HYTRONIK HIM31 High Bay Dual Sense Sensor Instruction Manual

June 6, 2024
HYTRONIK

HYTRONIK HIM31 High Bay Dual Sense Sensor LOGO

HYTRONIK HIM31 High Bay Dual Sense Sensor

HYTRONIK HIM31 High Bay Dual Sense Sensor IMAGE

Technical Specifications

Product type Tri-level control dual sense sensor
Operating voltage 220-240VAC 50/60Hz

Rated load

| 800VA(Capacitive)

1000W(Resistive)

Power consumption| < 1W
Detection angle| 360o
Detection area (Max.)*| Installation Height : 15m Detection Range (Ø) :18m
Detection range| 10% / 50% / 75% / 100%
Hold time| 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time| 0s / 10s / 1min / 5min / 10min / 30min / 1h / + ∞
Stand-by dimming level| 10% / 20% / 30% / 50%
Daylight threshold| 2 ~ 500Lux, Disable
Warmming up time| 30s
Operating temperature| -30oC ~ +50oC
IP rating| IP65
Sensor mode| HF, PIR, HF+PIR, HF / PIR

Rotary Switch Settings

A rotary switch is built inside the sensor for scene selection / fast programming. Total of 16 channels available:

HYTRONIK HIM31 High Bay Dual Sense Sensor FIG 1

Channel

| Detection range| Hold time| Stand-by time| Stand-by dimming level| Daylight threshold
---|---|---|---|---|---
0| 100%| 5s| 10s| 10%| Disable
1| 100%| 1min| 5min| 10%| 2Lux
2| 100%| 5min| 10min| 10%| 10Lux
3| 100%| 5min| 30min| 10%| 30Lux
4| 100%| 5min| 0s| Disable| 10Lux
5| 100%| 5min| +∞| 10%| 30Lux
6| 100%| 5min| +∞| 30%| Disable
7| 100%| 10min| 10min| 10%| 2Lux
8| 100%| 10min| 30min| 10%| 10Lux
9| 100%| 10min| +∞| 10%| 30Lux
A| 100%| 10min| +∞| 30%| Disable
B| 75%| 10min| +∞| 10%| 30Lux
C| 50%| 10min| +∞| 10%| 10Lux
D| 100%| 30min| +∞| 10%| 50Lux
E| 100%| 30min| +∞| 30%| Disable
F| 100%| 5s| 10s| 10%| 2Lux

Functions

  • 3.1 Tri-level Control (Corridor Function)
    Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas it requires a light change notice before switch-off. It offers 3 levels of light: 100%–>dimmed light–>off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.

  • 3.2 Lux Off Function
    The built-in daylight sensor can read ambient natural light and switch off the fixture automatically whenever artificial light is unnecessary (natural light lux level exceeds daylight threshold).
    Note: if the stand-by time is preset at “+∞”, the fixture never switches off even when natural light is sufficient.

  • 3.3 Load Indication
    The light will flash ONCE rapidly after receiving the command from the remote controller. Note: There is no load indication (the light will not flash) when button ON/OFF, POWER 100% or POWER 80% is pressed.

Installation

Warnings:

  1. Installation of the sensor involves connecting it to the mains supply. This work must be carried out by a specialist in accordance with electrotechnical regulations.
  2. Disconnect power supply before installing.
  • Ceiling mount

HYTRONIK HIM31 High Bay Dual Sense Sensor FIG 2

  • Screw to the Luminaire by conduit
  • HYTRONIK HIM31 High Bay Dual Sense Sensor FIG 3 Attach to the shade by clamp

HYTRONIK HIM31 High Bay Dual Sense Sensor FIG 4

Note : We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

Wiring Diagram

HYTRONIK HIM31 High Bay Dual Sense Sensor FIG 5

Three Options for PIR Lens and Detection Patterns

(End user can choose the suitable lens in real application for various requirements) * For single person walking across, the detection range is reduced by 1/3.

