Sauermann N1014-00 Max Flow Rate Pump Instruction Manual

June 1, 2024
sauermann

Sauermann N1014-00 Max Flow Rate Pump

Specifications

  • Max flow rate: 50Hz: 20 l/h, 60Hz: 19 l/h (US: 5 gph)
  • Max discharge head: 10m (33 ft)
  • Voltage: 230V – 50Hz – 14W or 120V~60Hz – 14W or 208 – 230V~50/60Hz – 14W
  • Safety switch: NC 8 A resistive – 250 V
  • Detection levels: On: 18mm, Off: 13mm, Al: 21mm
  • Sound level: 22 dBA (1m – 3.3 ft)
  • Security standards: CE, UKCA, EAC, UL
  • Protection: IPX4

Product Usage Instructions

Electrical Connection (DE / IT):

Connect the pump phase and neutral to the air conditioner power supply or network using appropriate cables according to local regulations. Ensure proper grounding and safety measures are in place.

Maintenance Recommendations (FR):

During maintenance, ensure there is protection on both the phase and neutral wires. Avoid cutting the ground wires of the air conditioner.

Interconnection Cable Recommendation (IT):

Use an interconnection cable securely fixed to the wall to prevent accidental disconnection during installation or maintenance procedures.

FAQ

  • Q: What are the safety standards this product complies with?
    • A: This product complies with CE, UKCA, EAC, and UL safety standards.
  • Q: What is the maximum flow rate of the pump?
    • A: The maximum flow rate is 20 l/h at 50Hz and 19 l/h at 60Hz (equivalent to 5 gallons per hour in the US).

SAFETY WARNING

Risk of electric shock. Make certain that the entire power supply to the unit/system is disconnected before attempting to install, service or remove any component. The pump unit must not be immersed in water, installed outside the premises, stored in a damp environment or exposed to frost. This pump has not been investigated for use in swimming pool or marine areas.
CAUTION: This pump has been designed for use with water only. All condensate collection elements (collection tray, connecting tubes, outlets etc…) must be cleaned thoroughly prior to installing the pump. This pump is designed to evacuate neutral-phase, non-oily condensate. It must not run dry. Ensure that there is no syphon effect on the discharge tube. The pump is supplied with :

  • A self-resetting thermal cut-out set at 115°C (239°F).
  • A self-extinguishing body case (UL94 V0 Material)

Technical Data

What In Box

Installation Instruction

Pump Power Supply

Connect pump Phase and Neutral terminals to the air conditioner unit’s power supply or to the mains supply to comply with local and National Standards. We suggest the use of :

  • An interconnecting power cable (CE: HO5 VVF 2 x 0.5 mm² ; UL/CSA: 2 x 0.5mm² (AWG20) certified UL2464
  • 80°C – 300V) which must be fastened securely to the wall, to avoid inadvertent disconnection during installation and later servicing.
  • This connection should be equipped with an electrical isolation device to the Phase and Neutral. The pump must be powered by an electrical circuit protected against overvoltage> 2.5kV. Pump safety switch

IMPORTANT: Connecting the safety switch is mandatory to avoid any risk of overflowing. For correct connection, refer to the manufacturer’s appliance instructions. The pump is equipped with an NC high water safety switch with a maximum rating of 8A/250V (safety switch CE: 2 x 0.5 mm², UL/CSA: 2 x 0.5 mm² (AWG20)). This contact may be used to switch off the air conditioner where there is a risk of condensate overflow (after thorough verification by the installer of the customer’s specific application and the resultant electric wiring diagram). Do not break the air conditioner’s earth and communication wire.

Initial operational test

  • First clean the condensate tray of any debris leftover from the manufacture or unpacking of the air conditioner unit
  • Pour slowly 100-250ml (3 – 8oz) of water onto the heat exchanger or into the condensate collection tray (a squeezable plastic bottle, ACC00944, is available)
  • Check that the pump unit starts & then stops as the water level decreases.
  • Check the safety switch by continuing to pour water until the alarm triggers.

The detection unit must be cleaned at the beginning of the season and regularly if the system is used all year round. The frequency of this cleaning varies according to the degree of pollution caused by the environment. Void warranty if the detection reservoir rubber seal is removed.

For any problem, check

  • the discharge lines are neither obstructed nor kinked,
  • the float inside the pump unit is not blocked
  • the hydraulic inlets nor outlets are not obstructed

If the pump is running continuously ( >1min), check:

  • the discharge height is < 10 m,
  • the pump is suitable for the capacity of the air conditioning unit,
  • while starting of the pump, the flow of the water poured into the collection tray was not too high (ex: 1l in 30s=60l/h >>20l/h).
    If the pump is running continuously and does not suck water, check that the suction hose (hose that connects the pump and detection unit) is connected and air tight

If the pump cycles continually or does not shut off,

  • turn the pump off and check water doesn’t return down the discharge line. If water returns down the line you should change the pump.
    Before you start cleaning your air conditioning system, you must remove the pump to prevent damage.

CERTIFICAT DE CONFORMITE

  • declares that the product Si-10 condensate lift mini-pump is in conformity with the standards :

  • EN 60335-1

  • EN 60335-2-41

  • EN 55014-1, EN 55014-2

  • EN 61000-3-2, EN 61000-3-3

  • EN 62233:2013
    Please note that it is prohibited to put this pump into service before the machine in which it is incorporated has been declared to conform with the provisions of machine directive 2014/35/UE and with the electromagnetic compatibility directive 2014/30/UE

  • Pour toute information / For further information: services@sauermanngroup.com

WARRANTY

Contact

SAUERMANN FRANCE

  • Parc d’activités de l’Orée de Chevry
  • Route de Férolles
  • 77173 CHEVRY COSSIGNY / FRANCE
  • Tel. : +33 (0)1 60 62 06 06
  • Fax : +33 (0)1 60 62 09 09
  • www.sauermann.fr

SAUERMANN GERMANY

  • Leibnizstrasse 6
  • 74211 LEINGARTEN / GERMANY
  • Fon : +49 (0)7131/399990
  • Fax : +49 (0)7131/399992
  • www.sauermanngroup.de
  • SAUERMANN N.A. Corp.
  • 415 Oser Avenue, Suite P,

Hauppauge, NY 11788 / USA

SAUERMANN Shanghaï Co. Ltd.

  • No. 1 Changxu Road,
  • Juyan New Park – Jiading District,
  • Shangai 201808/R.P. China
  • Tel. : (+ 86) 21 691 689 61
  • Fax : (+ 86) 21 691 689 62
  • www.sauermanngroup.com.cn
  • Sauermann Hong Kong Ltd.
  • 10A Seapower Ind. Centre,
  • 177 Hoi Bun Road, Kwun Tong
  • Kowloon, Hong Kong SAR
  • www.sauermanngroup.hk

SAUERMANN ITALIA

  • Via G.Golini 61/11
  • 40024 Castel S.Pietro Terme (Bo)
  • ITALY
  • Tél.: (+39)-051-6951033
  • Fax: (+39)-051-942254
  • www.sauermann.it

SAUERMANN UK

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals