HYTRONIK HCD405-BT Motion Sensor Instruction Manual

October 30, 2023
HYTRONIK

HYTRONIK HCD405-BT Motion Sensor Instruction Manual
Motion Sensor

Product Description

HCD405/BT is a Bluetooth built-in microwave sensor with 30mA DALI power supply built in. It is designed for professional lighting manufactures who would like to incorporate wireless control into their luminaires. It is suitable for any typical indoor applications such as office, classroom, car park, warehouse and other commercial/industrial areas. With Bluetooth wireless mesh networking, it makes communication much easier without any hardwiring, which eventually adds values to luminaires and saves costs for projects. Meanwhile, simple device setup and commissioning can be done via app.

App Features

 Quick setup mode & advanced setup mode
Floorplan feature to simplify project planning
 Web app/platform for dedicated project management
 Koolmesh Pro iPad version for on-site configuration
 Grouping luminaires via mesh network
 Scenes
 Detailed motion sensor settings
 Dusk/Dawn photocell (Twilight function)
 Schedule to run scenes based on time and date
 Astro timer (sunrise and sunset)
 Staircase function (primary & secondary)
 Compatible with EnOcean BLE switches
 Internet-of-Things (IoT) featured
 Device firmware update over-the-air (OTA)
 Device social relations check
 Bulk commissioning (copy and paste settings)
 Offiine commissioning
 Different permission levels via authority management
 Network sharing via QR code or keycode
 Remote control via gateway support HBGW01
 Interoperability with Hytronik Bluetooth product portfolio
 Continuous development in progress…

Hardware Features
 Photocell Advance
DALI Dimmable with 30mA DALI broadcast output for up to 15 LED drivers
 Plug’n’Play for fiexible installation and cost saving assemble
 Support to control DT8 LED drivers
 Zero crossing detection circuit reduces in-rush current and prolongs relay life
 5-year warranty

Smartphone app for both iOS & Android platform

Koolmesh Pro app for iPad

Web app/platform: www.iot.koolmesh.com

www.iot.koolmesh.com

Technical Specifications

Bluetooth Transceiver

Operation frequency| 2.4 GHz – 2.483 GHz
Transmission power| 4 dBm
Range (Typical indoor)| 10~30m
Protocol| 5.0 SIG Mesh
Sensor Data

Sensor principle| High Frequency (microwave)
Operation frequency| 5.8GHz+/-75MHz
Transmission power| <0.2mW
Detection range(Max.)| Max installation height: 6m
Max detection range:10m (diameter
Detection angle| 30°~150°
Input & Output Characteristics

Operating voltage| 220~240VAC 50/60Hz
Stand-by power| <1W
Load ratings:| 30mA (max. 15 devices)
Warming-up| 20s
Safety & EMC

EMC standard (EMC)| EN55015, EN61000, EN61547
Safety standard (LVD)| EN60669-1, EN60669-2-1
RED| EN300328, EN301489-1/-17
Certication| Semko, CB, CE , EMC, RED, RCM
Environment

Operation temperature| Ta: -20 O C ~ +55 O C
Case temperature (Max.)| Tc: +75 O
C
IP rating| IP20

***** The detection range is heavily infiuenced by sensor placement (angle) and different walking paces. It may be reduced under certain conditions.

Mechanical Structure & Dimensions

Structure
Dimensions
Structure
Dimensions

**Wire Preparation

**

To make or release the wire from the terminal, use a screwdriver to push down the button.

  1. 200 metres (total) max. for 1mm² CSA (Ta = 50℃)
  2. 300 metres (total) max. for 1.5mm² CSA (Ta = 50℃)

Wiring Diagram
Wiring Diagram

Detection Pattern
Detection Pattern
Detection Pattern

Additional Information / Documents

  1. For full explanation of Hytronik Photocell AdvanceTM technology, please kindly refer to
    www.hytronik.com/download ->knowledge ->Introduction of Photocell Advance

  2. To learn more about detailed product features/functions, please refer to
    www.hytronik.com/download ->knowledge ->Introduction of App Scenes and Product Functions

  3. Regarding precautions for Bluetooth product installation and operation, please kindly refer to
    www.hytronik.com/download ->knowledge ->Bluetooth Products – Precautions for Product Installation and Operation

  4. Regarding precautions for microwave sensor installation and operation, please kindly refer to
    www.hytronik.com/download ->knowledge ->Microwave Sensors – Precautions for Product Installation and Operation

  5. Data sheet is subject to change without notice. Please always refer to the most recent release on
    www.hytronik.com/products/bluetooth technology ->Bluetooth Sensors

  6. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy

Icons

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals