HYTRONIK HIM31 High Bay Dual Sense Sensor Instruction Manual
- June 6, 2024
- HYTRONIK
Table of Contents
HYTRONIK HIM31 High Bay Dual Sense Sensor
Technical Specifications
Product type | Tri-level control dual sense sensor |
---|---|
Operating voltage | 220-240VAC 50/60Hz |
Rated load
| 800VA(Capacitive)
1000W(Resistive)
Power consumption| < 1W
Detection angle| 360o
Detection area (Max.)*| Installation Height : 15m Detection Range (Ø) :18m
Detection range| 10% / 50% / 75% / 100%
Hold time| 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time| 0s / 10s / 1min / 5min / 10min / 30min / 1h / + ∞
Stand-by dimming level| 10% / 20% / 30% / 50%
Daylight threshold| 2 ~ 500Lux, Disable
Warmming up time| 30s
Operating temperature| -30oC ~ +50oC
IP rating| IP65
Sensor mode| HF, PIR, HF+PIR, HF / PIR
Rotary Switch Settings
A rotary switch is built inside the sensor for scene selection / fast programming. Total of 16 channels available:
Channel
| Detection range| Hold time| Stand-by time| Stand-by dimming level| Daylight
threshold
---|---|---|---|---|---
0| 100%| 5s| 10s| 10%| Disable
1| 100%| 1min| 5min| 10%| 2Lux
2| 100%| 5min| 10min| 10%| 10Lux
3| 100%| 5min| 30min| 10%| 30Lux
4| 100%| 5min| 0s| Disable| 10Lux
5| 100%| 5min| +∞| 10%| 30Lux
6| 100%| 5min| +∞| 30%| Disable
7| 100%| 10min| 10min| 10%| 2Lux
8| 100%| 10min| 30min| 10%| 10Lux
9| 100%| 10min| +∞| 10%| 30Lux
A| 100%| 10min| +∞| 30%| Disable
B| 75%| 10min| +∞| 10%| 30Lux
C| 50%| 10min| +∞| 10%| 10Lux
D| 100%| 30min| +∞| 10%| 50Lux
E| 100%| 30min| +∞| 30%| Disable
F| 100%| 5s| 10s| 10%| 2Lux
Functions
-
3.1 Tri-level Control (Corridor Function)
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas it requires a light change notice before switch-off. It offers 3 levels of light: 100%–>dimmed light–>off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area. -
3.2 Lux Off Function
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically whenever artificial light is unnecessary (natural light lux level exceeds daylight threshold).
Note: if the stand-by time is preset at “+∞”, the fixture never switches off even when natural light is sufficient. -
3.3 Load Indication
The light will flash ONCE rapidly after receiving the command from the remote controller. Note: There is no load indication (the light will not flash) when button ON/OFF, POWER 100% or POWER 80% is pressed.
Installation
Warnings:
- Installation of the sensor involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.
- Disconnect power supply before installing.
- Ceiling mount
- Screw to the Luminaire by conduit
- Attach to the shade by clamp
Note : We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.
Wiring Diagram
Three Options for PIR Lens and Detection Patterns
(End user can choose the suitable lens in real application for various requirements) * For single person walking across, the detection range is reduced by 1/3.
Descriptions of the
Button Functions (remote control HRC-11)
-
Permanent ON/OFF [button 1 ]
Press button 1 to select permanent ON or permanent OFF mode. Press button 2/4 to resume automatic operation.The mode will change to AUTO Mode after power failure. -
RESET [ button 2]
Press button 2, all settings go back to the rotary switch settings. -
Shift [ button 3 ]
Press buttonB, the LED on the top left corner is on for indication. All values/settings in RED are valid for 20 seconds. -
Auto Mode [ button 4] Press button 4 to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
Note : the function of Semi-auto is disabled -
Power output [ button 5] Press button 5 , the light output shifts between 80% and 100%.
Note : the function of “Sensor off” and “Twilight” are disabled. -
Brightness +/- [ button 6 ]
Press button 6 to adjust the light brightness between 10%~100% Scene prog. [ zone 7 ] (One-key-commissioning)
- Press button “Start” to program.
- Select the buttons in 8“Detection range”, 9/ 10“Daylight threshold”,11“Hold time”, “Stand-by time”, “Stand-by dimming level” to set all parameters.
- Press button “Memory” to save all the settings programmed in the remote control.
- Press button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +, stand-by dimming level 30%, the steps should be as follows: Press button 7 Start, button 8 100%,10 Disable, 3 Shift, 11 5min, 3 Shift, +12+ , 30%, 7 Memory. By pointing to the sensor unit(s) and pressing 7 Apply, all settings are passed on the sensor(s).
-
Detection range [ zone 8 ]
Press buttons in zone 8 to set detection range at 100% / 75% / 50% / 10%. -
Daylight threshold [ zone 9 ]
Press buttons in zone 9 to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable.
Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button Shift 3 at first. -
Ambient daylight threshold [ button 10 ]
1. Press button 3 Shift, the red LED is on for indication.
2. Press button 10 , the ambient lux level is sampled and set as the new daylight threshold. -
Hold time [ zone 11 ]
Press buttons in zone 11 to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button Shift 3at first.
2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode. *To exit from Test mode, press button 2 or any button in zone 11 . -
Stand-by time [ zone 12]
Press buttons in zone 12 to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h /
Note : “0s” means on/off control; “+” means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence is detected after hold-time. -
Stand-by dimming level [ zone 13 ]
Press buttons in zone 13 to set the stand-by dimming level at 10% / 20% / 30% / 50%.
Note.the function of 24h / 12h / 4h / 30s are disabled. -
Dual tech [ zone 14 ] Press buttons in zone 14 to select sensor technology. HF+PIR: Light is on when both HF and PIR sensors are activated. HF/PIR: Light is on when HF or PIR sensors are activated
-
RF mode [ zone 15 ]
All buttons in zone 15 are disabled.
Trouble Shooting
MALFUNCTION CAUSE REMEDY | CAUSE | REMEDY |
---|
The fixture does not light up
| Incorrect daylight threshold setting| Adjust daylight threshold setting
Faulty fixture| Replace fixture
No power supply| Check power to sensor
Detection zone not targeted| Check detection area setting
The fixture is always on| Continous movement in the detection zone| Check
detection area setting
The fixture is on when it should not
| Sudden change in temperature due to weather (wind, rain, snow) or air expelled from fans, open windows|
Adjust zone, change installation site
Hytronik Industrial Ltd. | www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai’gang road south,
Bo’gang village, Xiao Jin Kou town,Huicheng district, Huizhou 516023
Tel : 86-752-2772020 Fax : 86-752-2777877
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>