legrand PDX-915R, PDX-920R Rack Mounted Power Distribution Unit User Manual
- July 13, 2024
- Legrand
Table of Contents
- legrand PDX-915R, PDX-920R Rack Mounted Power Distribution Unit
- Product Information
- Product Usage Instructions
- IMPORTANT SAFETY INSTRUCTIONS
- Understanding Safety Symbols
- Safety Instructions: Rack Mount
- Regulatory Compliance
- Federal Communications Commission (FCC) Statement
- Waste Electrical and Electronic Equipment (WEEE) Directive
- Understanding General Symbols and Terms
- Supplied Components and Hardware
- Required Tools
- 2 Phillips Screwdriver
- Introduction
- Mounting Your NEXSYS Series Rackmount PDU
- Feature Set
- LED Protection Indicators
- Specifications
- Warranty
- FAQ
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
legrand PDX-915R, PDX-920R Rack Mounted Power Distribution Unit
Product Information
Specifications
The Rackmount PDU is part of the NEXSYS Series and comes with surge protection features.
Feature Set
The PDU includes LED protection indicators, surge protection, and voltage protection.
Hardware Features
The PDU is designed for rackmount installation and comes with the necessary mounting hardware.
Physical Specifications
- Dimensions: Vary based on model
- Weight: Varies based on model
- Color: Black
Product Usage Instructions
Installation
- Read the user manual carefully.
- Ensure the power outlet is properly grounded before connecting the PDU.
- Mount the PDU securely in a rack according to the provided instructions.
Operation
Once installed, connect your electronic devices to the PDU for power distribution.
Maintenance
Regularly check the LED protection indicators for any alerts. Keep the PDU clean and free from obstructions.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the product.
-
Only use attachments and accessories specified by the manufacturer.
-
Read all instructions before using the product.
Understanding Safety Symbols
Safety Instructions: Rack Mount
Elevated Operating Ambient: If installed in a closed-ed or multi-unit
rack assembly, the operating ambient temperature of the rack environment may
be greater than room ambient. Therefore, consideration should be given to
installing the equipment in an environment compatible with the maximum ambient
temperature (Tma) specified by the manufacturer.
Reduced Air Flow: Installation of the equipment in a rack should be such
that the amount of airflow required for safe operation of the equipment is not
compromised.
Mechanical Loading: Mounting of the equipment in the rack should be such
that a hazardous condition is not achieved due to uneven mechanical loading.
Circuit Overloading: Consideration should be given to the connection of the
equipment to the supply circuit and the effect that overloading of the circuit
might have on overcurrent protection and supply wiring. Appropriate
consideration of equipment nameplate ratings should be used when addressing
this concern.
Reliable Earthing: Reliable earthing of rack-mounting equipment should be
maintained. Particular attention should be given to supply connections other
than direct connections to the branch circuit (e.g. use of power strips).
Disconnect Device (Pluggable Equipment): The socket outlet shall be installed
near the equipment and shall be easily accessible.
When using electrical products, basic precautions should always be followed,
including the following:
- Read and follow all instructions before using.
- There are no user-serviceable components within this device. Removal of the cover from this device may present a shock hazard, and void the warranty.
- The mains plug is used as your disconnect device. This device shall remain readily operable.
- Unplug this apparatus during lightning storms or when unused for long periods.
- Do not overload the wall outlet where this device is being connected. Do not overload this device. Ensure the total load to this device does not exceed that which is listed in the specifications section of this manual.
- Ensure this device is connected to a properly grounded AC power source. Ensure the device is plugged into a source providing the required 120V. Do not use a plug adapter that defeats the ground pin of the AC plug.
Regulatory Compliance
Federal Communications Commission (FCC) Statement
Industry Canada (IC)
ICES-003 Class B Notice. This Class B digital apparatus complies with Canadian
ICES-003.
Industrie Canada (IC)
ICES-003 Avis NMB-003, Classe B. Cet appareil numérique de la classe B est
conforme à la norme NMB-003 du Canada.
Waste Electrical and Electronic Equipment (WEEE) Directive
Correct disposal of this product: This symbol indicates that this product must not be disposed of with household waste, according to the WEEE Directive (2012/19/EU) and your national law. This product should be taken to a collection center licensed for the recycling of waste electrical and electronic equipment (EEE). The mishandling of this type of waste could have a possible negative impact on the environment and human health due to potentially hazardous substances that are generally associated with EEE. At the same time, your cooperation in the correct disposal of this product will contribute to the efficient use of natural resources. For more information about where you can take your waste equipment for recycling, please contact your local city office or your household waste collection service.
Understanding General Symbols and Terms
Supplied Components and Hardware
After carefully opening all product packaging, identify the supplied components and hardware shown. If any pieces are missing or damaged, please report it immediately to Technical Support at av.middleatlantic.techsupport@legrand.com or 866-977-3901. Keep the original packaging in a safe place for future use.
Required Tools
2 Phillips Screwdriver
Introduction
This User Manual provides information about the installation, setup, and configuration of your NEXSYS Series Rackmount PDU product.
Mounting Your NEXSYS Series Rackmount PDU
- Use a #2 Phillips screwdriver and (4x) rack screws (not provided) through holes on the pre-installed ears and into the threaded holes on the rackrail to mount your NEXSYS Rackmount PDU as shown.
- Install the power cord retainer (C) by pressing inward on its sides and hooking the ends through the input post holes on the back of the unit as shown.
- Use the power cord to connect your Rackmount PDU from the AC input into an outlet on an appropriately rated receptacle.
Feature Set
-
A. Light Well
White: On, indicating power to the outlets.
Off: Off, no power to the outlets. -
B. Power Button
White: On
Amber: Off -
C. Surge LED Indicator
Surge indicator signals different protection statuses of your PDU. For more information, see LED Protection Indicators, on page 18. -
D. Voltage Protection LED Indicator and Button
Voltage indicator signals different PDU protection statuses. For more information, see LED Protection Indicators, on page 18.
Press to enable or disable voltage protection.
White: Voltage protection enabled.
Off: Voltage protection disabled. -
E. Remote LED Indicator and Button
Press to enable or disable the remote contact control.
White: Remote Enabled
Off: Remote Disabled -
F. Convenience Outlet
-
G. Input Circuit Breaker
-
Located next to the AC input, the input circuit breaker trips when the load exceeds the PDU power rating.
H. AC Input -
I. EC14 (for 15A) or IEC20 (for 20A) inlet based on the model purchased.
-
J. AC Input Retainer Clip
Use clip to secure the power cord into the IEC Inlet. -
K. Indicator Light
Green LED indicates power to the outlets. -
L. Status (Output)
NOTE
Terminal Block plug pre-installed on PDU.
For MOV Models: When contact is open, indicates the surge status is protected. When contact is closed, indicates the surge is compromised and no longer protected.
For Series Protection Models: When contact is open, indicates the unit is powered Off. When the contact is closed, indicates the unit is powered on. -
M. Remote (Input)
NOTE
Terminal Block plug with jumper pre-installed on PDU.
When enabled, outlets may be turned On or Off via contact closure.
When contact is closed, the outlets are turned On.
When contact is opened, the outlets are turned Off. -
N. Outlets
All outlets are controllable by a power button and remote contact.
P. External Grounding and Bonding Stud
For connecting an external ground wire to bond the chassis.
LED Protection Indicators
Specifications
Specifications for MOV Surge Models
Summary
Model | PDX-915R | PDX-920R |
---|---|---|
Nominal Voltage | 120VAC | |
Voltage Range | Minimum: 80VAC, Maximum: 140VAC | |
Frequency | 60 Hz | |
Maximum Peak Load | 15A | 20A |
Rated Load | 12A | 16A |
Number of Outlets | 9 | |
Outlet Type | NEMA 5-15R | NEMA 5-20R |
Overload Protection | Circuit Breaker | |
Outlet Control | Contact Closure | |
No Load Power Dissipation | __ |
< 1W
__
Input Power Cord
| SignalSAFE IEC to 5-15P, 10’ (3M)| SignalSAFE IEC to 5-20P, 10’ (3M)
Certifications| UL 62368, UL 1449, FCC Class B, ICES 7
Hardware Features
Model PDX-915R and PDX-920R
Surge Protection| Multi-Stage MOV
__
Peak Impulse Current
(8/20µS Waveform)
| 45,000 Amps, one time – Maximum peak impulse current pulse as defined
between line and neutral. 19,500 Amps, two times within 5 minutes – Maximum
multiple impulse current derated per spec.
Protection Mode| Line to Neutral only; no ground contamination.
Model PDX-915R and PDX-920R
Response Time| Less than 1 nanosecond.
Surge Energy Dissipation| __
705 Joules (10/100µS)
Voltage Protection Rating| __
500V (L-N); Type 3 SPD
__
EMI/RF Suppression
| >20dB Calculated Line to Neutral – 100kHz to 1Mhz – based on nominal
impedance.
__
Overvoltage Threshold
| Upper Limit Cutoff: 135V RMS
__
Upper Limit Restore: 126V RMS
Undervoltage Threshold| Lower Limit Cutoff: 100V RMS
__
Lower Limit Restore: 105V RMS
Physical
Model PDX-915R PDX-920R
Dimensions
(Width x Height x Depth)
| __
19” (483mm) x 1.735” (44mm) x 8.75” (222mm)
Product Weight| 6.84 lbs (3.1 kg)
Shipping Weight| 9.92 lb (4.5 kg) 10.58
lb (4.8 kg)
Warranty
Model PDX-915R and PDX-920R
__
Power Distribution
| Three Years Limited
For warranty information, refer to www.legrandav.com/policies/warranty_ information.
Specifications for Series Surge Protection Models
Summary
Model PDX-915R-SP PDX-920R-SP
Nominal Voltage| 120VAC
Voltage Range| Minimum: 80VAC, Maximum: 140VAC
Frequency| 60 Hz
Maximum Peak Load| 15A
20A
Rated Load| 12A 16A
Number of Outlets| 9
Outlet Type| NEMA 5-15R NEMA 5-20R
Overload Protection| Circuit Breaker
Outlet Control| Contact Closure
Model PDX-915R-SP PDX-920R-SP
No Load Power Dissipation| __
<1W
__
Input Power Cord
| SignalSAFE IEC to 5-15P, 10’ SignalSAFE IEC to 5-20P, 10’ (3M)
(3M)
Certifications| UL 62368, UL 1283, UL 1449, FCC Class B, ICES 7
Hardware Features
Model PDX-915R-SP PDX-920R-SP
Surge Protection| Series
Voltage Protection Rating| __
330V (L-N); Type 3 SPD
Maximum Applied Surge Voltage| 6000 Volts (1.2 x 50µS Pulse, Industry Standard
Combination Wave Per IEEEC62.41)
Maximum Applied Surge Current| __
Unlimited (Due to Inherent Current Limiting)
Maximum Applied Surge Energy| __
Unlimited (Due to Inherent Current Limiting)
EMI Filter, Differential Mode| __
40dB@100kHz 50dB@100kHz
50Ω Load| 50dB@3MHz 50dB@30MHz
EMI Filter, Common Mode| __
18dB@100kHz 30dB@100kHz
50Ω Load| 50dB@3MHz 50dB@30MHz
__
Overvoltage Threshold
| Upper Limit Cutoff: 135V RMS
__
Upper Limit Restore: 126V RMS
Undervoltage Threshold| Lower Limit Cutoff: 100V RMS
__
Lower Limit Restore: 105V RMS
Physical
Model PDX-915R-SP PDX-920R-SP
Dimensions
(Width x Height x Depth)
| __
19” (483mm) x 1.735” (44mm) x 8.75” (222mm)
Product Weight| 8.6 lb. (3.9 kg)
Shipping Weight| 11.47 lb. (5.2 kg) 12.35
lb. (5.6 kg)
Warranty
Model PDX-915R-SP and PDX-920R-SP
__
Series Surge Module
| Twelve Years Limited
For warranty information, refer to www.legrandav.com/policies/warranty_ information.
Warranty
For warranty information, refer to
www.legrandav.com/policies/warranty_information.
Contacting Corporate Headquarters
P: 866-977-3901 | F:
877-894-6918 |
www.legrandav.com |
av.middleatlantic.techsupport@legrand.com
Contacting Middle Atlantic Canada
P: 888-766-9770 | F:
888-599-5009 |
www.legrandav.com |
av.canada.customerservice@legrand.com
United States (US) Legrand | AV Headquarters 6436 City West Parkway Eden Prairie, MN, 55344, USA
At Legrand AV Inc. we are always listening. Your comments are welcome. Legrand AV is an ISO 9001 and ISO 14001 Registered Company.
Information in this document is subject to change without notice. The AV equipment described in this document is furnished under a license agreement or nondisclosure agreement. The equipment may be used or copied only by the terms of those agreements. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or any means electronic or mechanical, including photocopying and recording for any purpose other than the purchaser’s personal use without the written permission of Legrand AV.
Middle Atlantic is a brand of Legrand AV.
www.legrandav.com | Phone:
866-977-3901 | Fax:
877-894-6918 | Email:
av.middleatlantic.techsupport@legrand.com
Visit us at www.legrandav.com for firmware
updates, specifications, drawings, manuals, technical support information, and
more.
Middle Atlantic is a registered trademark of Legrand AV, Inc.
Legrand AV is an ISO 9001 and ISO 14001 Registered Company.
All other brand names or marks are used for identification purposes and are
trademarks of their respective owners.
All patents are protected under existing designations. Other patents pending.
Legrand AV Inc. Brands: Chief | Da-Lite | Middle Atlantic | Projecta | Sanus |
Vaddio
FAQ
Q: What should I do if the LED protection indicators show an alert?
A: If any LED protection indicator lights up, immediately disconnect the connected devices and contact customer support for assistance.
Q: Can I mount the PDU in any orientation?
A: The PDU is designed for rackmount installation and should be mounted following the provided instructions to ensure proper functionality.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>