HYTRONIK HIM31 High Bay Dual Sense Sensor FIG 6

Descriptions of the

Button Functions (remote control HRC-11)

HYTRONIK HIM31 High Bay Dual Sense Sensor FIG 7

  • Permanent ON/OFF [button 1 ]
    Press button 1 to select permanent ON or permanent OFF mode. Press button 2/4 to resume automatic operation.The mode will change to AUTO Mode after power failure.

  • RESET [ button 2]
    Press button 2, all settings go back to the rotary switch settings.

  • Shift [ button 3 ]
    Press buttonB, the LED on the top left corner is on for indication. All values/settings in RED are valid for 20 seconds.

  • Auto Mode [ button 4] Press button 4 to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
    Note : the function of Semi-auto is disabled

  • Power output [ button 5] Press button 5 , the light output shifts between 80% and 100%.
    Note : the function of “Sensor off” and “Twilight” are disabled.

  • Brightness +/- [ button 6 ]
    Press button 6 to adjust the light brightness between 10%~100% Scene prog. [ zone 7 ] (One-key-commissioning)

  1. Press button “Start” to program.
  2. Select the buttons in 8“Detection range”, 9/ 10“Daylight threshold”,11“Hold time”, “Stand-by time”, “Stand-by dimming level” to set all parameters.
  3. Press button “Memory” to save all the settings programmed in the remote control.
  4. Press button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +, stand-by dimming level 30%, the steps should be as follows: Press button 7 Start, button 8 100%,10 Disable, 3 Shift, 11 5min, 3 Shift, +12+ , 30%, 7 Memory. By pointing to the sensor unit(s) and pressing 7 Apply, all settings are passed on the sensor(s).
  • Detection range [ zone 8 ]
    Press buttons in zone 8 to set detection range at 100% / 75% / 50% / 10%.

  • Daylight threshold [ zone 9 ]
    Press buttons in zone 9 to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable.
    Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button Shift 3 at first.

  • Ambient daylight threshold [ button 10 ]
    1. Press button 3 Shift, the red LED is on for indication.
    2. Press button 10 , the ambient lux level is sampled and set as the new daylight threshold.

  • Hold time [ zone 11 ]
    Press buttons in zone 11 to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
    Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button Shift 3at first.
    2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode. *To exit from Test mode, press button 2 or any button in zone 11 .

  • Stand-by time [ zone 12]
    Press buttons in zone 12 to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h /
    Note : “0s” means on/off control; “+” means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence is detected after hold-time.

  • Stand-by dimming level [ zone 13 ]
    Press buttons in zone 13 to set the stand-by dimming level at 10% / 20% / 30% / 50%.
    Note.the function of 24h / 12h / 4h / 30s are disabled.

  • Dual tech [ zone 14 ] Press buttons in zone 14 to select sensor technology. HF+PIR: Light is on when both HF and PIR sensors are activated. HF/PIR: Light is on when HF or PIR sensors are activated

  • RF mode [ zone 15 ]
    All buttons in zone 15 are disabled.

Trouble Shooting

MALFUNCTION CAUSE REMEDY CAUSE REMEDY

The fixture does not light up

| Incorrect daylight threshold setting| Adjust daylight threshold setting
Faulty fixture| Replace fixture
No power supply| Check power to sensor
Detection zone not targeted| Check detection area setting
The fixture is always on| Continous movement in the detection zone| Check detection area setting

The fixture is on when it should not

| Sudden change in temperature due to weather (wind, rain, snow) or air expelled from fans, open windows|

Adjust zone, change installation site

Hytronik Industrial Ltd. | www.hytronik.com
3rd Floor, block C, complex building, 155#, Bai’gang road south,
Bo’gang village, Xiao Jin Kou town,Huicheng district, Huizhou 516023
Tel : 86-752-2772020 Fax : 86-752-2777877

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HYTRONIK User Manuals

Related Manuals