HYTRONIK HC038V Daylight Harvest PIR Sensor Instruction Manual

October 30, 2023
HYTRONIK

HYTRONIK HC038V Daylight Harvest PIR Sensor

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-product-
img

  • Daylight Harvest PIR Sensor
  • HC038V HCD038
  • Detached Linear Version with Remote Control

Applications

  • Occupancy detector with daylight harvest suitable for indoor use.
  • Suitable for building into the fixture:
  • Office / Commercial Lighting
  • Classroom
  • Use for new luminaire designs and installations

Features

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-1

Daylight harvest function to regulate light output for maintaining the required lux level

Special photocell to measure and differentiate natural light from LED light

Lux off function, daylight threshold prior to motion detection

Optional 1-10V or DALI dimming control method

One-touch daylight learning via remote control

Zero crossing detection circuit reduces the in-rush current and prolongs relay life (HC038V)

Loop-in and loop-out terminal for efficient installation (HC038V)

5-Year Warranty

Technical Data

Input Characteristics

Model No. HC038V  HCD038
Mains voltage 220~240VAC 50/60Hz
Stand-by power <0.5W
Load ratings:

HC038V

| 400VA (capacitive)

800W  (resistive)

HCD038| 30mA, 16VDC (max. 15 devices)
Warming-up| 20s

Safety and EMC

EMC standard (EMC) EN55015, EN61000
Safety standard (LVD) EN60669, AS/NZS60669

Radio Equipment (RED)

| EN300440, EN301489, EN62479
Certification| Semko, CB, CE , EMC, RED, RCM

Sensor Data

Model No.

| HIR01  HIR01/FM  HIR03

HIR09/S  HIR09/F  HIR09/C

---|---
Sensor principle| PIR Detection
Operation voltage| 5VDC
Detection range|
HIR01  HIR01/FM  HIR03|
Max installation height

Max Detection range

| 3m

6m (Diameter)

HIR09|
Max installation height| 15m (forklift)
| 12m (single person)
Max Detection range (Ø)| 24m (forklift)

20m (single person)

Detection angle| 360O

Environment

Operation temperature Ta: -20OC ~ +55OC
Case temperature (Max.) Tc: +80OC
IP rating IP20

Sensor Main Body

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-3

There are three different PIR sensor antenna modules to choose from:

  • PIR Sensor Head Model HIR01HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-4
  • PIR Sensor Head Model HIR01/FMHYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-5
  • PIR Sensor Head Model HIR03HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-6

PIR Sensor Head

HIR09/S

  • Surface mounting
  • For high-bay application
  • IP65 (facia/lens part)
  • The cable length is around 30cm.HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-7

HIR09/F

  • Flush mounting
  • For high-bay application
  • IP65 (facia/lens part)
  • The cable length is around 30cm.

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-8

HIR09/C

  • Screw to the luminaire by conduit
  • For high-bay application
  • IP65 (facia/lens part)
  • The cable length is around 30cm.

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-9

12 sensor antennas and 2 control units offer 24 combinations in total

  • A: PIR antenna HIR01 + DALI control HCD038
  • B: PIR antenna HIR01 + 1-10V control HC038V
  • C: PIR antenna HIR01/FM + DALI control HCD038
  • D: PIR antenna HIR01/FM + 1-10V control HC038V
  • E: PIR antenna HIR03 + DALI control HCD038
  • F: PIR antenna HIR03 + 1-10V control HC038V
  • G: PIR antenna HIR09/S + DALI control HCD038
  • H: PIR antenna HIR09/S + 1-10V control HC038V
  • I: PIR antenna HIR09/F + DALI control HCD038
  • J: PIR antenna HIR09/F + 1-10V control HC038V
  • K: PIR antenna HIR09/C + DALI control HCD038
  • L: PIR antenna HIR09/C + 1-10V control HC038V

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-10

Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

Functions and Features

Daylight Harvest

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-11

  • Light will not switch on when natural light is sufficient, even if there is motion detected.
  • The light switches on automatically with presence when natural light is insufficient.
  • The light turns on at full or dim to maintain the lux level.
  • The light output regulates according to the level of natural light available.

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-12

  • The light switches off when the ambient natural light is sufficient.
  • The light dims to a stand-by period after hold-time and stays on the selected minimum dimming level.
  • The light switches off completely after the standby period.

Note
The Light automatically dims down and eventually turns off if the natural light lux level exceeds the daylight threshold. However, if the stand-by period is preset at “+” , the texture never switches off but dims to a minimum level, even the natural light is sufficient.

Photocell AdvanceTM Function (HIR03)

  • It’s well known that LED lights have a totally different spectrum from natural light. Hytronik uses this principle and comes up with a special photocell and sophisticated software algorithm to measure and differentiate natural light from LED light so that this photocell can ignore the LED light and only respond to the natural light.
  • Our technology has no infringement on the existing patents in the market.

Lux Off Function

The light turns off automatically whenever the surrounding natural light lux level exceeds the daylight threshold for more than 5min, even there is motion detected. However, if the stand-by period is pre-set to infinity “+ ”, the fixture never switches off but stays at a dimming level, even when natural light is sufficient.

Manual Override
This sensor reserves access to the manual override function for the end-user to switch on/off, or adjust the target lux level by push-switch, which makes the product more user-friendly and offers more options to fit some extra- ordinary demands:

  • Short Push (<1s): on/off function;
  • On → Off: the light turns off immediately and cannot be triggered ON by motion until the expiration of pre-set hold-time. After this period, the sensor goes back to normal sensor mode.
  • Off → On the light turns on and goes to sensor mode, no matter if the ambient Lux level exceeds the daylight threshold or not.
  • Long Push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment on RC and the push switch can overwrite each other, the last adjustment remains in memory.

Note: if the end-user does not want this manual override function, just leave the “push” terminal unconnected to any wire.

Zero-cross Relay Operation (HC038V)

Designed in the software, the sensor switches on/off the load right at the zero-cross point, to ensure that the in-rush current is minimized, enabling the maximum lifetime of the relay.

Wiring Diagram

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-14

  1. 200 meters (total) max. for 1mm² CSA (Ta = 50℃)
  2. 300 metres (total) max. for 1.5mm² CSA (Ta = 50℃)

Detection Pattern

HIR01 HIR01/FM HIR03

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-15

HIR09 (High-bay)

| __**HIR09 : High-bay lens detection pattern for forklift @ Ta = 20℃ (Recommended installation height 10m-15m** )
A: Tangential movement

| B: Radial movement

| Mount height| Tangential (A)| Radial (B)
10m| max 380m2 (Ø = 22m)| max 201m2 (Ø = 16m)
11m| max 452m2 (Ø = 24m)| max 201m2 (Ø = 16m)
12m| max 452m2 (Ø = 24m)| max 201m2 (Ø = 16m)
13m| max 452m2 (Ø = 24m)| max 177m2 (Ø = 15m)
14m| max 452m2 (Ø = 24m)| max 133m2 (Ø = 13m)
15m| max 452m2 (Ø = 24m)| max 113m2 (Ø = 12m)
| __**HIR09 : High-bay lens detection pattern for single person @ Ta = 20℃ (Recommended installation height 2.5m-12m** )
A: Tangential movement

| B: Radial movement

| Mount height| Tangential (A)| Radial (B)
2.5m| max 50m2 (Ø = 8m)| max 7m2 (Ø = 3m)
6m| max 104m2 (Ø = 11.5m)| max 7m2 (Ø = 3m)
8m| max 154m2 (Ø = 14m)| max 7m2 (Ø = 3m)
10m| max 227m2 (Ø = 17m)| max 7m2 (Ø = 3m)
11m| max 269m2 (Ø = 18.5m)| max 7m2 (Ø = 3m)
12m| max 314m2 (Ø = 20m)| max 7m2 (Ø = 3m)

Settings (Remote Control HRC-11, for HIR01/FM & HIR03 & HIR09)

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-28

Permanent ON/OFF function

  • Press the button “ON/OFF” to select permanent ON or permanent OFF mode.
  • Press buttons “AUTO”, “RESET” or “Ambient” to quit this mode.
  • The mode will change to AUTO Mode after power failure.

Reset Settings

  • Press the button “RESET”, and all settings go back to default values.
  • For HIR01/FM: Detection range: 100%; Hold-time: 5min; Stand-by period: 10min;
  • Stand-by dimming level: 20%; Constant lux: 100lux
  • For HIR03: Detection range: 100%; Hold-time: 5min; Stand-by period: 10min;
  • Stand-by dimming level:10%; Lux disabled
  • For HIR09: Detection range: 100%; Hold-time: 5min; Stand-by period: 10min;
  • Stand-by dimming level: 20%; Constant lux: 100lux

Shift Button

  • Press the button “Shift”, the LED on the top left corner is on to indicate mode selection. All values/settings in RED are valid for 20 seconds.

AUTO mode

  • Press the button “AUTO” to initiate automatic mode. The sensor starts working and all settings remain as before the light is switched ON/OFF.

SEMI-AUTO mode

  1. Press the button “Shift”, and the red LED flashes for indication.
  2. Press the button “SEMI-AUTO/AUTO” to initiate semi-auto mode. The fixture is manually turned on by pressing the push switch and goes off automatically after standby time. (Absence detection mode)

Power output

  • Press the buttons to select light output at 80% (at initial 10,000 hours) or 100%.
  • Note: “Sensor off” and “Twilight” functions are disabled.

Brightness +/-

  • Press these two buttons to adjust the light output brightness and set a new target lux level. The daylight sensor can measure ambient daylight level and ignore the LED light, so as to calculate how much artificial light is needed to maintain the target lux level.

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-27Scene program – 1-key commissioning

  1. Press the button “Start” to program.
  2. Select the buttons in “Detection range”, “Daylight threshold”, “Hold-time”, “Stand-by time”, and “Stand-by dimming level” to set all parameters.
  3. Press the button “Memory” to save all the settings programmed in the remote control.
  4. Press the button “Apply” to set the settings for each sensor unit(s).
    For example, to set detection range 100%, daylight threshold Disable, hold- time 5min, stand-by time + , stand-by dimming level 30%, the steps should be:
    Press buttons “Start”, button ”100%”, “Disable”, “Shift”, “5min”, “Shift”, “+ ”, “30%”, and “Memory”. By pointing to the sensor unit(s) and pressing “Apply”, all settings are passed on to the sensor(s).

Detection range
Buttons in zone “Detection range” are disabled.

Daylight threshold

Press buttons in the zone “ Daylight threshold” to set the daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable.
Note: To set the daylight sensor at 100Lux / 300Lux / 500Lux, press the “Shift” button first.

Ambient daylight threshold

  1. Press the button “Shift”, and the red LED starts to flash.
  2. Press the button “Ambient”, the surrounding lux level is sampled and set as the new daylight threshold.

Hold-time

  • Press buttons in zone “hold-time” to set the hold-time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
  • Note: To set hold-time at the 30s / 5min / 15min / 30min, press the “Shift” button first.
  • 2s is for testing purposes only, the stand-by period and daylight sensor settings are disabled in this mode.
  • To exit from Test mode, press the button “RESET” or any button in “Hold-time”.

Stand-by time (corridor function)

  • Press buttons in the zone “stand-by time” to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / + .
  • Note: “0s” means on/off control; “+ ” means the stand-by time is infinite and the texture never switches off.

Stand-by dimming level

  • Press the button in the zone “stand-by dimming level” to set the stand-by dimming level at 10% / 20% / 30% / 50%.

Auto-configuration function

  • All buttons in this zone are disabled.

Dual tech & RF mode

All buttons in this zone are disabled.

Settings (Remote Control HRC-01, for HIR01)

HYTRONIK-HC038V-Daylight-Harvest-PIR-Sensor-fig-31

Note: the buzzer beeps one time when RC receives the signal successfully.

Permanent ON/OFF function

  • Press the “ON/OFF” button, the light goes to permanent on or permanent off mode, and the sensor is disabled.
  • Press the “Auto Mode”, “RESET” or “Scene Mode” buttons to quit this mode.
  • The mode will change to AUTO Mode after power failure.

Sensor mode

  • Press the “Auto Mode” button, the sensor starts to function and all settings remain the same as the latest status before the light is switched on/off.

Reset function

  • Press the “RESET” button, all settings go back to the default value (same as scene mode 3):
  • Detection range: 100%; Hold-time: 5min; Stand-by period: 10min;
  • Stand-by dimming level: 20%; Constant lux: 100lux

Dim +/-

  • Press these two buttons to adjust the light output brightness and set a new target lux level.
  • The daylight sensor can measure ambient daylight level and ignore the LED light, so as to calculate how much artificial light is needed to maintain the target lux level.

Test mode

  • This button is for testing purposes only. The sensor goes to test mode (hold-time is 2s) after commissioning, meanwhile, the stand-by period and daylight sensor are disabled.
  • This mode can be ended by pressing “reset”, or any button of “scene mode” and “hold-time”. The sensor settings are changed accordingly.

8H permanent on mode

  • In some circumstances, people want to disable the sensor and keep the light on for a certain period of time, even if there is no motion detected. This function is built-in in the software and can be achieved by pressing the “8H” button on the RC.
  • Press the “ON/OFF”, “Auto Mode”, “RESET” or “Scene mode” buttons to quit this mode.

Scene mode

There are 6 scene modes fixed programs built-in the remote control to choose for different applications.

Scene options| Hold-time| Stand-by period| Stand-by dimming level| Constant Lux| Detection range
---|---|---|---|---|---
SC1| 1min| 1min| 10%| 50Lux| disabled
SC2| 3min| 5min| 20%| 75Lux| disabled
SC3| 5min| 10min| 20%| 100Lux| disabled
SC4| 10min| 30min| 30%| 150Lux| disabled
SC5| 20min| 1H| 30%| 200Lux| disabled
SC6| 30min| +∞| 50%| 400Lux| disabled

  • End-user can adjust the settings by pressing buttons of detection range/hold-time/stand-by period/stand-by dimming level/daylight sensor. The last setting stays invalid.

Hold-time

  • Press the buttons of “hold-time” to set hold-time at 30s / 1min / 5min / 10min / 20min / 30min.

Stand-by period (Corridor function)

  • Press the buttons of “stand-by period ( corridor function)” to set the stand-by period at 0s/10s/1min/5min/10min/30min/1H/+ .
  • Note: “0s” means on/off control; “+ ” means bi-level dimming control and the texture never switches off.

Stand-by dimming level

  • Press the buttons of “stand-by dimming level” to set the stand-by dimming level at 10%/20%/30%/50%.

Detection range

  • Buttons of “detection range” are disabled.

Additional Information / Documents

  1. For a full explanation of Hytronik Photocell AdvanceTM technology, please kindly refer to  www.hytronik.com/download ->knowledge ->Introduction of Photocell Advance
  2. Regarding precautions for microwave sensor installation and operation, please kindly refer to  www.hytronik.com/download ->knowledge ->Microwave Sensors – Precautions for Product Installation and Operation
  3. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy