HYTRONIK HMW30 High Bay Microwave Motion Sensor Instruction Manual

June 6, 2024
HYTRONIK

HIGH BAY MICROWAVE MOTION SENSOR HMW30
Installation and Instruction Manual

Technical Specifications

Product type On/off control microwave motion sensor
Operating voltage  220~240VAC 50/60Hz
Rated load Capacitive: 800VA

Resistive: 1000W
Power consumption| < 0.5W
Detection angle|  360°
Detection area (Max.)*| Installation Height : 20m (forklift) 15m (person)
Detection Range (Ø) :20m
Detection range| 10% / 50% / 75% / 100%
Hold time| 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Daylight threshold| 2 ~ 500Lux, Disable
Warmming up time|  20s
Operating temperature| -20°C ~ +50°C
IP rating|  IP65

Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

Installation

Warnings:

  1. Installation of the sensor involves connecting it to the main supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.
  2. Disconnect power supply before installing.

A. Ceiling mount

B. Screw to the Luminaire by conduit

C. Attach to the shade by clamp

Rotary Switch Settings

A rotary switch is built inside the sensor for scene selection / fast programming. Total of 16 channels available:

Channel| Detection range| Hold time| Stand-by time| Stand-by dimming level| Daylight threshold
---|---|---|---|---|---
0| 100%| 5s| 10s| 10%| Disable
1| 100%| 1min| 5min| 10%| 2Lux
2| 100%| 5min| 10min| 10%| 10Lux
3| 100%| 5min| 30min| 10%| 30Lux
4| 100%| 5min| 0s| Disable| 10Lux
5| 100%| 5min| | 10%| 30Lux
6| 100%| 5min| | 30%| Disable
7| 100%| 10min| 10min| 10%| 2Lux
8| 100%| 10min| 30min| 10%| 10Lux
9| 100%| 10min| | 10%| 30Lux
A| 100%| 10min| | 30%| Disable
B| 75%| 10min| | 10%| 30Lux
C| 50%| 10min| | 10%| 10Lux
D| 100%| 30min| | 10%| 50Lux
E| 100%| 30min| | 30%| Disable
F| 100%| 5s| 10s| 10%| 2Lux

Note: settings can also be changed by remote control HRC-11. The last action controls.

Functions

4.1 On/off Control
This sensor is a motion switch, which turns on the light upon detection of motion, and turns off after a pre-selected hold-time when there is no movement. A daylight sensor is also built in to prevent the light from switching on when there is sufficient natural light.

4.2 Zero-cross Relay Operation
Designed in the software, the sensor switches on/off the load right at the zero-cross point, to ensure that the in-rush current is minimized, enabling the maximum lifetime of the relay.

Wiring Diagram

Detection Pattern

Descriptions of the Button Functions (remote control HRC-11)

Permanent ON/OFF button ⌈ 1⌉
Press button 1 to select permanent ON or permanent OFF mode.

  • Press button 2/4 to resume automatic operation.
    The mode will change to AUTO Mode after power failure.

RESET [ button 2)]
Press button 2. all settings go back to the rotary switch settings.
Shift [ button 3
Press button 3. the LED on the top left corner is on for indication. All values/settings in RED are valid for 20 seconds.
Auto Mode [ button4]
Press button 4 to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF. Note: the function of Semi-auto is disabled.
Power output [ button 5 )]
Press button 5, the light output shifts between 80% and 100%. Note: the function of ‘Sensor off” and ‘Twilight’ are disabled.
Brightness +/- [ button6)]
These two buttons are disabled.
Scene prog. [ zone7 ] (One-key-commissioning)

  1. Press the button “Start” to program.
  2. Select the buttons in 8“Detection range”, 9/10 “Daylight threshold”11, “Hold time12”, “Stand-by time13”, “Stand-by dimming level” to set all parameters.
  3. Press the button “Memory” to save all the settings programmed in the remote control.
  4. Press the button “Apply” to set the settings for each sensor unit(s).
    For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +∞, stand-by dimming level 30%, the steps should be as follows:
    Press button 7 Start, button8 100%10, Disable3, Shift, 11 5min, 3Shift12, +∞ ,13 30%, 7Memory. By pointing to the sensor unit(s) and pressing 7Apply, all settings are passed on the sensor(s).
    Detection range [ zone 8]

Press buttons in zone 8 to set detection range at 100% / 75% 50% / 10%.
Daylight threshold [ zone9 ]
Press buttons 9 in the zone to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable.
Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press the button 3 Shift at first.
Ambient daylight threshold [ button10 ] 1. Press button 3Shift, the red LED is on for indication.
2. Press button, 10the ambient lux level is sampled and set as the new daylight threshold.
Hold time [ zone11 ]
Press buttons11 in zone to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button 3 Shift at first.
2. 2s is for testing purposes only, stand-by period and daylight
sensor settings are disabled in this mode.
*To exit from Test mode, press the button or any button in the zone.

Dual tech & RF mode [ zone14 ]
All buttons in the14 zone are disabled.
Stand-by time [ zone12]
All buttons in zone12 are disabled.
Stand-by dimming level [ zone13 ]
All buttons in zone13  are disabled.

Trouble Shooting

MALFUNCTION CAUSE REMEDY

| CAUSE|

REMEDY

---|---|---
The fixture does not light up| Incorrect daylight threshold setting| Adjust daylight threshold setting
Faulty fixture| Replace fixture
No power supply| Check power to the sensor
Detection zone not targeted| Check detection area setting
The fixture is always on| Continous movement in the detection zone| Check detection area setting
The fixture is on when it should not| Sudden change in temperature due to weather (wind. rain, snow) or air expelled from fans, open windows| Adjust zone, change installation site

Hytronik Industrial Ltd. | www.hytronik.com
3rd Floor, Block C, complex building, 155#, Bai’gang road south,
Bo’gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023
Tel: 86-752-2772020 Fax: 86-752-2777877

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals