sauermann N1014-00 Condensate Pump Instruction Manual

May 15, 2024
sauermann

sauermann- logo

www.sauermanngroup.com N1014 – 00 Edition 23/09

SAFETY WARNING

Risk of electric shock. Make certain that the entire power supply to the unit/system is disconnected before attempting to install, service or remove any component.
The pump unit must not be immersed in water, installed outside the premises, stored in a damp environment or exposed to frost. This pump has not been investigated for use in swimming pool or marine areas.
CAUTION: This pump has been designed for use with water only.
All condensate collection elements (collection tray, connecting tubes, outlets etc…) must be cleaned thoroughly prior to installing the pump.
The pump is supplied with :

  • A self-resetting thermal cut-out set at 115°C (239°F).
  • A self extinguishing body case (UL94 V0 Material)

Max flow rate| 50Hz : 201/h
60Hz : 191/h (US: 5 gph)
---|---
Max discharge head| 10m (33 ft)
Voltage
| 230V – 50Hz – 14W
or 120V-60Hz – 14W
or 208 – 230V-50/60Hz – 14W
Safety switch| NC 8 A resistive – 250 V
Thermal protection (overheating)| 115°C (239°F)
Detection levels| On: 18rnm Off 13mm At 21mm On: 5/8″, Oft 17/32″, Al: 13/16″
Sound level| 22 dBA (1 m – 3.3 ft)
Security standards| CE, UKCA, EAC,UL
Protection| IPX4

  • Depending on reference

sauermann N1014 00 Condensate Pump - figer1

sauermann N1014 00 Condensate Pump - figer2

Pump Power Supply

Connect pump Phase and Neutral terminals to the air conditionner unit’s power supply or to the mains supply to comply with local National Standards. We suggest use of :
– An interconnecting power cable (CE: HO5 VVF 2 x 0.5 mm² ; UL/CSA: 2 x 0.5mm² (AWG20) certified UL2464
– 80°C – 300V) which must be fastened securely to the wall, to avoid inadvertent disconnection during installation and later servicing.
– This connection should be equipped with an electrical isolation device to the Phase and Neutral.
The pump must be powered by an electrical circuit protected against overvoltage> 2.5kV.
Pump safety switch
IMPORTANT : Connecting the safety switch is mandatory to avoid any risk of overflowing. For correct connection, refer to the manufacturer’s appliance instructions.
The pump is equipped with a NC high water safety switch with a maximum rating of 8A/250V (safety switch CE: 2 x 0.5 mm², UL/CSA: 2 x 0.5 mm² (AWG20)).This contact may be used to switch off the air conditionner where there is a risk of condensate overflow (after thorough verification by the installer of the customer’s specific application and the resultant electric wiring diagram).
Do not break air conditionner’s earth and communication wire.

Initial operational test

  • First clean the condensate tray of any debris leftover from manufacture or unpacking of the air conditioner unit
  • Pour slowly 100-250ml (3 – 8oz) of water onto the heat exchanger or into the condensate collection tray (a squeezable plastic bottle, ACC00944, is available)
  • Check that the pump unit starts & then stops as the water level decreases.
  • Check safety switch by continuing to pour water until the alarm triggers.

The pump must be cleaned and serviced at regular intervals in accordance with the degree of pollution existing witin the pump operating environment ****Void warranty if the detection reservoir rubber seal is removed.

For any problem, check :

  • the discharge lines are neither obstructed nor kinked,

  •  the float inside the pump unit is not blocked

  • the hydraulic inlets nor outlets are not obstructed
    If the pump is running continuously (>1min), check:

  •  the discharge height is < 10 m,

  • the pump is suitable for the capacity of the air conditioning unit,

  • while starting of the pump, the flow of the water poured into the collection tray was not too high (ex: 1l in 30s=60l/h >>20l/h).
    If the pump is running continuously and does not suck water, check that the suction hose (hose that connects the pump and detection unit) is connected and air tight If the pump cycles continually or does not shut off,- turn the pump off and check water doesn’t return down the discharge line. If water returns down the line you should change the pump.
    Before you start cleaning your air conditioning system, you must remove the pump to prevent damage.

CONFORMITY CERTIFICATE

SAUERMANN – Z.I l’orée de Chevry – 77173 CHEVRY COSSIGNY- FRANCE
– declares that the product Si-10 condensate lift mini-pump is in conformity with the standards :
EN 60335-1
EN 60335-2-41
EN 55014-1, EN 55014-2
EN 61000-3-2, EN 61000-3-3
EN 62233:2013
– Please note that it is prohibited to put this pump into service before the machine in which it is incorporated has been declared to conform with the provisions of machine directive 2014/35/UE and with the electromagnetic compatibility directive 2014/30/UE
For further information: services@sauermanngroup.com

WARRANTY

24 months. sauermanngroup.com/en-GB/warranty

www.sauermanngroup.com