BELLlighting 09040V2 Emergency Bulkhead Installation Guide
- July 30, 2024
- BELLlighting
Table of Contents
BELLlighting 09040V2 Emergency Bulkhead
Specification
- Operating environmental temp: O to +40°C.
- Operating relative humidity: less than 90%.
- Rated voltage: 220-240V 50/60Hz.
- Wattage: 3.3W.
- Conversion time: 1 second.
- LED: SMT 2835 LED*8pcs.
- Lumens: 1401m.
- Emergency duration: more than 180 minutes.
- Battery installed or replaced: LiFePO4 3.2V 1500mah
- Recharge time: 24 hours.
Important Information
We recommend that luminaires are installed by a qualified electrician ensuring the installation complies with current IEE wiring regulations BS7671:2018 & local building control.
- All tests should be carried out in accordance to EN 50172:2004.
- BELL will not accept responsibility for any claims arising from a poor installation.
- The light source of this luminaire is not replaceable: when the light source reaches end of life, the whole luminaire must be replaced.
Important User Advice
- The ambient room temperature should not exceed 30°C.
- Ensure that there is adequate free air ventilation around the fitting.
- Always switch off mains supply before installing.
Installation Instructions: Emergency Bulkhead (09040V2)
Read these instructions before installation and retain for future reference This equipment should be installed by a competent electrician
Installation :
- Connect mains supply a wiring as follows L(Live) N(Neutral)
- Power line & battery wires should be connected securely, and all screws fixed.
- Switch on 220-240V AC supply and check if the green LED indicator illuminates to confirm charging of batteries.
- Allow a short period for part charging of the batteries and then isolate the mains supply to the fitting in order to check the correct operation of the fitting in emergency mode. In the first use, after a continuous charge for 24 hours. a mains failure should be simulated to ensure that the fitting work for its specified time (only at a safe & appropriate time). The fitting will be fully charged with 24 hours continuous charging.
The instruction of the switch on PCB.
On indicates standard mode:
- indicates self-test mode
Please make sure that switch position is set before installation.
RECOMMENDED ROUTINE TEST PROCEDURE
The following test are designed to ensure the continued protection of your
premises and occupants. Because of the possibility of a failure of the normal
lighting supply occurring shortly after a period of testing, all tests should,
whenever possible, be undertaken at times of least risk. e.g. during daylight
hours.
ONCE ADAY
Visual inspection of battery charge led.
ONCE A MONTH
Each unit should be energised from it’s battery for adequate time to ensure,
by simulation of a failure of the normal lighting supply, the emergency mode
is functioning correctly.
ONCE EACH YEAR
All units should be placed into emergency mode and checked that the duration
provided by the battery meets the specified time period.
This product may contain substances that can be hazardous to the environment if not disposed of properly. Electrical and electronic equipment should never be disposed of with general household waste but must be separated for its correct treatment and recovery. Where possible recycle your packaging.
Self-Test
Self-Test fittings perform a self-commissioning test at first power on. After
charging for 24 hours a full duration test (3 hours) is performed. Initial
function and duration tests are randomly generated. They are then performed in
accordance with standard requirements (every 30 days for function tests and
every 52 weeks for duration tests). A single bi-colour indicator LED is titted
in all Self-Test products. This LED is clearly visible for manual inspection.
It indicates the module status. The LED shows permanent green or flashing
green when conditions are normal and flashing red if a fault condition is
present
Function test
A function test is a 2 minutes test that simulates a mains failure and checks
the operation of the emergency light source from the battery supply. The local
indicator LED slow flashes green whilst the 2 minutes function test is in
progress. If there is a failure during a function test the local indicator LED
changes to a flashing red.
Duration test
A duration test simulates a mains failure. It also checks the operation of the
emergency light source from the battery supply for the rated duration of the
module. The local indicator LED fast flashes green whilst the duration test is
in progress. If there is a failure during a duration test the local indicator
LED either changes to flashing red. The battery is required to be fully
charged before a duration test can be started.
The test button of the unit has the following functions:
Please refer to following chart below for more complete description/fault indication:
British Electric Lamps Ltd
BELL House, Foxbridge Way, Normanton Industrial Estate Normanton, West
Yorkshire. WF6 1TN
T: +44 (0)1924 893380
F: +44 (0)1924 894320
E:sales@belllighting.co.uk
Technical Helpline +44 (0)1924 893380
www.belllighting.co.uk