CPE 310
Quick Start Guide
Flush-mount multifunction pressure transmitter
| Input for interchangeable probe (Class 310)| | 3 analog outputs 0-5/10 V or
0/4-20 mA
---|---|---|---
| 3 audible and visual alarms| | MODBUS network RS485 system (optional)
General features
Power supply | 24 Vac / Vdc ±10% |
---|---|
Output | 3 x 0/4-20 mA or 3 x 0-5/10 V (4 wires) Common mode voltage |
Maximum load: 500 Ohms (0/4-20 mA) / Minimum load: 1 K Ohms (0-5/10 V)
Galvanic isolation| On the output
Consumption| 5 VA
Conformity| 2014/30/EU EMC; 2014/35/EU Low Voltage; RoHS 2011/65/EU
(EU)2015/863; 2012/19/EU WEEE
Electrical connection| Screw terminal block for cables from 0.05 to 1.5 mm²
or from 30 to 16 AWG Carried out according to the code of good practice
RS485 communication| Digital: Modbus RTU protocol, configurable communication
speed from 2400 to 115200 Bauds (optional)
Visual alarm| Blinking of the value
Audible alarm| Buzzer (70 dB at 10 cm)
Environment and type of fluid| Air and neutral gases
Conditions of use (°C/%RH/m)| From -10 to +50 °C. In non-condensing condition.
From 0 to 2000 m
Storage temperature| From -10 to +70 °C
Features of the housing
Front face | Brushed stainless steel 316 L |
---|---|
Back housing | Flush-mount in stainless steel 304 L |
Protection | IP65 in the front face |
Display | Electroluminescent alphanumeric (38 x 48 mm) Protection screen made |
of inactinic red PMMA
Height of the digits| 14 mm
Back fittings| Barbed fitting Ø 5.2 mm
Weight| 640 g
Symbols used
For your safety and in order to avoid any damage to the device, please follow
the procedure described in this document and read carefully the notes preceded
by the following symbol:
The following symbol will also be used in this document, please read carefully the information notes indicated after this symbol:
Connections
Electrical connections as per NFC15-100 standard
This connection must be made by a formed and qualified technician. Whilst making the connection, the transmitter must not be energized. The presence of a switch or a circuit breaker upstream of the device is compulsory.
Configuration
Class 310 transmitters allow you to set all the parameters managed by the transmitter: units, measuring ranges, alarms, outputs, channels… via the different methods shown below:
- Via the keypad, only on models with the display. A code-locking system for the keypad guarantees the security of the installation. See configuration manual.
- Via software (optional): simple and user-friendly. See LCC-S user manual.
Mounting
To install a transmitter on a wall, make a cutting of 198 x 72 mm in the wall.
Then drill 4 holes around the cutting as shown beside.
Insert the transmitter into the wall and fix it with the 4 screws (supplied
with the transmitter).
Accessories
Please refer to the datasheet to get more information about available accessories.
Maintenance: Please avoid any aggressive solvents. Please protect the transmitter and its probes from any cleaning product containing formalin, that may be used for cleaning rooms or ducts.
Precautions for use: please always use the device in accordance with its
intended use and within parameters described in the technical features in
order
not to compromise the protection ensured by the device.
Download the full manual Télécharger le manuel complet Descargue el manual de usuario Scarica il manuale completo
https://sauermanngroup.com/en-INT/technical-documents?search=cpe
Customer service portal
Use our Customer service portal to contact us
https://sauermann-en.custhelp.com
QSG – CPE 310 – 14/12/2021 – Non-contractual document – We reserve the right to modify the characteristics of our products without prior notice
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>