COOPER Lighting OSW-D-010 Occupancy Sensing Wall Dimmer Instruction Manual

June 6, 2024
COOPER Lighting

COOPER Lighting OSW-D-010 Occupancy Sensing Wall Dimmer

Installation Instructions

Specifications

Technology: Passive Infrared (PIR) and Ultrasonic (US) Electrical Ratings:

  • 120/277VAC Electronic Ballast 8 amps 60Hz (LED) 120/277VAC Magnetic Ballast 8 amps 60Hz Neutral required.
  • 0-10V Dimming Control 80mA max current sink Ballast Compatibility: Compatible with magnetic and electronic ballasts (LED)
  • No Minimum Load Requirement

Time Delays:

  • Selectable 5, 10, 15, 20 (default), 30 minutes Coverage:
  • Major motion – 30×30’
  • Minor motion – 18×18’
  • Light Level Sensing: 0 to 200 foot-candles

Description

The OSW-D-010 Occupancy Sensing Wall Dimmer is a Passive Infrared (PIR) and Ultrasonic (US) motion-sensing lighting control and VSW-D-010 Vacancy Wall Dimmer are all-in-one, used for energy savings and convenience.
US Technology The sensor produces a low-intensity, inaudible sound. It detects occupancy from changes in the acoustic waves caused by motion, such as reaching for a telephone, turning a page in a book, walking into a room, turning in a swivel chair, etc. The sensor does not respond to audible sounds.

PIR Technology

The device has a segmented lens that divides the field of view into sensor zones and detects the changes in light that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.
The OSW-D sensor dimmer is intended to act as a two-scene occupancy controller. A scene consists of the relay state and the dim level target. The occupied scene is determined by the preset configuration and the unoccupied scene is determined by two settings, low-end trim and partial off Low-end trim is the minimum output power of the sensor. Partial off Delay is how long the device will remain at the low-end trim before turning off. Hold On Time is the time interval, since sensing the last motion in the occupied space, after which the sensor will initiate power savings by dimming or turning off the light.

Operating Environment

  • Temperature 32° – 104°F (0°C-40°C)
  • Relative Humidity 20% to 90% non-condensing

Housing:

  • Durable injection-molded housing
  • Polycarbonate resin complies with 94V2.

Size:

Mounting plate/strap dimensions:

  • 4.19”H x 1.73”W x 0.048”D
  • Product Housing Dimensions:
  •  2.7”H x 1.73”W x 2.19”D

Mounting:

  • Fits in a standard 3.5” deep back box
  • Can be mounted in multiple gang back box
  • Refer to NEC box calculation for properly sized mounting box

LED Indicators:

  • Red LED indicates PIR detection Green LED indicates Ultrasonic detection

TIMEOUT VALUE

  • Occupancy Coverage Pattern

  • The OSW/VSW-D-010 is designed for spaces up to 1000 square feet (92.9 m2).

  • Operation Instructions (VSW versus OSW)

  • VSW (Vacancy Only) devices will be unable to set automatic occupancy and daylight load switching behaviors.

  • Only the dimming option will be available. For a vacancy device, occupancy mode operation is initiated by a manual On/Off toggle button press on the unit.

  • Device Overview and Installation

Installation

  • The OSW/VSW-D-010 fit into a 3.5” deep backbox. It may be installed in the same manner as an ordinary wall switch.
  • Wire the OSW/VSW-D-010 as described in the wiring section
  • Mount the OSW/VSW-D-010 in the junction box

Wiring Diagram:

  • Typical Wiring Diagram (Simple 3-way Switch), Scene Dimming Allowed

  • Only one sensor can be used in a 3-way circuit with a switch. The switch will turn on/off the load only at the brightness level selected at the dimmer.

  • Constructions built before Jan 2022 may have gray wire for 0-10 dimming control present. In these cases, the installer will label the gray building wire as a 0-10 dimming wire and connect to our product’s pink 0-10V dimming control wire. Reference NFPA70 (2020 NEC), section 410.69.

Setting Scenes

User’s Preferred Behavior| Preset| Low-End Trim| Partial Off “Grace Period” Time Delay
---|---|---|---
Occ- Max Bright, Unocc – Off| 100%| | 5 minutes
Occ- Max Bright, Unocc – Very dim| 100%| 0%| Never Off
Occ- Max Bright, Unocc – 50%| 100%| 50%| Never Off
Occ- 75%, Unocc – Off| 75%|
| 5 minutes
Occ -75%, Unocc – 25%| 75%| 25%| Never Off

Installer Adjustments

Feature Setting Changes – Sequence of Operations (Refer to Fig. —Settings change procedure)

Enter Configuration Mode

  • Turn ON the light by pressing the On/Off toggle button
  • Press and hold the ON/OFF button for 5 seconds
  • LED indicator begins to blink cyan
  • Release the ON/OFF button as soon as the LED starts to blink
  • The LED continues to blink and Configuration Mode is active

Note: If the ON/OFF toggle button continues to be pushed until the LED stops blinking, the device will exit Configuration Mode and resume normal operation.

Select Settings Mode

  • Press the ON/OFF toggle button for the number of times corresponding to the desired setting
    (Refer to the table for details)

  • The LED indicator will blink Yellow for each press

  • After pressing the ON/OFF toggle button the required number of times to enter a specific Settings Mode, and waiting for 2 seconds; the LED indicator will blink Yellow for the number of times the matching button pushes
    Wait until the LED blinks the number of times desired to confirm the correct Settings Mode.

  • Change the value for the selected setting

  •  Refer to the Settings Mode Options table for details

  • Save and Exit back to Configuration Mode

Settings Mode| Number of times to Press Toggle (while in Configuration Mode)
---|---
Occupancy/Vacancy Behavior| 2 times
High-End Trim| 3 times
Low-End Trim| 4 times
Occupancy Preset| 5 times
Partial Off Time Delay| 6 times
Hold-On Time| 7 times
Daylight Switching
/ Daylight Dimming Select| 8 times
Enter Installer Mode| 9 times
Disable LED| 10 times
PIR Sensitivity| 11 times
Ultrasonic Sensitivity| 12 times
Daylight Switching Calibration| 13 times
Open-Loop Dimming Calibration| 14 times
Factory Reset| 15 times
Exit Settings Mode| Press and hold for 3 seconds
Exit Config Mode| Press and hold for 5 seconds

  • Press and hold the [ON/OFF Toggle Button] for 3 seconds to save a new value for the selected setting
  • LED indicator blinks Yellow for the same number of times as in step 2d above, indicating successful saving of feature set; the unit will go back into the configuration mode and the LED starts to blink Cyan rapidly
  • If LED blinks Red rapidly immediately after pressing and holding above, that indicates invalid feature setting entry, which cannot be saved, and the unit goes back into Configuration Mode
  • Repeat steps 2 through 4 above for one or more other features
  • Exit Configuration Mode through one of the following ways
  • Press and hold the ON/OFF toggle button for 5 seconds; the LED stops blinking and the unit exits Configuration Mode
  • Do nothing (although the LED continues to blink) and the Configuration Mode will time out after 30 seconds, and the LED stops blinking.

COOPER Lighting OSW-D-010 Occupancy Sensing Wall Dimmer-
fig6

Setting High and Low End Trim

High-end trim and low-end trim are the maximum and minimum output, respectively, allowable by the sensor. Start configuration by modifying this setting. If content with default settings, please do not adjust this setting. Proceed to
modify other settings. From Configuration Mode, press the ON/OFF toggle button 3 times and then use the raise/lower dimming buttons to adjust the maximum output. Press and hold the ON/OFF toggle button when sure this is the maximum desired output level. From Configuration Mode, press the ON/OFF toggle button 4 times, and then use the raise/lower dimming buttons to adjust the minimum desired output. Press and hold the ON/OFF toggle button when the output is at the minimum desired output level.

Settings Mode Options| 1 Button Press (Green)| 2 Button Presses (Blue)| 3 Button Presses (Yellow)| 4 Button Presses (Magenta)| 5 Button Presses (Cyan)| Other
---|---|---|---|---|---|---
Occupancy/Vacancy Behavior| Occupancy (Auto-On)| Vacancy| | | |
High-End Trim| | | | | | Use Raise/Lower to set Max
Low-End Trim| | | | | | Use Raise/Lower to set Min
Occupancy Preset| | | | | | Use Raise/Lower to set Preset
Partial Off Time Delay| Immediate turn off (Default)| 5 minutes| Match hold time| Never off| |
Hold-On Time| 5 minutes| 10 minutes| 15 minutes| 20 minutes (Default)| 30 minutes**|
Daylight Switching/Dimming Select| Daylight Switching Enabled (Default)| Open- Loop Daylighting Enabled| | | |
Enter Installer Mode| Start Mode| | | | | Enters installer mode
Disable LED| LED ON

(Default)

| LED OFF| | | |
PIR Sensitivity| High sensitivity (Default)| Low sensitivity| | | |
Ultrasonic Sensitivity| High sensitivity| Normal sensitivity (Default)| Low sensitivity| Very Low Sensitivity| Disabled|
Daylight Switching Calibration| Start Calibration| | | | | See calibration instructions
Open-Loop Dimming Calibration| Start Calibration| | | | | Use raise/lower, see instructions
Factory Reset| Cancel| Factory Reset| | | |

Not allowable in some municipalities. Consult local energy code.

Occupancy and Vacancy

Depending on the local building codes, they may require manual turn-on only. In this case, the device is said to behave in the “vacancy mode”. To configure the device for this behavior, press and hold the ON/OFF toggle button for 5 seconds until the LED indicator flashes cyan rapidly. Then release the ON/OFF toggle button. In Configuration Mode, press the ON/OFF toggle button 2 times to enter occupancy/vacancy selection. Once this selection mode is made,(after led blinks 2 times for confirmation) press the ON/OFF toggle button the number of times below to select occupancy or vacancy:

  1. Occupancy (Default for occupancy sensors, not available for vacancy models)
  2. Vacancy

To exit the occupancy/vacancy selection menu, press and hold the ON/OFF toggle button down for 3 seconds to return to Configuration Mode.

Setting the Hold-On Time

From the Configuration Mode, adjust the hold-on time settings by pressing the ON/OFF toggle button 7 times. Use the following chart to select the appropriate timeout. Press and hold the ON/OFF toggle button for 3 seconds to save settings.

Number of Button Presses Timeout Duration (minutes)
1 5
2 10
3 15
4 20 (Default)
5 30

Disable LED settings

From the Configuration Mode, press the ON/OFF toggle button 10 times to change this setting. Press and hold the ON/OFF toggle button for 3 seconds to save settings.

Number of Button Presses Setting
1 LED Enabled (Default)
2 LED Disabled

Setting the Partial Off Time Delay

  • From the Configuration Mode, press the ON/OFF toggle button 6 times to enter
  • Partial Off Time Delay settings. Use the following chart to select the desired timeout:
  • Press and hold the ON/OFF toggle button for 3 seconds to save settings.
Number of Button Presses Timeout Duration
1 Immediate turn off (Default)
2 5 minutes
3 Match hold-on time delay
4 Never turn off

Daylight Switching Operation

The system has optional daylight switching behavior that can hold the lights in the OFF state whenever there is sufficient natural light available. Daylight switching is unavailable in the vacancy mode. Daylight switching is functional after calibration. Before beginning calibration, check that there is little natural light in the area, close the blinds, and turn on the lights. To begin, enter the Configuration Mode, press the ON/OFF toggle button 8 times to enter daylight switching/dimming select mode. The sensor will flash to confirm the selection. Press the ON/OFF toggle button 1 time to select “Daylight Switching”. The LED will shine GREEN to confirm daylight switching selected. Press and hold the ON/OFF toggle button for 3 seconds to return to Configuration Mode. Then press the ON/OFF toggle button 13 times to enter daylight switching calibration settings. Press the ON/OFF toggle button 1 time, and the device will provide an LED flashing indication for the user to move away from the unit for at least 30 seconds in order to capture the ambient light level in the space. The device will enter into a daylighting test mode for 5 minutes so that when the light level exceeds the user settings, the device will turn off and when the light level is less than the user setting the device will turn on. Press and hold the ON/OFF toggle button for 3 seconds to save. The device will blink 13 times to confirm the setting.

Ultrasonic Sensitivity Adjustment Mode

First, remove the button cover to expose the ultrasonic adjustment knob. Ultrasonic Sensitivity (Green LED) – Using a small flathead screwdriver turn the potentiometer so that the arrow points UP. (Note potentiometer will not rotate 360°).

  1. Stand in different areas of the room and wave hands.
  2. If the Green LED does not turn ON, increase the ultrasonic sensitivity by turning the green potentiometer clockwise in small increments. Repeat Step 1.
  3. Stand still three to four feet away from the sensor for five seconds. With no motion, the LED should not turn ON.
  4. If the Green LED turns ON without motion or is constantly ON decrease the ultrasonic sensitivity by turning the green potentiometer counter-clockwise in small decrements. Repeat Step 3.
  5. If after adjusting the ultrasonic sensitivity knob to the lowest setting the Green LED turns on without motion, enter the Configuration Mode by pressing and holding the On/Off Toggle button. Then press the On/Off Toggle button 12 times to enter the Ultrasonic Sensitivity Adjustment Mode for more sensitivity options. Do Not adjust sensitivity higher than necessary.
  6. Upon entering the Ultrasonic sensitivity mode, press the toggle button the number of times corresponding to your desired sensitivity setting (Green = HIGH SENSITIVITY, Blue = NORMAL (DEFAULT), Yellow = LOW, Magenta = VERY LOW, Cyan = DISABLED). When finished, press and hold the ON/OFF toggle button for 3 seconds to exit Ultrasonic Sensitivity Adjustment.

Mode and to return to Configuration Mode

Number of Button Presses

1| High sensitivity
2| Normal sensitivity (Default)
3| Low sensitivity
4| Very Low Sensitivity
5| Disabled

Open-Loop Daylight Dimming Operation

  • There is an open-loop daylight dimming method that is available for the sensor. Cooper Lighting Solutions only recommends using this setting if the sensor receives most of its light from natural lighting sources and if the unit faces a nearby window within the controlled area. To configure open-loop daylighting, enter the Configuration Mode. Press the ON/OFF toggle 8 times to enter the Daylight Dim/Daylight Switch selection. The sensor will flash to confirm the selection. Press the ON/OFF toggle button 2 times to select “Open Loop Dimming”. The LED will shine BLUE to confirm daylight dimming selected. Press and hold the ON/OFF toggle button for 3 seconds to exit the Daylight Dim/Daylight Switch selection mode.
  • Press the ON/OFF toggle button from Configuration Mode 14 times to enter Open Loop Daylighting Calibration mode. Press the ON/OFF toggle button 1 time to begin daylighting calibration. While standing to the side of the sensor without blocking natural light, use the raise and lower buttons to adjust the dimming output to the desired brightness. When finished, press and hold the ON/OFF toggle button for 3 seconds to exit Open Loop Daylighting Configuration Settings Mode and to return to Configuration Mode.

Installer Mode

After completing sensor installation, you can test the sensor as per the following steps: From Configuration Mode, press the ON/OFF toggle button 9 times to select Installer Mode. The sensor will flash to confirm the selection. Press and hold the ON/OFF toggle button 1 time to start installer test mode. While the unit is in Installer Mode the occupancy timeout is 15 seconds. The unit will automatically exit Installer Mode if there is no button press for 5 minutes.

Factory Reset

To factory reset the device: from the Configuration Mode, press the ON/OFF toggle button 15 times. Wait until the LED flashes 15 times to indicate that the device is in Factory Reset Mode. Then press the ON/OFF toggle button two times to confirm the selection. The LED will shine BLUE to confirm. Press and hold the ON/OFF toggle button for 3 seconds to confirm. If Factory Reset Mode is accidentally entered, press and hold 3 seconds and the device will return to Configuration Mode. Make sure that the LED shows color GREEN before pressing and holding 3 seconds.

Troubleshooting

Issue Possible Solution
Lights won’t turn on automatically Ensure that the device is not configured

for the vacancy
Check that daylight switching was not calibrated for too low of an ambient setting

Lights won’t turn off

| Adjust PIR sensitivity to a lower setting and the ultrasonic sensor sensitivity dial to a lower setting.
Check that the Partial Off Hold Time is set to something other than “Never off.”
Lights won’t turn off or on| Check that power is applied to the sensor. LED indicator should flash when occupancy occurs.
Lights won’t go to my preset level (Occupancy Mode Only)| The device will go to preset levels after double-pressing the toggle. The device according to code cannot turn on above 50% output.
Lights won’t get brighter| Check that the high-end trim is set to its maximum position in the settings.
Lights won’t dim lower| Check that the low-end trim is set to minimum
The device will not retain my scene settings| Make sure that high and low-end trim settings are right, then adjust preset settings to the desired level.
The device abruptly dims when using the raise and lower buttons| Adjust the high and low-end trim to optimize the operating range
When adjusting the dim level, the device doesn’t respond for a long time| Adjust the high and low-end trim to remove the unresponsive operation

Wiring

CAUTION: Before installing or performing any service on a Greengate sensor, the power MUST be turned off at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes

NOTE REGARDING COMPACT FLUORESCENT LAMPS

The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.

  1. Make sure power is turned OFF at the branch circuit breaker.
  2. Wire units as shown in wiring diagrams per applicable voltage requirements.
  3. Mount unit to wall box.
  4. Turn the power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
  5. Make necessary adjustments. (See Installer Adjustments section)
  6. Install wall switch plate.

Warranties and Limitation of Liability

FCC Statement

  • This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
  • This device may not cause harmful interference.
  • This device must accept any interference received, including interference that may cause undesired operation.

The grantee is not responsible for any changes or modifications not expressly approved by the party responsible for compliance. Such modifications could void the user’s authority to operate the equipment.

The equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

This device complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment must be installed and operated in accordance with provided instructions and the antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

COOPER Lighting User Manuals

Related Manuals