbus address. Each device on the network must have a unique Modbus address.

www.neptronic.com

Page | 31

Networkable Wall-Mount Controller
Specification and Installation Instructions

Scheduling Mode Settings
This menu is accessible through normal operation mode. The Mode Selector Jumper (JP1) must be set to the RUN position (Operation Mode).

1. Press and hold the button for 5 seconds. The ”

” screen appears.

2. Enter the password (367) within 1 minute. Use the and arrow keys to increase or decrease the value and the ,

buttons to toggle between the digits. If you enter the wrong password, the controller displays “Eror” and returns to Operation

Mode.

Use the same menu operations as described in Programming Mode on page 6.

The controller will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 minutes. The changed values will be saved automatically.

= scroll menu items
Schedul Main Menu HrS (Time) dAtE (Date) Opt (Options) SCHd (Schedule) rSt (Reset Schedule) quit (Exit Menu)

Time

Default: Range:

12 12 hours, 24 hours

Select the desired time format.

Range:

00 to 23 hours

Increment: 1 hour

Select the time in hours.

Range:

0 to 59 minutes

Increment: 1 minute

Select the time in minutes.

Date

Default: Range: Increment:
Select the year.

2020 2009 to 2099 1 year

Range: Increment:
Select the month.

01 to 12 1 month

Range: Increment:
Select the day.

01 to 31 days 1 day

www.neptronic.com

Page | 32

Options

Networkable Wall-Mount Controller
Specification and Installation Instructions

Default: Range:

No Yes, No

Select whether to schedule events or not. If set to No, then you will proceed to the quit option. If set to Yes, then you will proceed to Step 8, “Schedul Default Value”.

Default: Range:

OCC OFF, OCC (Occupancy), nOCC (Non-Occupancy), LOC (Locally)

Select the default occupancy mode for the schedule.

Schedule

Default: Range:

mo mo (Monday), tu (Tuesday), wE (Wednesday), th (Thursday), Fr (Friday), SA (Saturday), Su (Sunday)

Select the day of the week.

Range:

E1 to E6,

00 to 23 hours, 00,15, 30, 45 minutes,

OFF, OCC (Occupancy), nOCC (Non-Occupancy), — (Null), LOC (Locally)

Increment: 1

Set the parameters to schedule an event. Select the event number, followed by the time (hours and minutes) and occupancy mode. If — (Null) is selected, then the controller will remain turned off and the event will be unused. To exit the Event menu,

press the button.

Reset Schedule

Default: Range:

nO yES, nO

Select whether to reset and delete the scheduled events or not.

Network Setup Menu
This menu is accessible through normal operation mode. The Mode Selector Jumper (JP1) must be set to the RUN position (Operation Mode).

1. Press the and keys for 5 seconds. The ”

” screen appears.

2. Enter the password (637) within 1 minute. Use the and arrow keys to increase or decrease the value and the ,

buttons to toggle between the digits. If you enter the wrong password, the controller displays “Eror” and returns to Operation

Mode.

Use the same menu operations as described in Programming Mode on page 6.

The controller will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 minutes. The changed values will be saved automatically.

Range: Page:

Steps 142 to 156 Page 28 to 31

These network setup steps are exactly the same as those in the Programming Mode. Please refer to Steps 142 to 156, starting on page 28. When complete, continue to the following step.

www.neptronic.com

Page | 33

Networkable Wall-Mount Controller
Specification and Installation Instructions

Sensor Offset Menu
This menu is accessible through normal operation mode. The Mode Selector Jumper (JP1) must be set to the RUN position (Operation Mode).

1. Press the and keys for 5 seconds. The ”

” screen appears.

2. Enter the password (372) within 1 minute. Use the and arrow keys to increase or decrease the value and the ,

buttons to toggle between the digits. If you enter the wrong password, the controller displays “Eror” and returns to Operation

Mode.

Use the same menu operations as described in Programming Mode on page 6.

The controller will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5 minutes. The changed values will be saved automatically.

Range: Offset: Increment:

0ºC to 50ºC Max. ± 5ºC 0.1ºC

[32ºF to 122ºF] [± 9ºF] [0.2ºF]

Compare the displayed temperature reading with a known value from a thermometer or other temperature sensing device. To offset or calibrate the sensor, use the arrow buttons to set the desired temperature reading. This is useful for controllers installed in areas where the temperature read is slightly different than the room’s actual temperature. For example, a controller placed right under the air diffuser.

Range:

-40.0ºC to 100ºC [-40ºF to 212ºF]

Offset:

Max. ± 5ºC

[± 9ºF]

Increment: 0.1ºC

[0.2ºF]

This option appears only if you have selected t10.0 or t10V at Step 78, “UI1 Signal Type” or Step 82, “UI2 Signal Type”. The

display shows the temperature read by the external temperature sensor. Adjust the offset by comparing it with a known value

(e.g. thermometer). If the sensor is not connected or short circuited, the unit displays the sensor’s limit.

Offset: Range: Increment:

± 5% 10% RH to 90% RH 0.1% RH

This option appears if the controller is set to use an external humidity sensor. The display shows the relative humidity percentage read by the external humidity sensor. Adjust the offset by comparing it with a known value humidistat. If the sensor is not connected or short circuited, unit displays the sensor’s limits. The humidify symbol is also displayed.

Default: Range: Increment:

500 Pa 100 to pressure maximum range 1 Pa

This option appears only if you have selected VFdP at Step 13 “AO2 Ramp”, and P10V at Step 78, “UI1 Signal Type” or Step 82, “UI2 Signal Type”. Select the setpoint value for VFD pressure. The fan symbol is also displayed.

Default: Range: Increment:

22.0ºC

[72ºF]

10.0ºC to 40.0ºC [50ºF to 104ºF]

0.5ºC

[1ºF]

This option appears only if you have selected VFdt at Step 13 “AO2 Ramp”. Select the setpoint value for VFD pressure. The fan symbol is also displayed.

Reset to Factory Default Settings

This will erase all actual configurations and replace them with the factory default settings.

1. The Mode Selector jumper (JP1) of the digital room sensor must be set to the “RUN” position (Operation Mode). Refer to the Wiring section on page 3.

2. During the power up sequence of the controller and digital room sensor, press and hold both the [ ] and buttons.

3. The “Enter Password” screen appears. Enter 372 within 1 minute by using the arrow keys to increase or decrease the value and

the [ ] and [

] buttons to toggle between the digits.

4. Use the arrow buttons to select YES and then press [ ].

www.neptronic.com

Page | 34

Networkable Wall-Mount Controller
Specification and Installation Instructions
Operation Mode
The Mode Selector Jumper JP1 must be set to the RUN position (Operation Mode). Refer to the Wiring section on page 3.
Operation Mode

Actual Demand

C
Actual Tempertature
Press for 3 seconds to change the scale between Celsius and Fahrenheit

Press once to display Control mode

Press twice to display setpoint

Press once to display Fan Speed mode

Press to change mode -AUTO -HEAT ONLY -COOL ONLY -FAN -OFF
Exits after 5 seconds

Appears if setpoint adjustment is locked
C
Actual Temperature

Exits after 3 seconds

Change setpoint value

Exits after 5 seconds

Press to change mode – AUTO
-LOWSPEED
-MED SPEED
-HIGH SPEED

Power Up
Upon power up, the LCD illuminates and all segments appear for 2 seconds. The controller then displays its current version for 2 seconds.

LCD Backlight
Pressing any key illuminates the LCD for 4 seconds.

Default Display
The controller displays temperature and humidity readings or setpoints, with or without demand according to the selection made at Step 8, “Display Info”. If a humidity sensor is not used, the temperature values will always be displayed. If a sensor is disconnected or short circuited, then the unit displays the sensor’s limits. To toggle the temperature scale between °C and °F, press both the up
and down arrow keys for 3 seconds.

Temperature Setpoint Display and Adjustment

To display the setpoint, press the or key twice. The setpoint appears for 3 seconds. To adjust the setpoint, press the arrow

keys while the setpoint is displayed. If the setpoint adjustment has been locked (Step 5,

), the lock symbol appears.

Humidity Setpoint Display and Adjustment
To access the Humidity setpoint, press the button for 5 seconds. The humidity setpoint will be displayed for 5 seconds. To adjust the setpoint, press the and keys while the setpoint is displayed. The unit automatically exits this menu if you do not press any key for 3 seconds. The changed values will be saved automatically.

Control Mode
To access the Control Mode, press the key. The Control Mode appears for 5 seconds. Press the following control modes. These options can vary depending on the options selected at the following: Step 6, Step 7, Step 27,

key to scroll through the

· Auto (Automatic Cooling or Heating) · Cooling only (on, with cooling symbol) · Heating only (on, with heating symbol) · FAN (on, with fan symbol) · OFF (if it is not disabled in Programming Mode)

www.neptronic.com

Page | 35

Networkable Wall-Mount Controller
Specification and Installation Instructions

Fan Speed Selection Mode

To access the Fan Speed selection mode, press the key. The mode appears for 5 seconds. These options can vary depending

on the fan speed signal and auto mode settings at Step 30

and Step 26,

. If in No Occupancy mode, the

button now serves as the override button.

The Fan Speed Selection Mode is not available when VFD analog output is used and if Yes is selected at Step 29

.

· Automatic speed. This option is available if you have selected yES (Enable) at Step 30,

in Programming Mode.

· Low speed

· Medium speed

· High speed

· OFF. OFF is not selectable by the user, it appears only if the “Control Mode” is “OFF” and it indicates that the user cannot

change the speed of the fan.

Night Set Back (NSB) Mode

This function is only available if you have set input to nSb (Night Set Back contact). If the contact is triggered, the controller enters

NSB Mode (the symbol appears) and uses the NSB setpoints defined at Steps 113,

, 114,

and

111,

. Press any key to override NSB for the delay defined at Step 110,

. The symbol flashes

to indicate that the NSB mode is overridden (during this time the standard setpoints are used).

No Occupancy Mode
This function is only available if you have set input to OCC (occupancy contact). If the contact is triggered and the minimum occupancy time defined at Step 115, “OCC Minimum Time In Minutes” has elapsed, the controller enters No Occupancy Mode (the symbol appears) and uses the No OCC setpoints defined at Steps 119, “No OCC Heating Setpnt”, 120 “No OCC Cooling Setpnt” and 117, “No OCC Fan Mode”. Press the fan button to override no occupancy. Each time you press the button, 15 minutes are added to the override up to a maximum defined by Step 116, “No OCC Override Delay Minutes”. Press the fan button until “0” is displayed to disable the override. The icon will flash and the remaining override time will be displayed in minutes.

Backlight and Contrast Level Adjustment
For models with the grey LCD screen, the backlight level can be adjusted. For models with the black LCD screen, the contrast level can be adjusted. Press and hold the and buttons for 5 seconds and enter the password 367 to gain access to the backlight and contrast level adjustment settings. Use the and keys to adjust the backlight or contrast level in three modes: User (controller is in operation), Occupied (controller is idle and occupancy state is active) and Not Occupied (controller is idle and occupancy state is inactive). Press the key to save any changes.

www.neptronic.com

Page | 36

Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com.
400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com
Toll free in North America: 1-800-361-2308 Tel.: 514-333-1433 Fax: 514-333-3163
Customer service fax: 514-333-1091 Monday to Friday: 8:00am to 5:00pm (Eastern time)

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals