**sauermann Si-20 Pump Safety Switch User Manual
**
SAFETY WARNING
Risk of electric shock. Make certain that the power supply to the
unit/system is disconnected before attempting to ins- tall, service or remove
any component.
The pump unit must not be immersed in water, installed outside the premises,
stored in a damp environment or exposed to frost. This pump has not been
tested for use in swimming pools or marine areas.To reduce risk of electric
shock, read instruction manual for proper installation and install the pump
and all electrical compo- nents above the top grade level of the sump.
CAUTION: This pump has been designed for use with water only. All
condensate collection elements (collection tray, connecting tubes, outlets
etc…) must be cleaned thoroughly prior to installing the pump. This pump is
designed to evacuate neutral-phase, nonoily condensate. It must not run dry.
Ensure that there is no syphon effect on the discharge tube.
The pump is supplied with:
- A self-resetting thermal cut-out set at 115 °C (239 °F).
- A self extinguishing body case (UL94 VO Material)
When installed outside the AC unit, the pump must not be accessible without
the aid of a tool.
Pump Power Supply
Connect pump Phase and Neutral terminals to the air conditioner unit’s power
supply or to the mains supply by means of wiring to comply with local National
Standards. We suggest use of :
-
An interconnecting power cable (CE: HO5 VVF 2 x 0.5 mm2; UL/CSA:
2 x 0.5 mm² (AWG20) certified UL2464 – 80 °C – 300 V) which must be fastened securely to the wall, to avoid inadvertent disconnection during installation and later servicing. -
This connection should be equipped with an electrical isolation device (2
A Fused Spur, customer provided) to the Phase and Neutral.
The pump must be powered by an electrical circuit protected against over- voltage> 2.5 kV.
Pump safety switch
IMPORTANT: Connecting the cable of the safety switch is indispensable to
avoid any risk of overflowing. For correct connection, refer to the ap-
pliance instructions.
The pump is equipped with a NC high water safety switch with a maxi- mum
rating of 6 A/250 V (safety switch CE: 2 x 0.5 mm2, UL/CSA:
2 x 0.5 mm2 (AWG20)).This contact may be used to switch off the air
conditioner where there is a risk of condensate overflow (after thorough
verification by the installer of the customer’s specific application and the
resultant electric wiring diagram).
Ensure power cable is not subject to prolonged water exposure.
Initial operational test
- First clean the condensate tray of any debris left over from manu- facture or unpacking of the air handling unit.
- Pour water into the condensate collection tray (a squeezable plastic bottle, ACC00401, is available).
- Check that the pump unit starts & then stops as the water level de- creases.
- Check safety switch by continuing to pour water until the alarm trig- gers (cutting off the compressor).
The detection unit must be cleaned at the beginning of the season and
regularly if the system is used all year round. The frequency of this cleaning
varies according to the degree of pollution caused by the environment.
If the pump doesn’t start, check the wiring and incoming power supply.
For all problems first check:
- the discharge lines are neither obstructed nor kinked,
- the float inside the detection unit is not blocked
- the hydraulic inlets nor outlets are not obstructed
If the pump is running continuously ( >1min), check:
- the discharge height is < 10 m (33 ft)
- the pump is suitable for the capacity of the air conditioning unit,
- while starting the pump, the flow of the water poured into the collection tray was not too high (ex:1 l in 30 s = 60 l/h >>20 l/h – 1/8 gal in 30 s = 15 gph >> 5 gph)
If the pump is running continuously and there is no suction of water, check that the suction hose (hose that connects the pump and detection unit) is connected and air tight.
If the pump cycles continually or does not shut off:
- check the detection unit is mounted level.
- turn the pump off and see if the water returns down the discharge line. If water returns down the line you should replace the pump.
Product Package
Max flow rate | 20 l/h @ 50 Hz ( 5.28 gph )19 l/h @ 60 Hz (5 gph) | |
---|---|---|
Max discharge head | 10 m ( 33 ft ) | |
Voltage | 230 V~50 Hz – 15 W120 V~60 Hz – 13 W230 V~50/60 Hz – 15 W | |
Insulation class | (double insulation) | |
Safety switch | NC 6 A resistive – 250 V | |
Thermal protection (overheating) | 115 °C ( 239 °F ) auto-reset | |
Detection levels | On: 16 mm, Off: 11 mm, Al: 19 mm On: 5/8”,Off: 7/16’’, Al: |
3/4’’
Sound level| 19 dBA
Safety standards| CE / UL / CSA / EAC / UKCA
SI20CE02UN23 / SI20UL02UN12 / SI20UL02UN23
Flow rate
Discharge head
Before you start cleaning your air conditioning system, you must remove the pump to prevent damage.
-
PRODUCT CODE / CODE PRODUIT / CÓDIGO PRODUCTO / 产品码说明
Example : -
Production plant
-
Year
-
Week
-
Incremental number
-
Production order number
SERVICING OF DOUBLE-INSULATED APPLIANCES
A double-insulated appliance is marked with one or more of the following: The words ‘‘DOUBLE INSULATION’’ or ‘‘DOUBLE INSULATED’’ or the double insulation symbol (square within a square). In a double-insulated appliance, two systems of insulation are provided instead of grounding. No grounding means is provided on a double-insulated appliance, nor should a means for grounding be added. Servicing a double-insulated appliance requires extreme care and knowledge of the system, and should be done only by qualified service personnel. Replacement parts for a double-insulated appliance must be identical to the parts they replace.
CERTIFICAT DE CONFORMITÉ / CONFORMITY CERTIFICATE /
BEREINSTIMMUNGSBESCHEINIGUNG / CERTIFICATO DI CONFORMITA SAUERMANN – Z.- 77173
CHEVRY COSSIGNY – FRANCE
EN 60335-1
EN 60335-2-41
EN 55014-1, EN 55014-2
EN 61000-3-2, EN 61000-3-3
EN 62233:2013
Please note that it is prohibited to put this pump into service before the
machine in which it is incorporated has been declared to conform with the
provisions of machine directive 2014/35/UE and with the electromagnetic
compatibility directive 2014/30/UE
For further information: services@sauermanngroup.com
WARRANTY
2 years: https://sauermanngroup.com/en-GB/warranty
2 ans : https://sauermanngroup.com/fr-FR/garantie
24 meses : https://sauermanngroup.com/es-ES/node/1401
24 Monate : https://sauermanngroup.com/de-DE/garantie
2 anni : https://sauermanngroup.com/it-IT/node/1401
24 months: https://sauermanngroup.com/en-US/node/1401
https://sauermanngroup.com/zh-hans/node/1401
References
- Garantie | Sauermann group
- Warranty | Sauermann group
- Warranty | Sauermann group
- Warranty | Sauermann group
- Garantie | Sauermann group
- Warranty | Sauermann group
- 保修政策 | Sauermann group
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>