ELKO ATS-2D Analog Time Switch with Daily Weekly Program
Characteristics
- The mechanical time switch is a simple and inexpensive alternative to digital time switches for controlling heating, ventilation, cooling, lighting systems or pumps depending on real-time.
- Daily or weekly program
- Selection of operating modes using the switch on the panel: switches automatically according to the set program permanently closes permanently opens
- Power reserve after power off for up to 150 hours after fully charged.
- Sealable transparent front panel cover.
Connection
Time setting – daily program
Do not turn counterclockwise
Description
- Output contact (1-2-3)
- The direction of rotation of the programming dial
- Operating mode switch
- Supply voltage terminals (4-5)
- Transparent opening cover
- Time indicator
- Sealing spot
Day/time setting – a weekly program
Do not turn counterclockwise
Example: 3 = Wednesday, 2:45 p.m.
Setting
Minimum switching interval:
- daily 30 minutes (1 segment)
- weekly 210 minutes (1 segment)
High temperatures can affect the accuracy of the time switches operating mode
Operating mode
- switches automatically according to the set program
- permanently closes
- permanently opens
Power reserve (models only ATS-2DR, ATS-2WR)
The time switch starts working approx. 5 minutes after being connected to the power supply. After approximately 72 hours from the connection to the power supply, the power reserve, reaches it´s complete charge of 150 hours.
Technical parameters
Supply
Supply terminals: | 4,5 |
---|---|
Supply voltage: | AC 230V (50/60 Hz) |
Power consumption (max.): | 1W (1.5 VA) |
Supply voltage tolerance: | -10%, +10% |
Time circuit
Program: | daily | daily | weekly |
---|---|---|---|
Number of switching segments: | 48 | ||
Minimum switching interval: | 30 min | 30 min | 3.5 hour |
Operating accuracy: | 1s/day | ||
Power reserve: | x | max. 150h |
Output
Number of contacts: | 1x switching (AgNi) |
---|---|
Rated current: | 16A/AC1 |
Breaking capacity: | 3500 VA/AC1 |
Switching voltage: | 250 V AC |
Mechanical life: | 1.000.000 operations |
Electrical life (AC1): | 50.000 operations |
Other information
Operating temperature: | -10 to +50°C (14 to 122°F) |
---|---|
Storage temperature: | -10 to +50°C (14 to 122°F) |
Dielectric strength: | 4kV (supply – output) |
Operating position: | any |
Mounting: | DIN rail EN 60715 |
Protection degree: | IP20 |
Overvoltage category: | III. |
Pollution degree: | 2 |
Max. cable size
(mm2):
| max. 1x 4, max. 2x 1.5 /
s dutinkou max. 1x 4, max. 2x 1.5 (AWG 12)
Dimensions:| 90 x 35 x 60 mm (3.5˝ x 1.4˝ x 2.4˝)
Weight:| 117 g (4.1 oz.)
Standards:| EN 61812-1, EN 60669-1, EN 63044-1
Warning
The device is constructed for connection in a 1-phase main alternating current voltage and must be installed according to norms valid in the state of the application. Connection according to the details in this direction. Installation, connection, setting, and servicing should be installed by qualified electrician staff only, who has learned these instructions and functions of the device. This device contains protection against overvoltage peaks and disturbances in supply. For the correct function of the protection of this device, there must be suitable protections of a higher degree (A, B, C) installed in front of them. According to standards elimination of disturbances must be ensured. Before installation, the main switch must be in position “OFF” and the device should be de-energized. Don´t install the device to sources of excessive electromagnetic interference. By correct installation ensure ideal air circulation so in case of permanent operation and higher ambient temperature the maximal operating temperature of the device is not exceeded. For installation and setting use a screw-driver cca 2 mm. The device is fully-electronic – installation should be carried out according to this fact. Non-problematic function depends also on the way of transportation, storing and handling. In case of any signs of destruction, deformation, non- function or missing part, don´t install and claim at your seller it is possible to dismount the device after its lifetime, recycle, or store in the protective dump.